OM-5-2014 OPERATIONAL MANUAL for the CERTIFICATION

OM-5-2014
Published February 2014
OPERATIONAL MANUAL
for the
CERTIFICATION
of
AIR HANDLING UNITS
OM-5-2014
Published February 2014
Supersedes OM-5-2012 (Dec. 2012)
Editing (date):
Checking (date):
Approval (date):
Sylvain Courtey
Jean Fourcroy
Compliance Committee for AHU
CPPC
21 October 2013
16 October 2013
8 November 2013
25 February 2014
1 March 2014
Comes into effect from:
Modifications as against last version:
.
No.
1
2
3
4
5
6
7
Modifications
Editorial changes following the merge between Eurovent Certification Company and Certita
Deadline for real units delivery is set at 6 months after selection during the qualification test
campaign;
Cases of force Majeure are described.
Consistency check of HRS has been updated according to Decision 6 of the Compliance
Committee meeting held on 22 March 2013.
Insulation material (wool vs foam): density out of - 25%, conductivity out of + 15%
Failure treatment for model box test is added.
In case the real unit cannot reach the lowest class defined in the relevant standard (see RS
6/C/005) the participant is suspended until a re-design of the model box is done and a re-test is
successfully performed.
8
The list of major and minor non-conformities is listed in 0.
9
Mandatory information to be found on printouts has been added
10
The diploma number shall be displayed on the label
11
12
Handling of several ranges
Explanations on construction variations of AHU Model Boxes have been added.
Section
Page
All document
IV.6
9
IV.4
7
IV.5
8
Table 1
IV.12.b
10
12-13
IV.12.b
13
IV.15
13
31
16
0.
APPENDIX A
APPENDIX
B.II.2
0.
APPENDIX F
This document is strictly reserved for use in the Eurovent Certified Performance
Programmes. Reproduction or translation of any part of the document is forbidden without
written permission from Eurovent Certita Certification.
Published by Eurovent Certita Certification SAS
53 rue de Turbigo
75003 Paris, FRANCE
Tel: + 33 1 49 96 69 80
Fax: + 33 1 49 96 45 10
E-mail: s.courtey@eurovent-certification.com
AHU, OM-5-2014
Published February 2014
Page 2 of 36
19
31
35
TABLE OF CONTENTS
I.
II.
III.
PURPOSE _______________________________________________________________ 5
SCOPE __________________________________________________________________ 5
BASIC OUTLINE OF THE PROGRAMME ______________________________________ 5
III.1
III.2
III.3
III.4
IV.
Preapplication ......................................................................................................................................5
Qualifying procedure ...........................................................................................................................5
Repetition procedure ...........................................................................................................................5
Failure treatment .................................................................................................................................6
OPERATION OF THE PROGRAMME __________________________________________ 6
IV.1
Declaration of data ..............................................................................................................................6
a.
b.
c.
Rated performance data ................................................................................................................................... 6
Certification forms ............................................................................................................................................. 6
Modifications to the range ................................................................................................................................. 6
IV.2
IV.3
IV.4
IV.5
Preapplication procedure ....................................................................................................................7
Software ..............................................................................................................................................7
Factory visits........................................................................................................................................7
Consistency check of heat recovery ...................................................................................................8
a.
b.
c.
Manufacturer uses Eurovent certified heat recovery systems (HRS)................................................................ 8
Manufacturer does not use Eurovent certified HRS .......................................................................................... 8
For certified and non-certified rotors ................................................................................................................. 9
IV.6
IV.7
IV.8
IV.9
IV.10
IV.11
Qualifying campaign ............................................................................................................................9
Repetition campaign ............................................................................................................................9
Ranges to be taken out of production ...............................................................................................10
Selection of units for tests .................................................................................................................10
Ranges produced in several production places ................................................................................11
Procedures at the laboratory .............................................................................................................11
a.
b.
c.
General ........................................................................................................................................................... 11
Test conditions................................................................................................................................................ 11
Test report and tests results ........................................................................................................................... 12
IV.12 Failure treatment ...............................................................................................................................12
a.
b.
c.
d.
e.
f.
Component failure .......................................................................................................................................... 12
Unit failure on a real unit ................................................................................................................................. 12
No class reached during RU tests .................................................................................................................. 12
Unit failure on a Model Box ............................................................................................................................. 13
Failure in case of multiple production places .................................................................................................. 13
Irregularities in production places ................................................................................................................... 13
IV.13 Special complaint procedure .............................................................................................................13
IV.14 Brand Name ......................................................................................................................................13
IV.15 Non-respect of procedures ................................................................................................................14
V.
PROMOTION OF THE PROGRAMME ________________________________________ 14
V.1
V.2
By Eurovent Certita Certification .......................................................................................................14
By the Participant ..............................................................................................................................14
a.
b.
On printouts .................................................................................................................................................... 14
On units .......................................................................................................................................................... 15
APPENDIX A.
APPENDIX B.
18
B.I.
B.II.
SELECTION SOFTWARE MANDATORY REQUIREMENTS ______________ 16
EUROVENT CERTIFIED PERFORMANCE MARK AND ENERGY EFFICIENCY LABEL
Eurovent Certified Performance mark ...............................................................................................18
Eurovent Certified Performance energy efficiency label ...................................................................19
B.II.1. For units (eventually on printouts)................................................................................................................... 19
B.II.2. For printouts.................................................................................................................................................... 19
APPENDIX C.
C.I.
C.II.
CERTIFICATION SCHEDULE______________________________________ 20
Application and test schedule............................................................................................................20
Checking of software schedule .........................................................................................................22
AHU, OM-5-2014
Published February 2014
Page 3 of 36
APPENDIX D.
D.I.
FORMS _______________________________________________________ 23
Submittal for certification by Manufacturer ........................................................................................23
D.I.1. Form AHU-1A: Data list of certified models & sizes ........................................................................................ 23
D.I.2. Form AHU-1B: Data list of certified model boxes, or casing constructions ..................................................... 23
D.II.
Submittal for certification by Brand Name .........................................................................................23
D.II.1.
D.II.2.
Form AHU-2A: Data list of certified models & sizes (BN) ........................................................................... 23
Form AHU-2B: Data list of certified model boxes, or casing constructions (BN) ........................................ 23
D.III. Technical forms .................................................................................................................................24
D.III.1.
Form AHU-3A: Technical specification related to tested real unit ......................................................... 24
D.IV. Test result forms ................................................................................................................................28
D.IV.1.
D.IV.2.
D.IV.3.
APPENDIX E.
Form AHU-4A: Evaluation of mechanical, thermal and acoustical tests ................................................ 28
Form AHU-4B: Recalculation after Real Unit Test ................................................................................ 28
Form AHU-4C: Software Update Record Sheet .................................................................................... 30
MAJOR / MINOR NON COMPLIANCES ______________________________ 31
E.I. Handling of several ranges................................................................................................................31
E.II. Major Non-Compliances (2 Points) ...................................................................................................32
E.III. Minor Non-Compliances (0 Points) ...................................................................................................34
APPENDIX F.
F.I.
F.II.
F.III.
F.IV.
CONSTRUCTION VARIATIONS OF AHU MODEL BOXES_______________ 35
Corner post (corner and frame) .........................................................................................................35
Mullion ...............................................................................................................................................35
Filter construction ..............................................................................................................................36
Panel shape.......................................................................................................................................36
AHU, OM-5-2014
Published February 2014
Page 4 of 36
I.
PURPOSE
The purpose of this manual is to prescribe procedures for the operation of the Eurovent Certified
Performance Programme for Air Handling Units, in accordance with the Eurovent Certified
Performance Certification Manual.
II.
SCOPE
This programme applies to selected ranges of Air Handling Units. Each range shall at least present
one size with a rated air volume flow below 7 m 3/s. All Real Unit sizes in the range up to the
maximum stated air flow shall be declared. All Model Box configurations shall be declared.
Ranges without at least one size with a rated air volume flow below 7 m 3/s (25 000 m3/h) are
excluded.
III. BASIC OUTLINE OF THE PROGRAMME
III.1 Preapplication
Before the licence agreement is signed between the company and Eurovent Certita
Certification, the preapplication procedure shall be completed.
The company shall first submit to Eurovent Certita Certification name of the range and
complete list of names and versions of the corresponding selection tools (selection softwares)
for verification by an auditor appointed by Eurovent Certita Certification. If the software fulfils
all preliminary requirements, the company shall submit to Eurovent Certita Certification the
complete list of factories where the range is produced for verification by an auditor appointed
by Eurovent Certita Certification. If the software and the factory fulfil all the preliminary
requirements, the company is entitled to sign the Licence Agreement.
III.2 Qualifying procedure
After signing the Licence Agreement, the Applicant shall submit to Eurovent Certita
Certification the declaration list with all Real Unit (RU) sizes and Model Box (MB)
configurations with all the required characteristics and performance data as required by the
Rating Standard, RS 6/C/005.
The following number of units per factory producing the range (except the case of “sister
factories”, see IV.10) are then required for test in an independent laboratory selected by
Eurovent Certita Certification:
 The minimum number of Model Boxes to cover all worst configurations of the
mechanical, thermal and acoustical performance. If several ranges use the same
construction, the corresponding unit will be tested only once.
 One complete Air Handing Unit, being one size from the range, for all performance. The
Real Unit is selected during the factory visit by the auditor appointed by Eurovent Certita
Certification.
For units above the stated air flow rate of 7 m3/s, the software shall be checked for
consistency. If the tests show conformity with the relevant Rating Standard and consistency is
verified, certification is granted until next annual on-site checking of software.
III.3 Repetition procedure
For mechanical, thermal and acoustical testing, Model Boxes shall be tested every six years
for ISO-certified factories, every three years otherwise. For performance testing, a Real Unit
from recent regular production shall be tested, every three years for ISO-certified factories,
AHU, OM-5-2014
Published February 2014
Page 5 of 36
every year otherwise. If several factories produce exactly the same range with the same
components, suppliers and methods, one unit is sufficient instead of one per factory. In
addition, annual onsite checking of software shall be carried out every year. When the
repetition procedure is passed certification is renewed for another campaign.
