SAL 35 Catalog

Catalog 1.1.3
Linear Diffuser
SAL 35
Dusseldorf Fair Ground, Germany
Linear diffuser
NAD Klima
SAL 35 Model
content
Description, areas of application and benefits . . . . . . . . . . . . . . . . . . . . . . . .
SAL 1
Configuration, mode of operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 2
Selection the number of slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 3
Aerodynamic data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 4
Direction of the air flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 5
Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 6
Diagram and example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 7
Dimensions and installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 8
Dimensions of the plenum with side inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 9
Dimensions of the plenum with top inlet . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL 10
End cap and connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SAL 11
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SAL12
Codification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SAL 15
1.1.3
SAL 35
C
Concordia University, Montréal, Canada
Linear diffuser
NAD Klima
Description, Areas of application and Benefits
Linear diffuser SAL 35
The SAL diffuser has linear slots with
35mm profiles. It is composed of
extruded aluminum surfaces with ABS
eccentric drums which slide inside and
are mounted on the plenum.
The SAL 35 is available with one or
multiple slots depending on the application and the required amount of air.
The elements can be mounted one after
another to create a diffusion wave.
Areas of application
- Rest areas with average ceiling
heights.
Benefits
- Adjustable without reducing the
speed of the exiting air flow thanks to
the section of variable drums.
- Areas with levels of elevated and high
- Influence (e.g. extension) on the
speed air movement.
critical airflow trajectory.
- Situations where the diffuser must
adapt to the contours and colors of
the space.
- Influence on the method of induction
(diffuse mode).
- Systems with variable flow.
- Adjustment of the penetration of the
air jet.
- Offices, conference rooms, computer
rooms, white rooms, shopping malls,
cinemas, theatres etc.
- Optional suppression of the Coanda
effect.
- Change of the direction of the jet.
- Reproductive diffusion setting.
- Factory default setting.
- Adjustment of the diffuser still
possible even after installation.
- Diffuser settings not reset during
cleaning.
Subject to technical changes. Version 14 / 04 / 2015
1.1.3
SAL 35
1
NAD Klima
Linear diffuser
Configuration and mode of operation
Controlling the direction of airflow
6
Volume flow
F
4
3
1 A
min. max.
C D
E
B
5
2
Indexing- range
1/A
F/6
6 / 5/ 4
5
3/ 22/ 1
4/3
B
B /C
C/D
E/
F
A/
D/E
Dire
ction of air flow
Configuration
1. Extruded aluminum profile
2. Extra-wide or narrow profile
3. Eccentric drums
4. Plenum
5. Air guiding blades
6. Display and adjustment dial.
The SAL linear diffuser slots are
composed of extruded aluminum (1)
with additional wide or narrow profiles
(2), the eccentric drums (3), which can
rotate 360° and a plenum (4).
The eccentric drums (3) offer an acoustic level and optimal aerodynamics,
and possess on their axis multiple air
guiding planes (5), a display and
adjustment dial (6) on which are alphanumeric characters, allowing the user
to define and reproduce the drum
settings. The profiles, with a powder
coated paint are attached to the
plenum with the aid of rivets for applications in a suspended ceiling and by
central screws for the gypsum ceilings.
2
1.1.3
SAL 35
Mode of operation
The eccentric drums form, with the aid
of the aluminum air guiding slots a flow
of optimal air.
The design of approach to the drums
causes a drop in pressure as the air
enters. As the air leaves the slot it is
stable and generates a low level of
acoustic power. The flow maintains a
powerful induction of ambient air.
The positioning of the eccentric drums
allows an adjustment of the direction
of the air jet, with or without reduction
in the exit area.
To maintain a dense airflow and maintain the direction of the air flow
perpendicular to the axis of the drums,
the drums have small plates to guide
the air.
Mode of operation
Adjustment of the air jet direction
Thanks to the shape of the eccentric
drums and adjustment dial with alphanumeric characters, the direction of the
air jet at the outlet of the diffuser can be
directed changed up to 180°. For each
direction there are two (2) drums
positions (“reduced” or “not reduced”
positions) as illustrated in the diagram
above. The direction of the jet is indicated on the diagram if the diffusers are
freely suspended. For a ceiling installation, a horizontal airflow is generated
by the Coanda effect with the drums in
positions EF, F6, 1A, AB and 21, 32, 54
and 65. The length of the drums can
each be adjusted up to 100mm.
