COVER NOTE
Dear Factory Owner, Manager, Signatory Companies and Trade Unions,
This letter is to provide urgent guidance for common remediation queries we are receiving
from factories and signatories regarding:
• List of suppliers,
• Fire Alarm and Fire Protection system designs
• Locking features, collapsible gates/sliding doors/rolling shutters
• Fire door certification
• Detailed engineering assessments and structural retrofitting works
1. LIST OF SUPPLIERS:
The list of suppliers we have compiled to help factories to source fire equipment is based on
the information provided by the suppliers. We do not make any quality check during the
process of enlistment. The list is not an endorsement or approval by the Accord. There is no
approved supplier list by the Accord. Please refer to Appendix A for an updated list of
suppliers.
2. FIRE ALARM AND FIRE PROTECTION SYSTEM DESIGNS:
All fire alarm designs, sprinkler system designs and standpipe (hydrant) designs shall be
submitted to the Accord for review prior to installation. If the installation work is done
without reviewed designs, the system might not be recognized by the Accord. Please refer to
Appendix B for drawing submission criteria.
3. LOCKING FEATURES, COLLAPSIBLE GATES/SLIDING DOORS/ROLLING
SHUTTERS:
Under the national building code and the Accord, Alliance, and BUET standards, collapsible
doors or gates (horizontal, vertical, roll-up or accordion style) are prohibited in RMG factory
egress routes.
•
•
•
•
•
All collapsible gates must be permanently removed from the doorways and stairways
which lead to an exit of the building.
There are no exceptions to this requirement. All lockable, collapsible gates must be
removed from all exits from the RMG factory buildings.
Fire doors can be equipped with security hardware and locks which permit locking from
the outside where the door can still be opened from the inside (even when the door is
locked from the outside).
Fire doors with permitted locking systems as described above provide the same level of
security as collapsible gates.
The time lines in the inspection report are to be followed strictly.
4. FIRE DOOR CERTIFICATION:
•
•
•
•
•
2|12
•
The fire doors must be certified and manufactured by an authorized fire door
manufacturing facility.
There is currently no authorized manufacturer of certified fire doors in Bangladesh.
There is currently no authorized Bangladesh based certifier of fire doors or fire door
manufacturing facilities.
Please exercise care not to purchase doors which are not certified: the
inspections initiatives are receiving information that fire doors are being marketed which
have inauthentic seals or labels which are not really certified doors. These do not meet
the Accord, Alliance, or national standards. If installed, they would have to be replaced
by actual certified fire doors.
To verify the door you are purchasing is certified: Ask the supplier for the 3rd
party certification (i.e. UL, FM, Intertek, Warrington). Factory owner can then check the
online directory to verify the authenticity of the 3rd party certification using the
manufacturer’s traceable identification number which is on the door rating label.
Fire doors shall be equipped with panic hardware and a self-closing device. The door
•
•
•
must close and latch after each use, or be equipped with a magnetic hold open device
designed to release on fire alarm.
Exit doors must always be of the “swing” type. All fire doors must swing out, in the
direction of exit travel.
All fire door hardware such as hinges, panic bar, self closer, vision panel and locks must
also be certified. There is currently no certified hardware produced in Bangladesh. There is currently no authorized Bangladesh based certifier of fire door hardware
manufacturing facilities.
Acceptable certification and authorizations for fire doors include: UL, FM, INTERTEK,
Warrington etc.
If an Accord factory wishes to confirm the acceptability of a fire door prior to purchasing,
they can send all of the manufacturer’s literature including testing certification to the Accord
and we will determine acceptability. Please refer to Appendix C for fire door requirements.
5. DETAILED ENGINEERING ASSESSMENTS:
Please note the following considerations regarding DEAs:
• We do not have any short list of consulting firms to conduct DEA at this time
• The factory should get approval from the ACCORD before entering into a contract with
any firm to conduct a DEA.
• Our requirements of the consulting firm for conducting DEAs are:
5+ years of experience of the consulting firm in relevant field
10+ years of experience of the concerned engineer in relevant field
• The final DEA report must be approved by the ACCORD.
• No retrofitting work shall commence without approval from the ACCORD.
• For more details please contact the ACCORD Structural Team.
No additions to buildings are allowed without prior approval from the Accord.
The Accord engineering team is available to advise on the above matters where necessary.
Please contact them with any further queries:
Mohammad Shafiq Uddin, Accord Lead Structural Engineer
mohammed.uddin@bangladeshaccord.com
Md. Kamrujjaman
Accord Lead Fire Safety Engineer
md.kamrujjaman@bangladeshaccord.com
Shahin Azad
Accord Senior Electrical Engineer
shahin.azad@bangladeshaccord.com
Yours sincerely,
Brad Loewen
Chief Safety Inspector
Accord on Fire & Building Safety in Bangladesh
3|12
APPENDIX A
List of suppliers and vendors:
N.B.: It is simply a list of suppliers that we are aware of; it is not an endorsement or approval
by the Accord.