III.4 Failure treatment
When a unit fails to comply with the requirements of the relevant Rating Standard, failure
treatment shall be applied.
IV. OPERATION OF THE PROGRAMME
IV.1 Declaration of data
Each manufacturer shall nominate one contact person who will deal with all certification
matters, plus eventually one by factory.
a.
Rated performance data
All characteristics shall be expressed in SI Units.
b. Certification forms
Submittal of certification of models shall be completed and sent to Eurovent Certita
Certification as .xlsx files. Copies of these forms are part of this manual (see APPENDIX
D).
Original Equipment Manufacturer (OEM): Form AHU-1A for Real Units and Form AHU-1B
for Model Boxes will be used.
Brand Name: For models submitted by a company presenting on the market units, under
its own brand, manufactured by a certified company, forms AHU-2A and AHU-2B will be
used to identify the corresponding model number of the OEM.
Technical forms: For models selected for test, Forms AHU-3A and AHU-3B have to be
completed with technical description of all components along with characteristics and
performance data.
Evaluation of test result: For models tested, Forms AHU-4A is added to the test report
and AHU-4B is sent by Eurovent Certita Certification, showing the deviations between
claimed and measured data.
c.
Modifications to the range
The Participant shall inform Eurovent Certita Certification and the auditor of any
modification to the range and/or software, using Form AHU-5. A new software version
without impact on performance does not have to be sent. If new components (fans, coils
etc) are implemented in standard production, manufacturer shall inform Eurovent Certita
Certification and provide new software to the auditor. For next test new components shall
be selected.
Non compliance is considered as a non-respect of procedures (see IV.14).
Anytime, Eurovent Certita Certification has the right to perform extra checking of
software. Eurovent Certita Certification decides whether the modification is significant for
the certified performance data or not. In the case of significant modifications Eurovent
Certita Certification is entitled to demand adequate tests to verify the influence on
performance data. This test shall not be considered as a repetition one.
AHU, OM-5-2014
Published February 2014
Page 6 of 36
IV.2 Preapplication procedure
During the preapplication procedure, the auditor appointed by Eurovent Certita Certification
shall first verify that the software fulfils minimum requirements (no certification shall be
accepted without appropriate selection software). If yes, he shall visit the factory, verify that
AHUs are really manufactured there and selected with the software, and send a report of his
visit to Eurovent Certita Certification. If the report shows that rules are not followed the Licence
Agreement shall not be signed.
IV.3 Software
An English version of the software selection is necessary. Each quotation of a certified AHU
shall include the date/code/number of the software version used for the selection of the unit.
From the version code-key it shall be possible to check what the latest technical software
version is by splitting up the code in more characters. An example of a suitable code is given
below:
Version: XY / Z
characters indicating a version serial number,
not affecting the selection results
characters to indicate the technical version serial number
The participant is obliged to send the most recent technical software version to Eurovent
Certita Certification.
The selection software shall be operative as an entity with all unit components integrated in
one software. Components in an AHU that are selected with different software or any other
means of selection cannot be certified. The units of the applied range shall be built with
components specified in the selection software. If some components not present in the
certified software performing a certified performance item (see VI.2 of Rating Standard) are
included in the technical specification of a particular order, the following statement shall be
provided in the quotation: “This component is not included in the software Eurovent certified”.
This statement is not required for components serving for non-certified performance items (see
list on VI.2 of RS 6/C/005).
At least four sections must be included: fan, filter, heating and cooling. When a heat recovery
section is available, it shall be declared and included in the selected unit for test for
certification.
Consistency of the software shall be verified by the auditor appointed by Eurovent Certita
Certification. In case inconsistency of the software is observed, failure treatment shall be
applied.
Anytime, Eurovent Certita Certification has the right to collect data directly from customer and
perform extra checking of software.
IV.4 Factory visits
Before each visit the auditor appointed by Eurovent Certita Certification shall collect and study
the construction details and claimed performance of the relevant AHU range in order to make
a proper selection of suitable unit(s) for testing.
Anytime, Eurovent Certita Certification has the right to ask an auditor to conduct a surprise
visit to participants’ factory as well as to collect data directly from customer and perform extra
checking of software.
During selection visits, a factory tour shall be made by the auditor, accompanied by
manufacturer’s technical expert. A random selection of at least one unit under construction or
just built, shall be made. The selected unit shall be suitable for testing. If no unit suitable for
AHU, OM-5-2014
Published February 2014
Page 7 of 36
testing is under construction or just built, a random selection from files of recently delivered
units shall be made.
The entire composition and technical specifications of the selected units shall then be checked
onsite. Manufacturer’s technical expert shall fully inform the auditor by submitting all relevant
assembly drawings, specifications and technical data sheets of the selected units. Agreement
shall be reached between manufacturer and the auditor on final selection of Real Unit for
testing.
During annual on-site checking of software, the same procedure shall be applied, without
selection of unit for testing so without the restrictions for measuring facilities. This implies that
any size may be selected.
The expected performance shall be recalculated based on components reselected with the
software provided to Eurovent Certita Certification. The composition and technical
specifications and performance from recalculation shall be the same as the one specified and
announced to the customer. If in the meantime the Participant has officially launched a new
software version and recalculation is made with this version, deviations should be traceable in
the software update record sheet (see D.IV.2). Deviations on performance above tolerances
can lead to additional test (see IV.1c). If it appears that different software had been used, this
shall be considered as a non-respect of procedures (see Certification Manual).
In addition, mechanical construction (all the parameters) of one production unit shall be
verified by the auditor, to compare certified characteristics of production with the tested Model
Box(es). If it appears that different construction had been used, additional Model Box test shall
be required by the auditor.
Finally, consistency of heat recovery shall be verified by the auditor. At least one unit shall be
verified with the methodology detailed in the following paragraph.
In case of force majeure (e.g. accidents, labour disputes, natural events, acts of war) which
would not allow Eurovent Certita Certification to perform a factory visit Eurovent Certita
Certification can decide to replace it by another mean of verification, to postpone it within a
reasonable deadline or to cancel it. The Compliance Committee will be made informed
regarding these cases.
IV.5
Consistency check of heat recovery
a.
Manufacturer uses Eurovent certified heat recovery systems (HRS)
Compare the efficiency and pressure drop data in the AHU quotation or software with
results obtained from the current stand-alone certified software from the HRS supplier.
AHU manufacturer can never claim higher efficiencies and/or lower pressure drops than
the values received from the stand-alone software.
If possible one quotation with a rotor and one quotation with a plate heat exchangers
have to be checked.
b. Manufacturer does not use Eurovent certified HRS
Additional testing of non-certified HRS are requested in the laboratory of the regular
certification campaign, of the different models, one every year. Repetition would only be
necessary in case of change of the structure of the HRS. When a HRS is tested in the
RU one year, this additional testing is not necessary for that year.
Compare the efficiency and pressure drop data in the AHU quotation or software with
results obtained from the test result. Deviation shall be equal or lower than the
acceptable tolerance defined in the certification programme for the HRS. In case a RU is
tested every year, this additional testing is not necessary.
AHU, OM-5-2014
Published February 2014
Page 8 of 36
c.
For certified and non-certified rotors
Observations of rotor arrangements in the AHUs shall be made during the annual factory
inspection. If it appears that (sometimes) parts of the actual heat exchanger surface of
the rotor are blanked / obstructed it shall be verified in manufacturer’s software if this
unfavourable assembly has been considered. The software shall predict (small) reduction
in efficiency and (substantial) pressure drop increase, compared to a selection with
completely open rotor surface.
IV.6 Qualifying campaign
For a company (“Brand name”) presenting on the market units, under its own brand,
manufactured by a certified company, only on-site checking of software shall be conducted at
the place (“office”) where the orders to the customers can be accessed. This place is often the
factory of the certified manufacturer.
For manufacturers, Real Units taken from the production line shall be selected by the auditor
appointed by Eurovent Certita Certification during a factory visit, using the selection software.
Models Boxes will be directly selected by Eurovent Certita Certification from the declaration
list, to cover all worst configurations of the mechanical, thermal and acoustical performance
(see Table 1).
Selected units shall be sent to the independent laboratory within maximum 6 months. If this
deadline is not fulfilled another on-site checking with selection shall be scheduled within
maximum one year from the previous on-site checking.
Units are then tested and the obtained performances compared with the values calculated
using the software. The test on the Real Unit of a range can be carried out after the test results
on the Model Box(es) is/are available.
Assembly places of flat-package units shall be considered exactly the same way as
manufacturing places. When a manufacturer presents several manufacturing places, each
place shall be considered independently.
If all the test results are within the tolerances and calculation model appears consistent,
Eurovent Certita Certification shall grant the certification. If not, failure treatment shall be
applied.
When certified, the range is published on the Eurovent Certified Performance website with an
agreement number, associated characteristics and performance, name and version of the last
software verified by Eurovent Certita Certification, and production places. The participant is
then entitled to use the certification mark for this range in literature and on products (see V.2).
It shall be obvious for which products the certification is granted (see also APPENDIX B and
Certification Manual).
IV.7 Repetition campaign
For a company (“Brand name”) presenting on the market units, under its own brand,
manufactured by a certified company, only on-site checking of software shall be conducted
annually at the place (“office”) where the orders to the customers can be accessed.
For manufacturers, Participant’s quality control shall be appropriate to maintain the
performance within the tolerances. A quality system according to ISO 9001 (covering the
production quality systems) is acknowledged by a reduction in the frequency of repetition tests.
The manufacturer shall then annually provide a valid ISO 9001 certificate to Eurovent Certita
Certification. In addition, annual on-site checking shall be performed in each Participant’s
factory(ies). Assembly places of flat-package units shall be considered exactly the same way
as manufacturing places.