As a result, the combinations of airflow
are almost infinite. During manufacture, the drums are normally set
alternately in position 21 and 65 (diffusion mode). This setting produces
airflow with a strong induction which
can be used even in areas with high
cooling needs and mixed air rates.
Subject to technical changes. Version 10 / 06 / 2015
NAD Klima
Linear diffuser
Selection the number of slots
Note :
To facilitate the selection of the SAL, the
total airflow must be calculated for active
slot lengths of 1m.
1400 (250)
Specifications:
Height of the air-duct:
Airflow by diffuser:
Cooling:
Heating:
Length of SAL:
1100 (200)
1360 (243)
(248)
1300 (235)
1200 (215)
H = 3.00 m
Vo = 384 m3/h
∆T = - 15°C
∆T = +15°C
L = 1500 mm
(216)
1190 (213)
(217) 1200 (215)
1000 (180)
1020 (186)
900 (160)
900 (160)
(162)
1050 (189)
960(176)
850 (155)
800 (140)
Research:
1- Airflow by metre of slot section
2- Number of slots n in cooling
750 (135)
(cfm/pi.li)
700 (125)
.
Air flow V [m / h/m]
h/m
Solution:
1 Each slot of 1500mm = 1.5m of length,
which we divide by 1.5 to find the air flow
by metre of slot : 324m3/h / 1.5 = 256
m3/h/m
The diagram “Number of slots” and in a
cooling mode we find the number of slots :
n=3
2
600 (110)
(108)
500 (90)
510 (92)
(93)
450 (81)
400 (72)
340 (62)
300 (55)
(54)
300 (55)
1
100 (18)
600 (110)
480 (86)
(88)
360 (66)
240 (44)
170 (31)
150 (27)
120 (22)
120 (22)
2
1
Number of slots
720 (132)
680 (122)
(124)
600 (110)
200 (36)
840 (154)
2
3
4
5
6
7
.
Air Flow by meter of slot of SAL 35 V0
8
m3/h/m / slot
(cfm/ li.ft / slot)
Cooling only for all ceiling heights
Heating and cooling or cooling only for ceiling heights ≤ 3.0 m
50 - 120 (10-22)
Heating and cooling or heating only for heights of 3,0 m - 4,5 m
120 - 150 (22 - 27)
Heating and cooling or heating only for ceiling heights of 4.5m – 7m *
150 - 170 (27 - 31)
* validate the sound level
If heating mode cannot be selected for the initial flow in areas with ceiling heights of 3m, reduce the
length of the slots Ls to the recommended length.
.
V
.
Vmax
Angle of the direction of airflow
Air volume flow ratio
[°]
.
V
.
Vmax
3
2
1
Drum position
A
B
C
Subject to technical changes. Version 29 / 05 / 2015
D
E
F
6
5
Outlet airflow
The diagram below shows the ratio
between the airflow exiting the diffuser
and the drum position; the pressure of
the system remains unchanged. On the
other hand, through an increase of
pressure upstream, the speed of exiting
air can be noticeably increased while
maintaining the same airflow even with
the drum in the “reduced” setting.
4
1.1.3
SAL 35
3
NAD Klima
Linear diffuser
Aerodynamic data
( Slot length Ls = 1 m)
V˙
[m / h/m]
∆p
[Pa]
345
430
535
6
V˙
[m / h/m]
∆p
[Pa]
y
[m]
9
13
20
370
450
550
13
19
28
3.3
4.3
5.5
400
500
600
8
12
17
435
525
620
13
18
25
3.6
4.6
5.7
7
460
570
680
8
12
16
495
600
710
12
17
24
3.9
5.0
6.2
8
510
635
785
7
11
17
550
650
810
11
16
24
4.1
5.0
6.7
Size
[-]
LWA
[dB(A)]
Minimum
spacing [m]
x crit
[m]
Specification :
The minimum space for a 3m high sub-ceiling with air speeds in the occupied zone should not exceed 0.2m/s
Penetration of the vertical jet in heating mode + difference in temperature °C in cooling ∆T = - 8°C:
The blue column: Setting the drums to diffuse 1A/F6 (horizontal jet)
The red column: Setting of the drum in CD (vertical jet).