This is not an Approved list by the ACCORD.
4|12
SI
Vendor
Main Business Contact
area/s
Person
Cell Number
Email address
1.
TRI-ZONE
Fire Suppression
System;
Hydraulic
Calculation; Fire
Alarm System;
Fire Doors.
Mr. Ziaul Islam
CEO
+8801670024098
+8801711851403
ziaul.islam@gmail.com
2
Guraba Telecom
Bangladesh Ltd.
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Mr. K.M
Shamsul HuqCEO
+8801730704118
tareque@gurabatel.com
3
HARBINGER
TRADING
Fire Suppression
System; Fire
Alarm System;
Fire Doors.
Mr. Mamun
ChowdhuryCEO
+8801711543485
+8801938854767
Mamun752003@
yahoo.com
4
Micro Electrical
Mechanical
Solution Ltd.
Fire Suppression
System; Fire
Alarm System;
Md. Zafar
Hossain
Executive
Director
+8801712834949
+8801967700352
nafis.glexus@gmail.com
5
The Tool Master&
Eng. Co.
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Al Mamun
(Bulbul)
+8801674634723
toolmasterbd@gmail.com;
tool_mster@yahoo.com
6
Multisystem Eng.
Co. Ltd.
Fire Suppression
System; Fire
Alarm System;
Mr. Nafis
+8801720056249
+8801755507628
nafis@mecl-bd.com; info@
mecl-bd.com
7
Symantec
Technologies Ltd.
Fire Suppression
System; Fire
Alarm System;
Fire Doors.
Mr. Rashadul
Islam Asst.
Manager
+8801614047449
+8801614047444
mamun@symantecbd.com;
management@symantecbd.
com
8
Bengal
International
Agencies
Fire Suppression
System; Fire
Alarm System;
Mr. Shahjahan
Saju Managing
Director
+8801819405398
+8801979405398
bengal.fire@yahoo.com;
mecj.bms@yahoo.com
9
Genesis
Technologies Ltd.
Fire Suppression
System; Fire
Alarm System;
Mr. Omar Faruk
Director
+8801914067101
faruk@gtl.com.bd; info@
gtl.com.bd
10
ICEL Private Ltd.
Fire Suppression
System; Fire
Alarm System;
Fire Doors.
Mr. Javed
Mahmood
Managing
Director
+8801819777779
+8801199856500
javed@icelbd.com
11
Multi Product
Engineering
Limited.
Fire Suppression
System; Fire
Alarm System;
Fire Doors.
Mr. Probodh
Kumar Saha
General Manager
+8801713030108
pks@mplmagnum.com
12
ZM International
Fire Suppression
System; Fire
Alarm System;
Mr. Zakir Uddin
Ahmed CEO
+8801920098535
zakir@zmintl.com
13
Bangladesh Techno
rise Limited
Fire Suppression
System; Fire
Alarm System;
Mr. Kausarul
Hakim
Managing
Director
+8801711548167
info@technorise.com
14
Aim Tech Ltd
Fire Suppression
System; Fire
Alarm System;
Fire Doors.
Engr.Ataul Kabir
Director
+8801755504218
akabir971@gmail.com
15
GRASSHOPER
Fire Suppression
System; Fire
Alarm System;
Fire Doors; PPE;
Md. Mahmudur
RashidManaging
Director;
+8801917960900
+8801787671919
info@grasshoppergroupbd.
com; grasshopper_bd@
yahoo.com
17
Morgen
International
Fire Suppression
System; Fire
Alarm System;
Fire Doors.
Md. Niaz Ali
Chisty- CEO
+8801711531486
morgenbd@gmail.com
18
Pacific Engineers
International
Fire Suppression
System; Fire
Alarm System;
Fire Doors.
Md. Shahnewaj
Rashedi
+8801913511447
pacificei@gmail.com
19
TECH.ME
Engineering PVT
Ltd.
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Sujit Kumar Dey
+8801713002402
sujit@techmeengg.com
20
Emkay Enterprises
Ltd.
Fire Suppression
System; Fire
Alarm System;
Fire Doors
SAM Toufiqul
Alam
+8801766666910
toufique@emkayenterprise.
com
21
Zed Technology
Fire Hydrant
and Fire Alarm
System
Anwar Hossain
+8801790111188,
+8801977411188
corporate@zedtechbd.
com;zetechcorporate@
gmail.com; web:www.
zedtechbd.com
22
OLYMPIA FIRE
PROTECTION
Fire Suppression
System; Fire
Alarm System;
Fire Doors
MD.WAHID
UDDIN
(DIRECTOR)
+8801711546983
wahiduddinmd@gmail.
com; www.ofpbd.net
23
ATS GROUP (AlAmin Trade
Syndcate)
Fire Suppression
System; Fire
Alarm System;
Fire Doors
M.A. KHAN
JEWELL
+8801911339990
Btel.bd77@yahoo.com
24
ABG Engineering
Services Ltd.