AHU, OM-5-2014
Published February 2014
Page 9 of 36
For each certified range and factory, repetition tests in the independent laboratory selected by
Eurovent Certita Certification shall be required:
 Every six years for mechanical, thermal and acoustical performance on Model Boxes for
participants holding valid ISO 9001 (every three years otherwise)
 Every three years for performance on Real Unit for participants holding valid ISO 9001
(every year otherwise)
Eurovent Certita Certification shall select the units for repetition using the same procedure as
for selection of units for the qualification test. If possible, a RU size or MB configuration
different from those previously tested shall be selected.
If all the test results are within the tolerances and calculation model appears consistent,
Eurovent Certita Certification shall maintain the certification for another period. If not, failure
treatment shall be applied.
IV.8 Ranges to be taken out of production
Running a test on a unit from a range which is going to disappear from the market can
represent a useless cost for the Participants. If a test is necessary on a unit from a range
which is going to disappear from the market, the Participant may send an official letter to
Eurovent Certita Certification stating that the range will disappear between the date of the
scheduled test and the date + one year. The range remains then certified for maximum one
year. If the Participant changes his mind or if it appears that the range is still available after
that time, it is considered as a major breach of the rules, and the Participant will have to pay a
penalty fee of 15 000 €. In addition, the unit will have to be tested and the following test will
have to follow normal schedule.
IV.9
Selection of units for tests
Table 1: Table for selection of model boxes
Construction
variation
Corner post
Mullion
Filter construction
Panel shape
Panel thickness
Sheet metal thickness
Insulation material
(wool vs foam):
- density out of - 25%
- conductivity out of + 15%
Way of insulation mounting
(fixed vs loose)
Metal sheet of panel
(galvanized vs stainless steel)
Casing
strength
x
x
Casing air
leakage
x
x
x
the thinnest
the thinnest
x
the thinnest
x
(density)
Filter bypass
Thermal
leakage
transmittance
x
x
x
x
x
x
the thinnest
the thickest
-
Thermal
bridging
x
x
Acoustic
insulation
x
x
x
the thinnest
the thickest
x
the thinnest
the thinnest
x
x
(conductivity) (conductivity)
x
x
(density)
x
worst case:
galvanized
worst case:
galvanized
External finishing
(galvanized vs coated)
Hinge and /or latch
Regarding Model Boxes, Eurovent Certita Certification shall select the minimum number of
units to cover the construction variations available on the software and catalogue under the
declared range names. All variations (marked by a X) and worst cases are mandatory to be
tested according to the Table 1 above, and worst case performances can be transferred from
the tested MB to other constructions. To claim better class on one performance data, another
MB with the construction parameter variation has to be tested too.
AHU, OM-5-2014
Published February 2014
Page 10 of 36
Selection of one Real Unit suitable for testing shall be made during selection visits as
described above (see IV.4). Size of the units, air volume performance, heating and cooling
capacity, shall be within the limits of the measuring facilities of the laboratory. An up-scaled or
down-scaled unit can be selected if no suitable size is available. In case no unit with heat
recovery or cooling/heating coils can be provided by the factory, these components and the
associated performance shall be non-certified. Because it is a significant parameter for the
energy efficiency classification, in case the software proposes heat recovery, then the selected
unit shall include heat recovery.
Unit for test shall be supplied to the laboratory within six weeks for factories in Europe and
within eight weeks for factories outside Europe (see APPENDIX C). When the manufacturer
does not meet the time limits for the supply of units this will be considered as a non-respect of
procedures. The manufacturer shall inform the laboratory (preferably before the test) if he
wants the unit to be scrapped after the test results are available.
IV.10 Ranges produced in several production places
When a manufacturer presents several production places, each place will be considered
independently so each factory has to be visited every year by the auditor appointed by
Eurovent Certita Certification (selection or annual on-site checking). Assembly places of flatpackage units shall be considered exactly the same way as manufacturing places.
Regarding the selection of units to be tested, the production places for an identical product –
identical software, identical components (designation) and suppliers, same casing (same
drawings and materials), same assembly procedures and ISO 9001 – have to be considered
as one collective production place. In that case each time a different production location will be
randomly chosen for the selection of the unit to be tested. The different production places are
thus called “sister production places”.
During the annual on-site checking (see IV.4), if there is any suspicion that the production
place cannot ensure the same performances as its sister production places, then the auditor
may ask that a Real Unit and/or Model Box be tested.
IV.11 Procedures at the laboratory
a.
General
Only the independent laboratory personnel shall be permitted to handle test units. The
manufacturer's installation and handling instructions shall be followed. The laboratory
shall be responsible for uncrating, handling, testing and recrating the unit for shipment.
The laboratory personnel shall make repairs to the test unit only in agreement with the
manufacturer. No manufacturer's personnel shall be present in the test facility during the
test.
b. Test conditions
The units shall be tested at the conditions as stated in the relevant Rating Standard.
Thermal tests will be performed at 2 conditions in the heating mode and 2 conditions in
the cooling mode (one condition at manufacturer’s rated design and one condition
selected by Eurovent Certita Certification within the scope of the selection software).
Independent laboratory shall test units at the conditions as close as possible to the
selected rating conditions.
Aerodynamic tests (air flow - pressure - power input) shall be performed in accordance
with the test standard ISO 5801, in an operating range of +/-5% around the selected
rating point.
AHU, OM-5-2014
Published February 2014
Page 11 of 36
Testing for heat recovery shall be carried out with at least 20 K difference, under dry
conditions (supply air temperature should not be below +5°C).
c.
Test report and tests results
For each unit, upon completion of all the measurements, the laboratory will render a test
report (pdf) to Eurovent Certita Certification with tested data compared to original
selection data. If at least one performance measurement is out of the tolerances, the
auditor shall conduct a “test check”, i.e. the selection software will be used to recalculate
the performance at conditions used for test: test data will be compared to recalculation
data. Eurovent Certita Certification will transmit a copy of the report together with results
of test check (Forms AHU-4, see APPENDIX D).
Manufacturer has to collect its products one month after receiving the test report. After
this delay, the laboratory will destroy the units if not collected and the manufacturer will
be invoiced through Eurovent Certita Certification.
If the results are out of the allowable tolerance, or the calculation model appears
inconsistent, failure treatment shall be applied.
IV.12 Failure treatment
For each test, a performance item fails when the difference between the declared value and
the measurement differs by more than the allowable tolerance (see relevant Rating Standard).
A test fails when one or more performance(s) fail. In case of failure, Eurovent Certita
Certification shall promptly notify the Participant.
a.
Component failure
The manufacturer shall be authorised to examine the reasons of the failure. In case of a
component failure the unit may be repaired or replaced by a new one of the same model
within 4 weeks, which shall be tested then, according to normal schedule of the
laboratory.
b. Unit failure on a real unit
If the failure is established after the recalculation, the manufacturer shall rerate his data
by adapting the software to the test results within 6 weeks (see APPENDIX C). If the
software is then in accordance with all measurements, certification is granted or
maintained with the re-rated data.
After reverification (“test recheck”), if the software is still not in accordance with the test
results, manufacturer will have two additional weeks for final adjustment of the software
(see APPENDIX C). In case of new failure, no adjustment of software will be accepted
and manufacturer has to restart the test procedure.
c.
No class reached during RU tests
In case of failure on RU tests not reaching any Filter By-pass Leakage (FBL) class, it is
considered as Component failure (immediate stop of the test) and complete retest is
mandatory. In case retest is failed, manufacturer is excluded from the programme for 1
year.
In case of failure on RU tests not reaching any Casing Air Leakage (CAL) class, it is
considered as Component failure (immediate stop of the test) and complete retest is
mandatory. In case retest is failed, manufacturer is excluded from the programme for 1
year.
AHU, OM-5-2014
Published February 2014
Page 12 of 36
d. Unit failure on a Model Box
Manufacturer has four weeks after notification of failure to select one of the following
alternatives:
 Accept measured values. (Uprate is allowed.)
 Ask for a second test on the same unit. In this case, the Manufacturer can choose
to re-test only the performances which are not accepted
 Ask for a second test on another unit of the same model selected by Eurovent
Certita Certification. The delivery shall be done within 8 weeks from the date of
the test report. In this case, all measurements are to be re-tested.
e.
Failure in case of multiple production places
When a range is tested for different production places, if one repetition test fails, all
production places will have to re-rate their data and the software shall be re-rated
according to the worst test results for each performance item.
f.
Irregularities in production places
Irregularities found in a factory can be a reason for retesting or suspension of certification
of the factory or the complete range. In case several factories produce the same range, if
one factory is suspended, the Participant has one year to align it. After this delay, if the
factory is still not in accordance with the requirements, the complete range is suspended
from certification for one year.
IV.13 Special complaint procedure
The general complaint procedure is described in Certification Manual.
In addition, if a Participant obtains doubtful data from a competitor quotation he may present a
complaint request. The Participant who complains will pay 1000 € as fee. Eurovent Certita
Certification auditor will examine complaint within 6 weeks and complaint data will be also
used during annual on-site checking.
If checking results show that the obtained data are different – meaning that other software had
been used or quotation data manipulated – this is considered as a non-respect of procedures
(see Certification Manual). The 1000 € fee will then be sent back to the plaintiff and it will be
invoiced to the Participant who failed.
IV.14 Brand Name
This covers the case of models submitted by a company presenting on the market units, under
its own brand, manufactured by a certified company. When Company A doesn’t produce his
own range but distributes under its own brand ranges already certified by Participant B, no
additional test is required for A. Nevertheless, A has to declare to Eurovent Certita Certification
a place (“office”) where the orders to the customers can be accessed to and the software can
be annually verified by an Eurovent Certita Certification auditor, during the same quarter as the
verification of software hold by B. A’s office is often B’s factory. If a range or a production place
of B doesn’t fulfil the requirements and B’s certificate is suspended and/or expelled from the
programme, A is also automatically suspended. If B quits certification, A is offered the
possibility to cover test expenses for B’s products.
The Brand of the A company must be shown on the output.
A is fully responsible of his software and any non compliance may have a consequence on A
certification, even if B is the software provider.