4
1.1.3
SAL 35
Subject to technical changes. Version 14 / 04/ 2015
NAD Klima
Linear diffuser
Controlling the direction of the air jet
The setting produces airflow with
strong induction which can be adjusted
to the cooling or heating needs of the
room in areas with high airflow.
When all of the drum of the first slot are
adjusted to 2 1 and in the second slot
are adjusted to 6 5, the adjustment
produces a flow in two directions
(divergent).
The diagrams below illustrate the
different relationships between the
position of the eccentric drums and the
direction of the air jet at the outlet of
the drum.
Examples of application
BC / 6 5
Diffuse
DFL
BC/EF
Diffuse
DFE
21/65
Diffuse
DFS
AB/EF
Diffuse
DFF
Notes :
The adjustable side of the drum
must be to the left of the collar.
BC/65
Diffuse
DFL
1.8 m
(6 ft)
BC/EF
Diffuse
DFE
1.8 m
(6 ft)
max. 3 m (10 ft)
As a result, the combinations of airflow
are almost infinite. For the diffusion
mode, the drums must be set alternately to the configuration illustrated in
the diagram in positions 2 1 and 6 5.
It doesn’t matter if multiple slots are
mounted parallel to one another; any
airflow or direction of air can be achieved through different drum combinations.
max. 4 m (13 ft)
Due to the zone of low air pressure and
the level of the eccentric drums, the
direction of the air flow can be altered
by up to 180°.
During assembly the NAD label
must always be placed on the same
side as the collar of the plenum.
max. 6 m (20 ft)
When the air inlet is on the top or
a wall installation, follow the
directions on the workshop design.
Indexing
Range
Volume Flow
min. max.
CD
Divergent
DVV
BC/DE
Diffuse
DFH
CD
Divergent
DVV
1.8 m
(6 ft)
Air jet on one side
Air
inlet
collar
C D / AB
Diffuse
DFN
C D / AB
Diffuse
DFN
1.8 m
(6 ft)
Drums at 2 1
Subject to technical changes. Version 28 / 05 / 2015
Drums at 6 5
1.1.3
SAL 35
5
NAD Klima
Linear diffuser
Diagrams
·
Air flow V
cfm/pi.li. slot
m3/h/m slot
V max =
V max Diagram *k
Drum position
9
7
11
13
14
16
18
Standard
22
27
Number of slot
All
example
All 1A or
All F6
CD
See example on page 7 1
m3/h/m slot
cfm/pi.li. slot 7
·
Air flow V
Airflow distance after meeting y [m]
9
11
13
14
16
18
22
27
3
Airflow distance x [m] with 1A, F6 (diffuse)
4
x
x
irfl
A
x
y
ymax
Vertical : all C D
x crit
6
1.1.3
SAL 35
ve
,
5
x crit [m] Airflow distance with 1 A, F 6 (diffuse)
6
ow
ymax [m] Airflow distance with CD
2
ax
yv m
it
loc
Subject to technical changes. Version 29 / 05 / 2015
Linear diffuser
NAD Klima
Diagram
Example
Loss of pressure / Level of acoustic power
Example
Drum position
Specifications:
- 4 diffusers installed in a series of
3 slots each:
SAL 35 - 1500 - 3
- Total airflow :
1535 m³/h
- Cooling mode:
∆T = - 15 °C
- Heating mode:
∆T = + 15 °C
- Width of space:
4m
- Length of space:
8m
- Height of space:
2.74 m
- Head height:
1.8 m
CD
21
Research :
1. Air flow by metre of slot
2. Maximum airflow speed in occupied
zone Vmax
3. Critical distance in cooling mode
Xcrit ?