AHU, OM-5-2014
Published February 2014
Page 13 of 36
IV.15 Non-respect of procedures
The general consequences of non-respect of procedures are described in Certification Manual.
In complement applied penalties can be:
 A certified range and/or production place is withdrawn from the Eurovent Certified
Performance website for one year.
 Any minor non-conformity identified during an on-site checking will be escalated to major
if not solved prior or during the next follow-up audit.
 At the end of the first penalty year and after a second checking, if failure occurs again,
the certified range and/or production place is withdrawn from the Eurovent Certified
Performance website for three years.
The level of penalties and the list of major and minor non-conformities are listed in 0.
V.
PROMOTION OF THE PROGRAMME
V.1 By Eurovent Certita Certification
The following information shall be published for each certified range on the Eurovent Certified
Performance website www.eurovent-certification.com:
 Name of Company
 Trade or brand name
 Agreement number (format: YY.MM.NNN)
 Designation(s) of the range
 Software name and version
 List of certified characteristics and performance items
 Designation of certified sizes of the real units
 Heights and widths of the real units
 Designation of certified model boxes
 The certified mechanical, thermal and acoustical performance data of the model boxes:
casing strength (deflection) identified with a “(M)”, casing air leakage at -400 Pa and
+700 Pa identified with a “(M)”, filter bypass leakage identified with a “(M)”, thermal
transmittance, thermal bridging factor and sound level at different frequencies
 Production sites (city, country)
V.2 By the Participant
The design of the Eurovent Certified Performance mark for Air Handling Units, letter size and
style are presented in APPENDIX B. Display of Eurovent Certied Performance mark on
literature is detailed in Eurovent Certified Performance Certification Manual, paragraph VI.2.
The design and specifications of the energy efficiency label are given in APPENDIX B.
a.
On printouts
Participants are obliged to display the Eurovent energy efficiency class on the printouts of
certified ranges by the means of class on first page (statement, small or large label). If
possible the graphical energy efficiency label shall be displayed. Otherwise statement
shall be: “Eurovent energy efficiency class X”. The following shall be applied:
AHU, OM-5-2014
Published February 2014
Page 14 of 36
motor out only
Standard plate and rotary heat exchangers, as well as standard fans and motors shall be
evident in the software and label is mandatory (first column).
In case of a special project and a heat recovery component is not included in the AHU
software but Eurovent certified or covered by IV.5a or IV.5b Erreur ! Source du renvoi
introuvable.(second column), or if the motor is out only (third column), label is
mandatory.
In case of special projects and if displaying the energy label is not allowed (third column),
the following statement shall be written instead: “Heat recovery component and/or fan
selection beyond certified software does not comply with the Eurovent Certified
Performance rules for label designation.”
b. On units
Each Participant is entitled to display the Eurovent Certified Performance mark on units
of ranges which have been certified:
 By using the relevant Eurovent Certified Performance mark
 By application of the relevant Eurovent Certified Performance mark directly on the
nameplate
 By using the relevant Eurovent Certified Performance energy efficiency label if
applicable. In case the Participant has chosen to display the Eurovent Certified
Performance Energy Efficiency label on units, each unit shall be marked, even the
one with class <E.
AHU, OM-5-2014
Published February 2014
Page 15 of 36
APPENDIX A.
SELECTION SOFTWARE MANDATORY REQUIREMENTS
The auditor assigned by Eurovent Certita Certification shall receive a software program, on a CD-Rom or a
website with remote access. Other access facilities are only possible in consultation with Eurovent Certita
Certification and the auditor. The primary language of the software including outputs must be in English.
The software must be able to calculate operating points between the upper and lower operating condition
without changing any components (for example):
 The operating point of fan (nominal air flow = 100 %) have to calculate by +5 %, +2.5 %,
-2.5 % and
-5 % of nominal air flow. The fan speed must be constant. The external pressure will be variable. The
software has to calculate the power input (in kW) at the electric terminal of the motor / FU-controller.
 The software must have the possibility to calculate the heating capacity with the selected heating coil
between the upper and lower operating condition. It must be possible to change the air flow rate, the
water flow rate, the air inlet temperature. The software must show and print out the results. The
software must give a warning, in case that the result data run out of limits.
 The software must have the possibility to calculate the cooling capacity with the selected cooling coil
between the upper and lower operating condition. It must be possible to change the air flow rate, the
water flow rate, the air inlet temperature, the air inlet humidity. The software must show and print out
the results. The software must give a warning, in case the result data run out of limits.
 The software must have the possibility to calculate the heat recovery capacity with the selected heat
recovery system between the upper and lower operating condition. It must be possible to change the
air flow rate, the supply air inlet temperature and humidity, the exhaust air inlet temperature and
humidity. The software must show and print out the results. The software must give a warning, in case
the result data run out of limits.
The selection software must have the following Mandatory requirements including Input data & Output data.
General Requirements:
 Printouts should be provided as a minimum pdf file.
 There must be only one Eurovent certified software version.
 All components must be described by product key or relevant information (manufacturer name and
reference).
 Calculations must all be at a minimum in SI units.
 The software must show a sketch of the AHU
 Software able to store & restore the selection details without alterations of the calculation.
General: all data which are asked for in D.IV.2 “Form AHU-4B: Recalculation after Real Unit Test” must be
given from the selection software.
Mandatory Input Data:
 Reference nomenclature of unit i.e ABC 40.
 Upper & lower Summer & Winter operating conditions (outdoor air temp & humidity).
 Air flow rate & external pressure.
 Heating coil water inlet temp, water flow rate or water outlet temp & supply air temp behind the heater
coil.
 Cooling coil water inlet temp, water flow rate or water outlet temp & outlet air temp & relative humidity
and supply air temp and humidity behind the cooler.
 Selected filter section (filter class).
 Selected fan section (fan type, motor type).
 Selected inlet & outlet sections.
 Selected heat recovery system with all necessary inputs (Rotary, Plate HX & Run around coils.)
Mandatory information to be found on printouts:
General information:
 On the first page:
AHU, OM-5-2014
Published February 2014
Page 16 of 36
o
o
o
o
o
o
Project name
Customer
Quote/Order no.
Unit range
Unit designation
Eurovent Energy efficiency class. Preferably the graphical energy efficiency label shall be
displayed. Otherwise the statement: “Eurovent energy efficiency class X”, must be announced.
o If the graphical energy efficiency label is not used the Eurovent Certified Performance mark
shall be displayed
o If it is not allowed to display the Eurovent Certified Performance mark or energy class/label, a
statement shall be written instead, e.g. “Heat recovery component- and/or fan selection
beyond certified software do not comply with Eurovent Certified performance rules for label
designation”.
 On each page (including the first page):
o Software name, version code and version date
o printout date
o page numbering with total number of pages (e.g. page x of y)
 Statement “This component is not included in the software Eurovent certified”, if a component, serving
a certified performance, cannot be selected within the certified software. This statement is not required
for non certified components that are not included in the software (e.g. filters, attenuators, humidifiers,
etc.).
 Unit sketches with overall dimensions must be available on selection printouts.
Technical data:
The technical specification of a quoted AHU shall include all technical data required to verify the claimed
energy efficiency class:
 General
 Velocity in the cross section of the filter section (or of the fan cross section if no filter)
 Octave bands (dB) Outlet and Inlet in-duct sound power(dBA) and Airbourne Sound Power(dBA)
 Air Density if set at 1.2kg/m3 then no need to be on printout, otherwise actual density must be provided
on selection output.
 Design winter outdoor temperature for the selected unit, specified as a separate item or mentioned as
design inlet temperature for the first thermal component (heat recovery component or heating coil)
 Mixing ratio (RCA/SUP) at design winter outdoor temperature (maximum value 85%)
 External static pressure for the supply and extract unit (where applicable)
 Basic unit construction (same as model box), it is not necessary to include leakage class & deflection
on the selection / quotation output.
 Internal static pressure drop across the components in the AHU. This requirement shall be fulfilled in
one of the following ways:
o the air side pressure drop across each component is specified in the technical specification
(mandatory method unless unit configuration does not permit this practice)
o the sum of these pressure drops is specified as total internal static pressure drop across
components (pressure drop across filters, HRS and designed (dry or wet) cooling coil shall
always be specified individually);
o the external static pressure, static fan pressure and fan system effect for the design duty point
is specified.
The useful fan static pressure increase to calculate the fan reference power can be derived from all
three data sets.
 Fans
 Fan speed in rpm
 Absorbed electrical power from the mains for each fan in the AHU, including the power losses in any
motor speed controller. If no fan speed controller is quoted, but the fan needs such a device to operate
AHU, OM-5-2014
Published February 2014
Page 17 of 36
on the design fan speed, the power loss of such device shall be included in the specified absorbed
power.
 Filters
 Filter type and class
 Pressure drops: clean, design and final conditions
 Heat recovery system (HRS)
 Dry temperature efficiency (no condensation on extract side) of the HRS for design winter operation at
equal mass flows (extract flow equal to design supply flow)
 Air side pressure drop across the heat recovery system on the extract side and supply side for the
design air flows at winter condition and standard density 1.2 kg/m3.
 Brine concentration in fluid of run around coil system (where applicable)
 Coils
 Statement if air side pressure drop cooling coil is for dry (“dry pressure drop”) or wet (“wet pressure
drop”) condition or statement if fan has been designed for dry or wet condition.
 Heating coil: air side Inlet/Outlet temperatures, airside pressure drop, water flow, & waterside
Inlet/Outlet temperatures & pressure drop.
 Cooling coil: airside Inlet/Outlet temperatures, inlet/Outlet relative humidity, airside pressure drops
(designed: wet or dry, both can be provided, however dry shall be always visible in the software),
waterside flow rate and Inlet/Outlet temperatures and pressure drop.
APPENDIX B. EUROVENT CERTIFIED PERFORMANCE MARK AND ENERGY
EFFICIENCY LABEL
B.I. Eurovent Certified Performance mark
See relevant specifications in Certification Manual.
In addition, the mark shall also include the name of the certified range and the Agreement number
provided by Eurovent Certita Certification when certification is granted.
Figure 1: Eurovent Certified Performance mark specifications and Eurovent Certified
Performance mark for Air handling units
AHU, OM-5-2014
Published February 2014
Page 18 of 36
B.II. Eurovent Certified Performance energy efficiency label
Rules for the use of Eurovent Certified Performance energy label are given in the Certification
Manual.
It is not mandatory to use Eurovent Certified Performance energy labels however it is highly
recommended to do so. If an energy label is used by the participant it is mandatory to use the
layout described on our website.
High resolution files of these labels, as well as specifications for the layout are available on the
website in the manufacturer’s restricted area.
http://www.euroventcertification.com/en/Documentation/_ECC_mark_and_Energy_efficiency_labels.php?rub=09&srub=07&ssrub=&lg=en
B.II.1.
For units (eventually on printouts)
Figure 2: Examples for Eurovent Certified Performance Energy Efficiency Label – for units
B.II.2. For printouts
The label shall be at least 40 mm wide and 40 mm high. The diploma number shall be
displayed on the label.
Conditions of use: can only be used in printed/web document:
 if the product shown is certified
 if no other product is shown
 if all certified performance of the product are displayed next to the label.
Files can be found on the restricted part of the Eurovent Certified Performance website
http://www.euroventcertification.com/en/Documentation/_ECC_mark_and_Energy_efficiency_labels.php?rub=09&srub=07&ssrub=&lg=e
n
Figure 3: Eurovent Certified Performance Energy Efficiency Label – for printouts
AHU, OM-5-2014
Published February 2014
Page 19 of 36
APPENDIX C.
CERTIFICATION SCHEDULE
C.I. Application and test schedule
The process lasts an average of about 8½ months, including the preliminary steps (see Table
2 and Figure 4). About 7 months are necessary for repetition tests (pre-checking is not
included).
Table 2: Minimum, maximum and average time needed for certification of a range
Certification Step
How many weeks does it take? min max
Average week number
The auditor appointed by Eurovent Certita Certification contacts the manufacturer.
Manufacturer sends software to auditor.
The auditor pre-checks the software. When software does not meet the certification requirements,
the manufacturer has to correct it and send a new version. When the software meets the
certification requirements, the manufacturer makes an appointment with the auditor to visit the
factory.
Waiting for the visit date.
The auditor visits manufacturer’s factory, checks sale data and selects one unit for testing. The
auditor sends the visit report and technical form completed for the selected unit to Eurovent
Certita Certification. The manufacturer must up-date his list of products and then to send it to
Eurovent Certita Certification (Forms AHU-1A and 1B).
Eurovent Certita Certification has to send the manufacturer the visit report and the quotation
according to the technical form of the selected real unit(s). When necessary, Eurovent Certita
Certification has also to send the quotation for the model box(es).
The manufacturer has to send the order/payment(s) to Eurovent Certita Certification. The unit(s)
has(have) then to be delivered to the independent laboratory(ies) (2 to 6 weeks for Europe, 4 to 8
weeks for outside of Europe).
Waiting for the availability of the test rig.
The unit(s) is/are tested at the laboratory(ies).
The auditor checks that the software is in accordance with the test results. The laboratory has to
send the test report and the checking report to Eurovent Certita Certification.
Eurovent Certita Certification has to send the report (comments included) to the manufacturer. If
the software is in accordance with the test results, the certification is granted for the next period.
In case the software is not in accordance with the test results, the manufacturer has to send the
software revised according to the test results to the auditor.
The auditor has to check the revised software and send Eurovent Certita Certification a new,
revised report.
Eurovent Certita Certification has to check this report and send it to the manufacturer. If the
software is in accordance with the test results, the certification is granted for the next period.
In case the software is still not in accordance with the test results, the manufacturer may correct
again and send back to the auditor for rechecking.
The auditor has to check the software and send a new report to Eurovent Certita Certification.
If the software is in accordance with the test results, the certification is granted for the next period.
In case the software is still not in accordance with the test results the selection process has to
start again from the beginning and the manufacturer’s data are withdrawn from Eurovent Certified
Performance Website until the certification is granted (min. one year after the first certification
step).
TOTAL number of weeks necessary
1
1
1
4
1
3.5
1
2
5
1
4
7.5
1
2
9
1
3
11
2
8
16
0
1
5
2
18.5
20
1
2
21.5
0
2
22.5
2
6
26.5
1
2
28
0
2
29
2
4
32
1
2
33.5
0
1
34
16
52
34
AHU, OM-5-2014
Published February 2014
Page 20 of 36
APLLICATION
PROCEDURE:
PRE-CHECKING
Figure 4: Planning for application procedure and testing of units
1st contact
Send
software
1 week
1.5 weeks
Software
failure
Checking of
software
Send revised
software
6 weeks
NO
Softwar
e ok ?
YES
3.5 weeks
Appointment
Licence
agreement
Factory visit
QUALIFYING OR REPETITION PROCEDURE: TESTING OF UNITS
4 weeks
1.5 weeks
2 weeks
5 weeks
4 weeks
0.5 week
Failure
treatment:
4 weeks
1 week
Factory
ok?
YES
Visit report
Sign
licence
agreement
Report of
selection of
real unit
Up-date of
lists
Quotation for
real unit
Quotation for
model box
Purchase
order
Purchase
order
Delivery
Delivery
Testing and
test report
Testing and
test report
Checking
Send revised
software
3 weeks
1.5 weeks 1.5 weeks
Checking
report
NO
Softwar
e
ok?
YES
0.5 weeks
EUROVENT C.
certificate
ISO
9001?
NO: every
year
YES: every
3 years
AHU, OM-5-2014
Published February 2014
Page 21 of 36
C.II. Checking of software schedule
The process lasts an average of about 3½ months (see Table 3 and Figure 5).
Table 3: Schedule for annual onsite checking – Minimum, maximum and average time
needed for certification of a new AHU range
Certification Step
How many weeks does it take? min max
Average week number
1
1
1
1
2 2.5
1
4
5
Eurovent Certita Certification informs the manufacturer about the need for a visit of the factory.
The manufacturer has to give to the auditor an appointment for visit of the factory.
Waiting for the visit date.
The auditor has to visit manufacturer’s factory and check sale data. The auditor sends the visit
report to Eurovent Certita Certification.
Eurovent Certita Certification has to send the report including its comments to the manufacturer. If
the onsite software version is in accordance with the certified software version kept by the technical
auditor and the last test results, the certification is granted for the next period.
In case the software is not in accordance with the test results, the manufacturer has to send the
revised software according to the test results to the auditor.
The auditor has to finalize the recheck of the software and send back to Eurovent Certita
Certification a new report.
If the software is in accordance with the test results, the certification is granted for the next period. In
case the software is still not in accordance with the test results it is considered as violation of rules.
REPETITION PROCEDURE: CHECKING
TOTAL number of weeks necessary
1.5 weeks
Appointment
4 weeks
Factory visit
0.5 weeks
Failure
treatment:
1.5 weeks
6.5
0
2
7.5
2
4
10.5
1
2
13
0
1
13.5
7
18 13.5
Send revised
software
Checking
report
Sofwar
e
ok?
YES
2 weeks
2
Checking
3 weeks
1 week
1
NO
EUROVENT C.
certificate
Figure 5: Planning for on-site checking of software
AHU, OM-5-2014
Published February 2014
Page 22 of 36
APPENDIX D.
FORMS
D.I. Submittal for certification by Manufacturer
Information to be provided by Manufacturer (except gray cells)
D.I.1.
n°
PA
id
Form AHU-1A: Data list of certified models & sizes
Trade
name
Range
Agree
ment
Sub
Range
Model
name
Height
Catalo
Software
gue
Width
Perf
Lib
Certified
The “Perf Lib” column should be filled in with: “heating only”/”reversible”/”cooling only” and “with heat
recovery”/”without heat recovery”.
D.I.2.
Form AHU-1B: Data list of certified model boxes, or casing
constructions
n°
PA
id
Trade
name
Range
Model box tests (followed by “(M)”)
Casing Air Casing Air
Filter
Casing
Leakage
Leakage
Bypass
Strength
400 Pa
700 Pa
Leakage
Insertion
125
Insertion
250
Insertion
500
Panel
shape
Panel
thickness
Sheet
metal
thickness
Agreement
Casing
name
Real Unit tests (followed by “(R)”
Casing Air Casing Air
Filter
Casing
Leakage
Leakage
Bypass
Thermal
Bridge
Thermal
Transmittance
Strength
400 Pa
700 Pa
Leakage
Insertion
1000
Insertion
2000
Insertion
4000
Insertion
8000
Corner post
Mullion
Insulation
material
Insulation
material
density
Insulation
material
conductivity
Way of
insulation
mounting
Metal sheet
of panel
Certified
Filter
construction
D.II. Submittal for certification by Brand Name
Information to be provided by the Brand Name (except gray cells)
D.II.1.
Form AHU-2A: Data list of certified models & sizes (BN)
OEM
id
n°
PA
Trade
Name
Range
Brand name
Sub
Range
Model
Height
Width
id
n°
PA
Trade
Name
Range
Sub
Range
Model
Software
Catalogue
D.II.2. Form AHU-2B: Data list of certified model boxes, or casing
constructions (BN)
OEM
id
n°
PA
Trade
Name
Range
Brand name
Casing
Name
id
n°
PA
Trade
Name
Range
Casing
Name
AHU, OM-5-2014
Published February 2014
Page 23 of 36
D.III. Technical forms
D.III.1.