4. Acoustic pressure LWA ?
5. Loss of pressure ∆P t ?
2. From the sizing diagram, a wall
distance x=2m 2 and a trajectory
after they meet y=3m – 1.8m = 1.2m, 3
we can find the maximum air speed
in the occupied zone of :
Vmax=0.25m/s 4
3. For the cooling mode of -15°C, 5 we
can determine the critical distance
Xcrit = 8.5m 6
4. The acoustic power diagram and
airflow by metre of slot of 85m3/h/m
we read the acoustic power diagram
LWA = 28 dB(a). 7
From the values shown in the table
we calculate the level of power
generated: LWA = LWA diagram + I =
28+4.7+7.8 = 40.5 dB(A)
40.5 dB(A) - 10 dB(A)= 30.5 dB(A)
5. For an airflow by metre of 85 m³/h/m
slot we read: ∆P t = 13 Pa 8
Subject to technical changes. Version 29 / 05 / 2015
8
m3/h/m slot
cfm/pi.li. slot
·
Air flow V
et
65
7
Pressure loss ∆p t [Pa]
Solution:
1. For a total air flow of 1535m3/h and 4
SAL35 diffusers, we find:
1535 X 4 = 384 m3/h by diffuser.
We divide by the number of slots:
384 m³/h ÷ 3 = 128 m³/h.
Each slot of 1500mm = 1.5m in
length, we divide by 1.5 to find the air
flow per metre of slot:
128 m³/h ÷1.5 = 85 m³/h/m 1
5
et
)]
(A
L WA
9
11
Number of slot 1
k [dB] 0.0
13
2
3.0
14
3
4.7
1
4
6.0
18
5
7.0
B
[d
22
6
7.8
25
7
8.4
8
9.0
29
9
9.5
10
10.0
How to determine the diffusion length
Diffusers installed in parallel
The lenght of diffusion: 3 m
Diffusers installed in series
The lenght of diffusion : 9 m
Lenght
of
diffusion
I [dB(A)]
1
0.0
2
3.0
3
4.7
4
6.0
5
7.0
6
7.8
7
8.4
8
9.0
9
9.5
10
10.0
3m
3m
3m
3m
Important :
The absorption of the room is not accounted for.
For a comparison with North American values,
reduce the acoustic power by 10.
1.1.3
SAL 35
7
NAD Klima
Linear diffuser
Dimensions and Installation
Wide or narrow diffuser slots made of
extruded aluminum surfaces with ABS
eccentric drums.
32
32
32
32
35
58
The diffuser is also available with a
made to measure steel plate (p.13)
Available dimensions L(mm)
300, 400, 500, 600, 700, 800, 900, 1000,
1100, 1200, 1300, 1400, 1500, 1600,
1700, 1800, 1900, 2000 Intermediate
dimensions available.
One-slot SAL profile
with narrow profile
A combination of multiple standard
lengths allows the creation of a diffuser
of the desired length. The connection,
which is invisible, is made with pins
(p.13).
One-slot SAL profile
with wide profile
65
65
65
65
68
91
Two-slot SAL profile
with narrow profile
Two-slot SAL profile
with wide profile
Mounting and suspension for a gypsum ceiling
3
6
4
C D
E
B
14
F
1 A
14
5
Attach it with the screws which are provided for
this purpose. Suspension of the plenum is achieved
with the help of hooks and a threaded rod M4 – M5.
(not supplied)
2
The balancing key (optional) is adjustable per
the diffuser.
Position and fix the plenum and ensure the inlet
opening of the diffuser is level with the ceiling,
by simply pressing the diffuser inlet.
H
H
ØD
Screw to fix
the diffuser
ØD
Spring
balancing
damper
(optional)
Gypsum
3 2
B
F 6
4
1 A
.
58
5
gypsum 5/8”
C
D E
Opening in the gypsum
8
1.1.3
SAL 35
Subject to technical changes. Version 14 / 04 / 2015
Linear diffuser
NAD Klima
Dimensions
Plenum with top inlet and wide profiles
SAL 35, 1 row
SAL 35, 2-row
D
D
D
50
14
SAL 35, 3 rows and more
50
14
50
14
B
Perforated
plate
H
Perforated
plate
H
H
Perforated
plate
B
F
E
91
PS (with cover profiles)
PL (with support profiles)
58
Note: The measurements are indicated in the table on pages 10 and 11
Plenum with side round inlet and wide profiles
SAL 35, 2-row
SAL 35, 3 rows and more
14
14
B
Spring
Balancing Damper
(optional)
B
ØD
Perforated
plate
H
H
H
ØD
Radial
Blade Damper
(optional)
Grillage
14
ØD
SAL 35, 1 row
F
E
58
90.5
PS (with cover profile)
PL (with support profile)
Note: The measurements indicated in the table on pages 10 and 11
are for a plenum with the inlet on the side and support profile.