Form AHU-3A: Technical specification related to tested real unit
INFORMATION RELATING TO TESTED UNIT and CERTIFIED VALUES
APPLICANT
DESIGNATION
Software version
Manufacturing place
PERFORMANCE
Nominal
applied
value
Meas.1
Meas.2
0
0
a - Air flow
Total fan pressure
External pressure
Filter pressure drop
Fan speed
Power input
1)
1)
0
0
Pa
Values transposed to
0
Pa
20°C ; 101325 Pa ; 1,2 kg/m3
0
0
0
0
0
0
0
0
2)
of the clean filter
kW
63
Total
rpm
at the terminal of the motor / frequency converter
b - Octave band OUTLET in-duct sound power, supply air only
Conditions:
Fan speed:
0
rpm - Ext. pressure:
0
dBA
(air flow measurements
have to be +/-5%
around nominal point)
m3/h
Pa
0
2)
Meas.3 Meas.4 Meas.5
125
Pa - Air flow:
250
500
1000
0
m³/h at
0
°C
2000
4000
8000
Hz
no value
dB
c - Octave band INLET in-duct sound power, supply air only
Conditions:
Fan speed:
0
rpm - Ext. pressure:
0
dBA
63
Total
125
Pa - Air flow:
250
500
1000
0
m³/h at
0
°C
2000
4000
8000
Hz
no value
dB
d - Airborne sound power, supply air only
Conditions:
Fan speed:
0
rpm - Ext. pressure:
dBA
63
125
Total
0
250
Pa - Air flow:
500
1000
0
2000
m³/h at
4000
0
8000
no value
e - Capacity of cooling coil
dB
1st point
2nd point
m3/h
kg/h
Supply air flow rate :
27 /
°C
7 /
°C
Water flow rate :
47 /
dm3/h
%
kW
m3/h
kg/h
Supply air flow rate :
(at 1,2 kg/m³) Supply air flow rate :
0
Mass air flow rate :
Air in/out :
Cold water in/out :
Water flow rate :
Humidity in/out :
f - Capacity of heating coil
°C
Hz
Supply air flow rate :
³
(at 1,2 kg/m ) Mass air flow rate :
0
m3/h
kg/h
Air in/out :
/
°C
Cold water in/out :
/
°C
/
dm3/h
%
kW
Mass air flow rate :
Humidity in/out :
m3/h
kg/h
Mass air flow rate :
Air in/out :
10 /
°C
Air in/out :
/
°C
Hot water in/out :
Water flow rate :
60 /
°C
Hot water in/out :
Water flow rate :
/
°C
dm3/h
kW
dm3/h
kW
The test w ill be perform ed at the specified w ater flow rate and the specified air flow rate. The air flow rate w ill be adjusted
before the test if the claim ed available pressure for this flow is not achieved during the aerodynam ic test.
g - Heat recovery : category
(in accordance with EN 308)
winter conditions
Temp.
supply-air inlet
°C
supply-air outlet
°C
exhaust-air inlet
°C
exhaust-air outlet
°C
0,0
m3/h
kg/h
0,0
m3/h
kg/h
ratio #DIV/0! %
h - Pressure loss on water side
Cooling coil
kPa
kPa
Heating coil
kPa
kPa
AHU, OM-5-2014
Published February 2014
Page 24 of 36
DESIGNATION
xxx
xxx
Software version
xxx
APPLICANT
ADDITIONAL INFORMATION
FAN
Type
Model
Diameter / Number
Manufacturer
Speed
belt pulley diameter
belt pulley type
Belt type
Efficiency of belt drive
Supply air circuit
Motor
Type
Model
Diameter / Number
Manufacturer
Nominal Voltage
Nominal current
Start current
Efficiency of motor
Speed
belt pulley diameter
Frequency converter
Frequency (in / out)
Efficiency of converter
Supply air circuit
FILTER
Brand and type
Filter class
Initial pressure drop (clean filters)
Final pressure drop (dirty filters)
Design pressure drop
Type of filterframe
Number and size of filters
Supply air circuit
Type
Manufacturer
Fin Spacing / number per m
Fin Thickness and type
length(l) x height(H) x width(L)
Number of Rows deep
Number of circuits
Tube Nominal OD
Tube Wall Thickness
Tube Pattern
Tube innergrooved/smooth
Inlet Connection
Outlet Connection
Internal Volume
Air pressure drop (dry) qv1 & qv2
Air pressure drop (wet) qv1 & qv2
Type code of manufacturer
Exhaust air circuit
-------------------
rpm
mm
%
rpm
mm
%
Exhaust air circuit
---------------------------
V
A
A
%
rpm
mm
Hz
%
Exhaust air circuit
---------------
Pa
Pa
Pa
COOLING COIL
HEATING COIL
mm Nb/m
mm Nb/m
mm type
V
A
A
%
rpm
mm
Hz
%
Pa
Pa
Pa
mm type
mm
mm
mm
mm
mm
mm
dm3
Pa
Pa
Drop eliminator of cooling coil
Air pressure drop at qv1 & qv2
yes / no
Pa
---
Pa
Pa
q v1 ; q v2 : air volume flow 1; 2
HEAT RECOVERY SYSTEM
PLATE
Manufacturer
Reference
Material
Fin spacing
Fin thickness
Dimensions
Pressure drop on air side sup./ ex.
Drop eliminator of HR
Air pressure drop at nominal point
mm
mm
mm
Pa
yes / no
Pa
TOTAL UNIT
Net weight
kg
Dimensions (overall)
mm
Dimensional drawing of unit and the coil circuiting shall be provided
AHU, OM-5-2014
Published February 2014
Page 25 of 36
HEAT RECOVERY COILS
COOLING COIL
Type
Manufacturer
Designation
Diameter / depth
Fin Spacing / number per m
Fin Thickness and type
length(l)xheight(H)xwidth(L)
Number of Rows deep
Number of circuits
Tube Nominal OD
Tube Pattern
Tube innergrooved/smooth
Inlet Connection
Outlet Connection
Internal Volume
Air pressure drop at nominal point
HEATING COIL
mm
mm Nb/m
mm type
Drop eliminator of cooling coil
Air pressure drop at nominal point
mm
mm Nb/m
mm type
mm
mm
mm
mm
mm
mm
mm
mm
dm3
Pa
mm
mm
dm3
Pa
yes / no
Pa
TOTAL UNIT
Net weight
HEAT
Dimensions (overall)
ROTARY
Dimensional drawing of unit and the coil circuiting
shall be provided
Type
Manufacturer
Reference of the wheel
Material
Fin Spacing or Density
mm type
Fin Thickness and type
/
Pressure drop on air side sup. / ext.
Diameter
Depth
Speed
Power input
Nominal voltage
Frequency
Drop eliminator of cooling coil
Air pressure drop at nominal point
kg
mm
RECOVERY SYSTEM
mm
Pa
mm
mm
rpm
W
V
Hz
yes / no
Pa
TOTAL UNIT
Net weight
Dimensions (overall)
Dimensional drawing of unit and the coil circuiting shall be provided
kg
mm
Notes for the Test House
1
2
Physical checks shall made on the additional informations and result shown before performance test.
Fin spacing - the number of fins shall be counted over three separate 100 mm sections of the coil face, the
average figure shall then be divided by 100 and the reciprocal shown to 2 decimal places.
Dimensional drawing and circuit diagram - this shall be checked against test unit.
Fan type : Axial - Centrifugal - Tangential 3
Fin type : Flat - Corrugated - Louvered - Wavy
action or reaction
Date :
AHU, OM-5-2014
Published February 2014
Page 26 of 36
INFORMATION
RELATING
TESTED UNIT
and
Form AHU-3B:
TechnicalTO
specifications
related
to CERTIFIED
tested modelVALUES
box
MECHANICAL CARACTERISTICS
MANUFACTURER:
UP DATE:
Eurovent test code/ Article number
Serial Number
Manufacturing place
name
email adress
Contact for technical questions:
Contact for pickup of model box:
MODEL BOX 1
Range names using this casing:
Designation of the panel:
Max.admissible pressure:
Pa
Cover: Painted
(Painted, corrosive treatment,....)
Option:
(Special joint, hygienic.....)
Length of model box:
mm
Width of model box:
mm
Heigth of model box:
mm
thickness of side panel:
mm
thickness of bottom panel:
mm
thickness of roof panel:
mm
thickness of access doors:
mm
Insulation type:
( Rock wool, PU, mineral wool.....)
specific volume of insulation:
coefficient of heat conductivity
of insulation:
kg/m³
W/mK
Sheet metal material: Galvanized
Thickness of sheet metal (inside):
Thickness of sheet metal (outside):
mm
mm
Profile dimentions:
a - Casing strength
b - Casing air leakage
c - Filter bypass leakage
x
mm
Applied classes
D1
- 400 Pa
+ 700 Pa
L2
L2
(specified in EN1886)
Maximum relative deflection:
4,00
mm/m
F7
Maximum leakage rate:
Maximum filter bypass leakage rate:
d - Thermal transmittance
T3
Thermal transmittance range:
e - Thermal bridging factor
TB3
- 400 Pa
+ 700 Pa
0,44
0,63
2,00
1<U<=1,4
l.s -1m-2
%
W.m-2.K-1
0,45<=kb<0,60
125
250
500
1000
2000
4000
8000
f - Acoustical insulation
AHU, OM-5-2014
Published February 2014
Page 27 of 36
D.IV. Test result formsEUROVENT CERTIFICATION PROGRAMME FOR
D.IV.1.
AIR HANDLING UNITS
REPORTING OF TEST RESULT
Evaluation
of mechanical,
MODEL
BOX
Form AHU-4A:
thermal and acoustical tests
Participant :
Real unit designation :
Model box designation :
Eurovent article number:
Eurovent test number:
Software name and version :
Laboratory
TÜV SÜD GmbH
APPLIED:
MEASURED:
Class (EN 1886)
a - Casing strength
Values
Conclusion
Class (EN 1886)
CERTIFIED:
Class (EN 1886)
Maximum relative deflection [mm/m]:
- 400 Pa
b - Casing air leakage
c - Filter bypass leakage
Maximum leakage rate [l.s -1m-2]:
Maximum filter bypass leakage rate [%]:
d - Thermal transmittance
Thermal transmittance range [W.m -2.K-:]:
+ 700 Pa
- 400 Pa
+ 700 Pa
- 400 Pa
+ 700 Pa
125 Hz
250 Hz
500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
- 400 Pa
+ 700 Pa
- 400 Pa
+ 700 Pa
e - Thermal bridging factor
APPLIED [dB]:
MEASURED [dB]:
f - Acoustical insulation
Tolerance
Conclusion:
CERTIFIED [dB]:
Signature:
RECALCULATION AFTER REAL UNIT TEST
Sandrine MARINHAS
Certification Manager
Date of
D.IV.2.
recalculation
Participant
Real unit designation
Software Designation
Version number
Laboratory
2012-08-19
Participant
AHU 12
AHU Selection Software
1.0.1
TNS
Date:
Form AHU-4B: Recalculation after Real Unit Test
CAPACITY
Applied
1st point
Measured
Cooling kW
49,30
44,70
Heating kW
53,98
52,50
Applied
2nd point
Measured
-9,3%
20,80
21,00
1,0%
FAILED
-2,7%
23,20
22,00
-5,2%
FAILED
Deviation
Deviation
Result
Tolerance -2%
Water-side pressure loss in kPa
Applied
Measured
Water flow Press. loss Water flow Press. loss
3
kPa
dm /h
Cooling
Heating
3
kPa
dm /h
Deviation
#1
Deviation
#2
Result
1st point
1870
2,7
1911
4,80
71,0%
2,0
2nd point
3580
8,7
3633
15,70
75,7%
6,8
FAILED
1st point
560
0,5
562
0,70
39,1%
0,2
PASSED
2nd point
1010
1,4
1011
2,00
42,6%
0,6
PASSED
PASSED
The pressure losses are compared with the following formulas #1 and #2:
Deviation#1 {[( D p / q m 1,8 ) Measured / ( D p / q m 1,8 ) Applied ] - 1}
Tolerance: 10%
Deviation#2 {(Dp)Measured - (Dp / qm1,8)Applied * (qm1,8)Measured}
Tolerance: 2.0k Pa
HEAT RECOVERY
Applied
Supply air
Exhaust air
Measured
In
5,1
5,1
Out
16,0
15,7
In
25,2
25,2
Out
14,4
13,8
54,23%
52,7%
Ratio
Air-side pressure loss in Pa
Temperatures in °C
Deviation
1,5%
Result
PASSED
Applied
Measured
96
111
300
320
Deviation
#1
Deviation
#2
Result
15,6%
15,0
PASSED
6,7%
20,0
PASSED
Deviation#1 Tolerance : 10%
Deviation#2 Tolerance: 15Pa
Tolerance-3%-points
SOUND POWER
Conditions during acoustic test
Fan speed:
rpm
2305
Air flow:
m³/h
5000
ESP:
Pa
250
Octave Band In-duct OUTLET in dB
125
82
250
87
500
87
1000
84
2000
80
4000
75
8000
71
Hz
Applied
Measured
68
85
91
82
77
73
68
dB
Deviation
-14
PASSED
-2
PASSED
4
FAILED
-2
PASSED
-3
PASSED
-2
PASSED
-3
PASSED
dB
Result
dB
Octave Band In-duct INTLET in dB
125
80
250
85
500
85
1000
82
2000
78
4000
73
8000
69
Hz
Measured
75
89
80
85
80
70
70
dB
Deviation
-5
4
-5
3
2
-3
1
dB
Applied
dB
AHU, OM-5-2014
Published February 2014
Page 28 of 36
Supply air
Exhaust air
Out
16,0
15,7
In
25,2
25,2
Out
Ratio
14,4
13,8
54,23%
52,7%
Deviation
1,5%
Result
PASSED
96
111
15,6%
15,0
PASSED
300
320
6,7%
20,0
PASSED
Deviation#1 Tolerance : 10%
Deviation#2 Tolerance: 15Pa
Tolerance-3%-points
SOUND POWER
Conditions during acoustic test
Fan speed:
rpm
2305
Air flow:
m³/h
5000
ESP:
Pa
250
Octave Band In-duct OUTLET in dB
125
82
250
87
500
87
1000
84
2000
80
4000
75
8000
71
Hz
Applied
Measured
68
85
91
82
77
73
68
dB
Deviation
-14
PASSED
-2
PASSED
4
FAILED
-2
PASSED
-3
PASSED
-2
PASSED
-3
PASSED
dB
Result
dB
Octave Band In-duct INTLET in dB
125
80
250
85
500
85
1000
82
2000
78
4000
73
8000
69
Hz
Measured
75
89
80
85
80
70
70
dB
Deviation
Result
-5
PASSED
4
FAILED
-5
PASSED
3
PASSED
2
PASSED
-3
PASSED
1
PASSED
dB
Applied
dB
AIRBORNE Sound Power - Total in dB(A)
Applied
Measured
Deviation
Tolerance
Result
72
74
2
3
PASSED
Air flow in m3 /h
dB(A)
External pressure in Pa (1)
Applied
Measured
Applied
Measured
4719
4850
4973
5093
5211
4719
4850
4973
5093
5211
365
520
360
515
360
(3)
Power input in kW (2)
Fan speed in rpm
Deviation
Results
Applied
Measured
Deviation
Results
Applied
Measured
321
-12,2%
FAILED
2,140
3,200
49,5%
FAILED
1661
1661
325
-9,9%
FAILED
2,160
3,200
48,1%
FAILED
1659
1659
589
394
9,4%
PASSED
2,170
3,100
42,9%
FAILED
1662
1662
310
469
334
7,7%
PASSED
2,600
3,000
15,4%
FAILED
1662
1662
295
431
314
6,3%
PASSED
2,800
2,850
1,8%
PASSED
1661
1661
Available
Values listed above are related to nominal condition r =1,2 kg/m 3
(1) Allowable deviation : -4 % or -15 Pa
(2) Allowable deviation : +3 %
(3) To get the available external pressure, the measured one must be lowered by the unconsidered part of the design filter pressure drop
for the nominal conditions and dry cooler during the air flow test.
Correction for the ESP measured during air flow test
All pressure drops in Pa
Corrected design pressure drop of filter
360+(-34/2)
Measured pressure drop of clean filter
148
Difference to be taken in consideration @ nominal point 100%
195
Applied
Available (cooler dry)
limit
Air flow / PowerXinput
Measured
Y limit
Applied
(1) Allowable deviation : -4 % or -15 Pa
2,17
(1) Allowable deviation : -4 % or -152,2785
Pa
#VALEUR!
2,2785
#VALEUR!
2,17
(1) Allowable deviation : -4 % or -15 Pa
2,17
3,40
3,20
Power input in kW
External pressure in Pa
X limit
Y limit
Air flow / Pressure
(1) Allowable deviation : -4 0% or -15 Pa
(1) Allowable
700 deviation : -4 0% or -15 Pa
#VALEUR!
0
#VALEUR!
0
600
(1) Allowable deviation : -4 0% or -15 Pa
500
400
300
3,00
Measured
2,80
2,60
2,40
2,20
2,00
1,80
200
100
4600
1,60
4700
4800
4900
5000
5100
5200
1,40
4600
5300
4700
4800
4900
5000
5100
5200
5300
Air flow in m³/h
Air flow in m³/h
Recalculation after Test
Calculation External Static Pressure (ESP) - Correction of filter pressure drop
Date:
19/08/2012
Air Flow Points Air Flow Rate
95,0%
97,5%
100,0%
102,5%
105,0%
Δpclean filter in Pa
Δpdesign filter in Pa
ESP in Pa
m³/h
measured
applied
Δpclean, mea-app
applied
corrected Δpcorr. design - clean
4719
4850
4973
5093
5211
160
155
148
165
162
171
184
182
185
193
-11
365
360
200
520
-29
360
346
191
515
-34
360
343
195
589
-20
310
300
135
469
-31
295
280
118
431
measured
available
321
325
394
334
314
AHU, OM-5-2014
Published February 2014
Page 29 of 36
D.IV.3.
Form AHU-4C: Software Update Record Sheet
Company Logo
XXXXX Software Name
Software Update Record Sheet
Prepared By: _____________________________
Software Revision
Date
Brief Description of update
AHU, OM-5-2014
Published February 2014
Page 30 of 36
APPENDIX E.
MAJOR / MINOR NON COMPLIANCES
Each certified range shall be allocated of 15 audit points (after first delivery of certificate). Each major
non-compliance related to the range (independently of the manufacturing place), shall remove 2
points to the account of the range.
If a range reaches 0 point, Participant shall be notified for immediate suspension of the range for one
year. A 24-months period without major non-conformity resets the account to the initial level.
E.I. Handling of several ranges
Does
product 1
carry the
ECP mark
Does
product 2
carry the
ECP mark
NO
YES
NO
YES
“Classic range”
YES
“Classic
range”
“Classic range”
“Classic
range”
“Classic
range”
Name of the
range of
product 1,
certified
Name of the
range of product 2
Are energy
components
basically the same
Is
mechanical
construction
the same ?
“Super
range”
“Poor range”
YES
“Super
range”
“Poor range”
“Classic
range”
“Classic
range”
Compliant
with
certification
rules ?
Cause
NO
YES
2 different ranges, different names, it is ok.
YES
NO
YES
2 different ranges, different names, it is ok.
YES
YES
NO
NO
Not at all
YES
YES
NO
NO
“Classic range”
Special product
YES
except certified
plate or rotary HE
YES
YES
YES
YES
“Classic range”
Special product
YES
except non certified
plate or rotary HE
YES
YES
YES
YES
Marking is mandatory for AHU printouts, all
printouts for units of the certified range shall be
marked.
Marking is mandatory for AHU printouts. Misleads
the customer about the components.
Marking
and labelling
are mandatory
Misleads the customer about the components
Marking
is mandatory,
but labelling
is forbidden
Misleads the customer about the components
Marking
is mandatory,
“Classic range”
Special product
YES
except
fan
“Classic range”
Special product
YES
except
motor
YES
“Classic range”
YES
NO
YES
YES
NO
Misleads the customer about the construction
“Range for Exotic
market”
YES
YES
YES
NO
UNCLEAR
Waiting for CPPC decision
YES
YES
YES
YES
but labelling
“Classic
range”
“Classic
range”
“Classic
range”
YES
YES
is forbidden
YES
Marking
and labelling
are mandatory
AHU, OM-5-2014
Published February 2014
Page 31 of 36
E.II. Major Non-Compliances (2 Points)
Ite
Major Non Compliance = Non-compliance which involves direct impact on the units finished product performance , and may mis-lead the end user
m OM-5,
from
the software output / product and marketing advertisment, or impacts on the completion of the 3A Technical Form for ECC Real Unit test selection.