Subject to technical changes. Version 15 / 04 / 2015
1.1.3
SAL 35
9
NAD Klima
Linear diffuser
Dimensions
SAL 35, 1-row with plenum
Dimensions [mm]
Size B
Size H
from 650
to 900
88
88
286
Size E
286
26
Size F
26
32
Size PS
32
Size Ø D
side
top
Air inlet (Qty)
from 950 from 1550
to 1500
to 2000
88
286
26
32
Size B
Size H
120
120
120
120
286
342
342
342
342
26
Size E
58
58
58
58
32
Size F
65
65
65
65
68
68
68
68
91
91
91
91
side
150
200
200
200
top
150 (oval)
200 (oval)
200 (oval)
200 (oval)
1
1
1
2
35
58
58
58
58
Size PL
125
125
150
125
125 (oval)
125 (oval)
150 (oval)
125 oval)
1
1
1
2
from 650
to 900
152
152
342
90
96.5
from 950 from 1550
to 1500
to 2000
152
342
90
96.5
from 950 from 1550
to 1500
to 2000
184
184
184
184
342
Size H
392
392
392
392
90
Size E
122
122
122
122
96.5
Size F
130
130
130
130
133
133
133
133
155
155
155
155
side
200
200
250
250
top
200 (oval)
200 (oval)
250 (oval)
250 (oval)
1
1
1
2
98
98
122.5
122.5
122.5
122.5
Size PL
side
150
200
250
200
top
150 (oval)
200 (oval)
250 (oval)
200 (oval)
1
1
1
2
Size Ø D
Air inlet (Qty)
SAL 35, 6-row with plenum
from 300
to 600
from 650
to 900
Size B
216
216
216
216
Size H
392
392
392
Size E
154
154
Size F
162
Size PS
Size PL
1.1.3
from 650
to 900
Size B
98
from 950 from 1550
to 1500
to 2000
from 950 from 1550
to 1500
to 2000
from 300
to 600
from 650
to 900
Size B
248
248
248
248
392
Size H
392
392
392
392
154
154
Size E
187
187
187
187
162
162
162
Size F
195
195
195
195
165
165
165
165
Size PS
198
198
198
198
188
188
188
188
Size PL
221
221
221
221
side
200
250
302
250
side
200
250
302
250
top
200 (oval)
250 (oval)
302 (oval)
250 (oval)
top
200
250 (oval)
302 (oval)
250 (oval)
1
1
1
2
1
1
1
2
Dimensions [mm]
10
from 300
to 600
152
SAL 35, 5-row with plenum
Air inlet (Qty)
Dimensions [mm]
98
Air inlet (Qty)
Size Ø D
Air inlet (Qty)
Size PS
v PL
Cote Ø D
Size Ø D
SAL 35, 4-row with plenum
from 300
to 600
96.5
Size PS
from 950 from 1550
to 1500
to 2000
Size H
35
90
Size F
from 650
to 900
Size B
35
342
Size E
from 300
to 600
88
SAL 35, 3-row with plenum
Dimensions [mm]
Dimensions [mm]
Size PS
35
Size PL
SAL 35, 2-row with plenum
from 300
to 600
SAL 35
Dimensions [mm]
Size Ø D
Air inlet (Qty)
Subject to technical changes. Version 14 / 04 / 2015
Linear diffuser
NAD Klima
Dimensions
SAL 35, 7-row with plenum
SAL 35, 8-row with plenum
from 300
to 600
from 650
to 900
from 300
to 600
from 650
to 900
Size B
280
280
280
280
Size B
Size H
392
392
457
312
312
312
312
392
Size H
Size E
219
219
392
392
457
392
219
219
Size E
Size F
226
251
251
251
251
226
226
226
Size F
Size PS
259
259
259
259
229
229
229
229
Size PS
Size PL
262
262
262
262
252
252
252
252
Size PL
286
286
286
286
side
200
250
353
250
side
250
302
353
302
top
200
250
353 (oval)
250
top
250
302 (oval)
353 (oval)
302 (oval)
1
1
1
2
1
1
1
2
Dimensions [mm]
Size Ø D
Air inlet (Qty)
from 950 from 1550
to 1500
to 2000
from 650
to 900
Size B
344
344
Size H
392
392
Size E
283
283
Size F
291
291
Size PS
294
294
Size PL
317
317
side
250
302
top
250
302
1
1
Air inlet (Qty)
from 950 from 1550
to 1500
to 2000
SAL 35, 10-row with plenum
from 300
to 600
Size Ø D
Size Ø D
Air inlet (Qty)
SAL 35, 9-row with plenum
Dimensions [mm]
Dimensions [mm]
from 950 from 1550
to 1500
to 2000
Dimensions [mm]
from 300
to 600
from 650
to 900
from 950 from 1550
to 1500
to 2000
344
344
Size B
376
376
376
376
457
392
Size H
392
392
457
392
283
283
Size E
315
315
315
315
291
291
Size F
334
334
334
334
294
294
Size PS
337
337
337
337
317
317
Size PL
350
350
350
350
353
302
side
250
302
353
302
353 (oval)
302
top
250
302
353 (oval)
302
1
2
1
1
1
Subject to technical changes. Version 14 / 04 / 2015
Size Ø D
Air inlet (Qty)
1.1.3
2
SAL 35
11
Linear diffuser
NAD Klima
Dimensions
Total length with end cap
(mm)
Nominal
size
PLP/PSP
PLL/PLR
PL2
PSR/PSL
PS2
298
398
497
573
696
795
895
994
1093
1183
1292
1392
1491
1590
1690
1789
1889
1988
313
413
512
588
711
810
910
1009
1108
1198
1307
1407
1506
1605
1705
1804
1904
2003
328
428
527
603*
726
825
925
1024
1123
1213*
1322
1422
1521
1620
1720
1819
1919
2018
300
400
499
575
698
797
897
996
1095
1185
1294
1394
1493
1592
1692
1791
1891
1990
302
402
501
577
700
799
899
998
1097
1187
1296
1396
1495
1594
1694
1793
1893
1992
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
* Dimensions modified for insertion into a suspended ceiling
PL2, PLR, PLL
15 mm
15 mm
PS2, PSR, PSL
2 mm
2 mm
PLP, PSP
12
1.1.3
SAL 35
Subject to technical changes. Version 18 / 06 / 2015
Linear diffuser
NAD Klima
End caps and connectors
PS with narrow profile
2 mm
flat end cap
2 mm
PS2 : with flat end cap on both sides
PSR : with flat end cap on right side
PSL : with flat end cap on left side
2 mm
PL with wide profile (”L”)
End cap in
« L » shape
15 mm
15 mm
15 mm
PS2: with wide end on both sides
PSR: with wide end on the right side
PSL: with wide end on the left side
APA for the steel plate (made to measure
Note : it is essential to write the
overall dimensions you need
(in mm) of the steel plate
in annotation.
Connectors (pull pins)
Connectors (pull pins)
The connection between
diffusers is made with the aid of
pins (included) when needs
indicate that more than one
diffuser in length is required.
PLL
PLP
PLR
Left
Middle
Right
Subject to technical changes. Version 14 / 04 / 2015
1.1.3
SAL 35
13
NAD Klima
Linear diffuser
Specifications
1 - Description and physical characteristics
2 - Performance
1.1 The NAD Klima SAL 35 ceiling air diffuser is composed of
extruded aluminum blades with one, two or multiple slot
combinations. A width of 35mm and with plastic (ABS)
eccentric drums in either matte black or white.
2.1 The SAL 35 diffuser assures a strong rate of induction
even in highly variable areas in order to maintain an
acceptable temperature differential in the air jet. That is
to say, the difference between the designated temperature and the temperature of the air projected by the
diffuser into the occupied zone.
1.2 The 100mm long NAD Klima eccentric drums are individually adjustable with an alphanumeric codification and
can be rotated through 360°. Accordingly the diffuser
remains fully adjustable throughout the range of diffusion
(in height and through 180°).