No. Page No.
P14
Any minor non-conformity identified during an on-site checking will be escalated to major if not resolved prior or during the next follow-up audit (IV.15 OM-5)
1
3
P9/P18
4
5
6
P6/P13
Mis-use of ECC mark in portraying products / ranges to be certified when they are not, this also applies to branded products that have not been declared to ECC or tracability of the
original ECC manufacturer has been removed, either software or unit (IV.14 - OM-5)
Use of ECC mark: The participant is entitled to use the certification mark for the certified range in literature and on products, however it must be obvious for which products the
certification is granted. See also guidance in Certification Manual.
Declaration of Certified Brand without prior knowledge / approval from ECC HQ.
P6/P16
Model Size in Certified range not already declared to ECC
7
P8
8
P11
2 P9/P14/P17
P11
Declaration of Certified MB values without prior knowledge / approval from ECC HQ
If it appears that different MB construction has been used during the factory audit to that supplied for the MB certification charateristics, then this is deemed a failure and additional
MB test shall be required.
Several production places: During the annual on-site checking (see IV.4), if there is any suspicion that the production place cannot ensure the same performances as its 'sister'
production places, then the auditor can issue a major non-compliances and ask for that a Real Unit and/or Model Box be tested.
Software update record sheet not available for updated perfomance to existing components i.e DLL updates
P7
9
P8
Software update record sheet must provide enough traceable information should differences exist during factory software checking
10
11 P5/P10/P11 Manufacturer not providng proof of ISO 9001 continuation after existing certification has lapsed.
12
P8/P9
13
14
15
16
P8
P8
P7/P9
Consistancy checks of Heat Recovery stand-alone ECC software or Real Unit component test to unit selection: NO unit selection software performance can be higher than that of the
stand-alone ECC software or outside the tolerance of the independent Heat Recovery test report.
Able to re-calculate the last Real Unit before removing the compoment from selection software, otherwise re-calculation can not be completed.
If moving to new software platform between the period when the Real Unit was selected & re-calculation, the same unit (all components) must be selectable.
During the factory audit if it appears that different software has been used, then this shall be considered as a non-respect of procedures (see certification manual)
Calculated Eurovent Certified Performance energy class is lower than the claimed energy class
If it is not allowed to display the energy class classification a statement shall be written e.g "Heat Recovery component -and/or fan selection beyond certified software do not comply
17 P15/P17 with Eurovent Certita Certification rules for Energy Class classification.," Refer to Table V.2 in OM-5 for heat recovery systems & fan / electrical motors for when the energy
classification can be used.
General Software Requirements
18
19
20
21
22
23
24
25
P20
P16
Printouts must be provided as a minimium pdf file.
P16
There must be only one active Eurovent Certified AHU software version
P16
If the software is able to export to other formats, then the key output selection requirements must exist eg. Software version, Project name etc…
P16
All components must be described inside the software by a product key or relevant tracable information.
P16
Software data charateristics shall be expressed in SI Units as a minimuim.
P7/P16
The primary language of the software including outputs must be in English.
P17
ECC energy efficiency Class i.e. 'A' must be on the first page (at least on one page)
P16
Unit Sketches and overal dimensions must be available from software.
26
P16
Software must be able to calculate between the upper & lower operating conditions without changing components, software should provide user warning if selection not possible.
27
P16
Software able to store & restore the selection details without alterations of the calculation.
AHU, OM-5-2014
Published February 2014
Page 32 of 36
Ite
Major Non Compliance = Non-compliance which involves direct impact on the units finished product performance , and may mis-lead the end user
m OM-5,
from the software output / product and marketing advertisment, or impacts on the completion of the 3A Technical Form for ECC Real Unit test selection.
No. Page No.
Input / Selection Print Output Data
28
29
30
P16
Unit reference nomenclature to be present on selection output i.e. ABC 40 The product name must be same as that of the certified product listed on the ECC website.
P16
Upper & Lower Summer & Winter operating conditions (outdoor air temperature & humidity)
P16
31
P16
32
33
P7/P17
Air flow rate & external pressure
Heating & Cooling coil water inlet temp's, water flow rate or water outlet temp's. Supply air temp behind heating coil & outlet air temp & relative humidity for cooling coil and supply air
temp and humidity behind the cooler
On the First Page: Project name / Customer / Quote No./ Unit designation & Project selection date must be at a minimium on the first page.
35
36
37
38
P17
All data to calculate the Energy efficiency Class must be available from the data selection sheet.
P17
Velocity in cross-section of the filter section (or of the fan cros-section if no filter)
P17
Octave bands to be in (dB) and Outlet/Inlet & Airbourne Sound Power (dBA) of the unit
P17
39
P17
40
41
42
P17
If software not using standard 1.2kg/m3 air density, then actual air density must be provided on selection output
Design Winter outdoor air temperature and % factor of recirculation air (if applicable) must be declared on the selection printout or mentioned as design inlet temperature for the first
thermal component (heat recovery or heating component)
External static pressure for the supply and extract unit (where applicable)
P17
Basic unit construction(same as Model Box), it is not necessary to include leakage class & deflection on the selection /quotation output
P18
43
P18
44
P18
Selected filter sections with filter type & class, pressure drops for Clean, Design & Dirty conditions (Energy class based on Design)
Heat recovery system (HRS): Dry temperature efficiency (no condensation on extract side) of the HRS for the design winter operation @ equal mass flows (extract flow equsl to
design supply flow)
Brine concentration in fluif of run around coil system (where applicable)
45
P18
Coils: statement if airside pressure drop cooling coil is dry (dry pressure drop) or wet (wet pressure drop) condition or statement if fan has been designed for dry or wet condition
46
47
48
P18
Cooling Coil: Designed wet or dry, both can be provided, however dry shall be always visible in the software
P18
Fan & motor type including fan and motor data i.e. RPM, Input Power Absorbed Power, must be declared on selection output.
On Each Page: Software name, version code and version date, printout date, page numbering with total no. of pages (e.g. x of y)
Statement: "This componenet is not included in the software certified by Eurovent Certification", if a component, serving a certified performance, cannot be selected within the certified
34 P7/P17
software. This statement is not required for non-certified components that are not included in the software (e.g Filters, Attenuators, Humidifiers, etc)
Technical Selection Print Output Data
49
50
51
P17
Inverter power absorption not included in total active power absorbed of the unit when inverter is not fitted in factory but required to run unit
Total static pressure values of actual unit configuration different to that declared on printout “Total internal static pressure + external static pressure (+possible system effect) but not
P18
including Dynamic pressure”.
P17/P18 All data to calculate the Energy efficiency Class must be available from the data selection sheet.
P18
P33
Note:
If unit called same for certified & non certified with different components (unit must have different range name!)
The above list is not absolute and at the auditors discretion based on the definition of "major" non-compliance this will be included in the audit assessment
Notes: Some of these items may have also been listed on the 'minor' non-compliance list, however they will be considered as a 'major' non-compliance should they not be resolved during the n+1 audit
AHU, OM-5-2014
Published February 2014
Page 33 of 36
E.III. Minor Non-Compliances (0 Points)
Ite
m OM-5,
No. Page No.
P7
1
P19
2
P15
3
P17
4
Minor Non Compliance = which does not involve a direct impact on the units finished product performance, and does not mislead the end user from the
Software output / product and marketing advertisment, or does not impact on the audit completion.
Software update record sheet not provided to ECC HQ for additional component additions or other updates within Software excluding performance changes to certified scope
Incorrect design of ECC Mark used on any documentation as detailed in the certification manual (VI.2), this also includes color of mark
If the participant has chosen to fit the energy efficiency class to the units even the one with class <E must be fitted.
Filter pressure drop is missing on software print out, however tracable in software audit check
5
P18
6
7
8
9
10
11
P18
If selection design is based on WET fan condition and the energy class is calculated correctly based on the WET pressure drop of the internal static pressure, but NO note can be
found on Fan selection output designed for WET conditions.
The middle-life filter pressure drop is not the average between clean and final filter pressure drop. EN13053 §6.9.2
P17
No Page numbering on selection outputs
P17
Software name / Version and printout date displayed on each page of the selection output with page numbering.
P17
Project name / Customer / Quote No./ Unit designation & Project selection date must be at a minimium on the first page.
P17
If Energy Efficiency class is provided on selection output but not on the first page
P17
Software version number required on DWG (not created by Software) to customer that includes selection output data.
Note:
The above list is not absolute and at the auditors discretion based on the definition of "minor" non-compliance this will be included in the audit assessment
Notes: Some of these items may have also been listed on the 'major' non-compliance list, however they will be considered on the first occasion as a 'minor' non-compliance
AHU, OM-5-2014
Published February 2014
Page 34 of 36
APPENDIX F.
CONSTRUCTION VARIATIONS OF AHU MODEL BOXES
F.I. Corner post (corner and frame)




material: steal/aluminium/plastic
shape (see pictures):
thickness of the material
with/without thermal break
F.II. Mullion




material: steal/aluminium/plastic
shape (see pictures):
thickness of the material
with/without thermal break
AHU, OM-5-2014
Published February 2014
Page 35 of 36
F.III.Filter construction







fixed or laterally extractable
position in the unit (fixed on mullion or on panel)
kind of filter gasket ( flat/profiled)
material/thickness of gasket
fixing of gasket (glued/clamped/foamed)
fixing of filter cell (with springs/screws/...)
used sealing material (gasket/silicone/...)
F.IV. Panel shape
 with/without thermal break
 design (see sketch)
AHU, OM-5-2014
Published February 2014
Page 36 of 36