1.3 The diffuser is supplied with a wide or narrow profile.
2.2 The performance of the SAL 35 diffuser is guaranteed by
a software simulation which indicates the loss of
pressure and the acoustic power generated. It also
provides a cross-sectional view of the critical trajectory
of the air and the nominal speed in the occupied zone in
cooling mode, in heating mode and isothermal mode at
1.8m from the ground or at the request of the engineer.
3 - Adjustment
3.1 The diffuser includes a plenum provided by the manufacturer. The plenum is made from 24 gauge galvanised
steel and comprises suspension points at the four
corners. The inlet collar can be centred on the side and
adapted to the air flow. The interior joints of the plenum
are sealed with silicon.
3.2 The SAL 35 diffuser includes a perforated airflow
stabilizing (equalizing) frontal plate.
4 -Balancing
4.1 The balancing must be executed by a ventilation
balancing technician with a recognised professional
certification.
4.2 The technician must take into account the factor of
correction for the volume of air using a balometer (factor
FCB).
5 - Certification
5.1 The linear diffuser SAL 35 meet the standard of ASTME
162 "Surface Flammability of Materials Using a Radiant
Heat Energy Source"
6. Required quality : NAD Klima SAL 35 model.
14
1.1.3
SAL 35
Subject to technical changes. Version 04 / 06 / 2015
Conference room, Germany
TPSGC, Québec, Canada
NAD Klima
Linear diffuser
Codification
Product
SAL 35
0300, 0400, 0500, 0600, 0700, 0800, 0900, 1000, 1100, 1200, 1300, 1400, 1500, 1600, 1700, 1800, 1900, 2000
Number of slots
1, 2, 3, 4, 5, 6, 7, 8, 9, 10
DFS
DFL
DFH
DFE
DFF
DFN
=
=
=
=
=
=
Standard diffuse 21 / 65
Window diffuse B C / 65
Diffuse height BC / DE
Diffuse window (max. 4 m) BC / EF
Diffuse AB / EF
Diffuse CD / AB
PL2 =
PLL =
PLR =
PLP =
PS2 =
PSL =
PSR =
PSP =
APA =
DVB
DVD
DVM
DVV
DVS
DRB
= Divergence 21
= Divergence 65
= Wall divergence DE (jet towards the ceiling)
= Vertical divergence CD
= Divergence 21 / 65
= Divergence with jet nozzles
Wide profile with end cap in “L” shape on both sides
Wide profile with end cap in “L” shape on left side
Wide profile with end cap in “L” shape on right side
Wide profile without an end cap (with pins)
Narrow profile with flat end cap on two sides
Narrow profile with flat end cap on left side
Narrow profile with flat end cap on right side
Narrow profile without end cap (with pull pins)
With a steel frontal plate * (Write the dimensions you need (in mm) in annotation)
W = White drums or white nozzles (RAL 9003)
C = Cream drums or cream nozzles (RAL 9010)
B = Black drums or black nozzles
9003 =
9010 =
00SB =
00SM =
_____ =
Length of diffuser
White
Cream
Solar black (Standard matte black )
Matte silver (Standard metallic gray )
RAL color (indicate the number of the colour)
S = Plenum with inlet on the side
T = Plenum with inlet on the top
X = Without plenum
I = With acoustic insulation
A = With closed cell acoustic insulation
X = Without insulation
F = With fireproof insulation and fireproof dampers
X = Without fireproof insulation and fireproof dampers
D = With spring damper
R = With radial damper **
X = Without damper
G = Gypsum ceiling
W = Wall
X = Suspended ceiling
SAL 35 - 0300 - 1 - DFS - PL2 - B - 9003 - S - X - X - X - X
Annotation
Airflow
Profile
and end cap
Colour of the drums
and nozzles
Diffuser colour
Plenum
Acoustic insulation
Fireproof insulation
Balancing damper
Type of installation
Example
Notes :
* For the APA model, it is essential to indicate the overall dimensions of the steel plate you need (in mm), in annotation.
** Not available on oval collar
Subject to technical changes. Version 14 / 04 / 2015
1.1.3
SAL 35
17
w w w.na dk l ima. co m
NAD Klima 144 Léger St, Sherbrooke Québec, Canada J1L 1L9 • T : 819 780-0111 - 1 866 531-1739 - F : 819 780-1660 • info@nadklima.com