Fire Suppression
System; Fire
Alarm System;
Mr. Ferdous
Alam
Managing
Director
+8801713065871
+8801973992702
alam@abgbd.com;
alam777bd@gmail.com
25
Faa Associates Ltd.
Fire Doors
Iqbal forkan
+8801822220090
iqbal@faaassociates.com
26
Sygra International
Inc.
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Mahbub
Choudhury
+8801715505555
mahbub.choudhury@
sygraint.com;
www.sygraint.com
27
Project Planner
And Consultant
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Md.Nuruddin
Sohel;
Chief Operating
Officer
+8801913027001,
+8801713044656
projectplannerandconsultant@
Fire Suppression
System
Syed Golam
Rabby
+8801678005689
28
5|12
Auspicious
Bangladesh
gmail.com; www.
projectplannerandconsultant.
com
rabby@auspiciousbd.com
6|12
29
KS International
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Md. Wahedunabi
Mondal
+8801780222211
info@ksinternationalbd.
com
30
BENGAL
TECHNOLOGICAL
CORPORATION
LTD.
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Chandan K Shah
Manager
Projects
+8801755579825
btclpm@yahoo.com
31
Ace Controls
Limited
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Md. Abdur
Rahman
Sales Engineer
+8801915360345
abdur.rahman@
acecontrolsltd.com; http://
www.acecontrolsltd.com
32
Meghna Fire
Fighting and
Equipments
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Nur E AlamManaging
Director
+8801711234762
meghnafirebd@gmail.com
33
Pran RFL Group
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Md. Rashedul
Rahman
+8801912257271
Coo.rmil@prangroup.com;
rfl58@prangroup.com;
www.pranrflgroup.com
34
NewGen Ltd.
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Engr. Sheehab
Quadir
+880186222222
Mahabur.rahman@
gurababd.com; info@
gurababd.com
35
Atlantech
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Shaklayen
Shaheed (Joy)CEO
+8801841504773;
+8801747504773
ceo@atlantechbd.com
36
ETA FIRE ALARM
& SECURITY
SYSTEM
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Abu Saker
Shohel-CEO
+8801736277433;
+8801681524889.
saker135@yahoo.com
37
Luminous
Associates
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Mohd. Noor
Nabi- Owner
+880189223168
info@luminous-bd.net
38
Eastern Fire
Solution
Fire Suppression
System; Fire
Alarm System;
Fire Doors
HM Bulbul
Ahmed- MD
+8801726567062
efs_fire@yahoo.com
39
MAMS Automation
Systems
Fire Suppression
System; Fire
Alarm System;
Fire Doors
Fazlur Rahman
Jewel; Assistant
Manager
+8801766676615
www.mamsbd.com
40
Mechanism Trade
& Engineering
Fire Suppression
System; Fire
Alarm System;
Fire Doors
MD SAKHAWAT
HOSSAIN
+8801713273033;
+8801712513770
sales@mecahnismtrade.
com,
mechanismtrade@yahoo.
com; info.mtel.bd@gmail.
com, enquiry@
mecahnismtrade.com,
41
M/S SIGMA
GROUP
Fire Suppression
System; Fire
Alarm System;
Preetam Basu
+880-2-9122165,
9128395
www.sigma-bd.com
42
Binary Signature
Fire Suppression
System; Fire
Alarm System;
Md. Rafiqul
Islam
01678629555-57
info@binarysignature.com
43
Soyeb Enterprise
Fire Suppression
System; Fire
Alarm System;
S.M. Ezaz
Shamim
+8801711536235;
+8801611536235;
Teehan_ezaz@yahoo.com
44
ATCL Pvt. Ltd
Fire Suppression
System; Fire
Alarm System;
Md. Asraful
Alam
+8801983603860
Ashraful_mr9@yahoo.com;
info@atclbd.net
45
Techno Apogee
Fire Suppression
System; Fire
Alarm System;
Md. Mosaddique
Hossain
+8801714378008
ceo@technoapogee.com
46
MEP Engineering
Consultancy Firm
Fire Suppression
System; Fire
Alarm System;
Engr. Md.
Masud Kawsar
+8801613837902;
+8801710189680
masud.mep@gmail.com;
mepecf@gmail.com
(Office)
47
EMACO
ENGINEERING &
TECHNOLOGY
Limited
Fire Suppression
System; Fire
Alarm System;
Mohammad
Omar Faruque
+88 01817-181250/+88 01823072-560
omar.emaco@gmail.com
48
BAFFESCO
Fire Suppression
System; Fire
Alarm System;
Arick Nikolas
Recardo
49
Bangladesh Safety
and Security
Service
Fire Suppression
System; Fire
Alarm and
Security System
-----
029841405
info@bss-bd.com
50
Ezzy Automations
Fire Suppression
System; Fire
Alarm and
Security System
Mohammad
Shakilur
Rahaman
+8801777757961
Fire.automations@gmail.
com
51
A3 Associates Ltd
Building safety
consultant (Fire
and Electrical)
Sakib Sarker
+8801731 804030
a3associatesltd@gmail.com
52
A4S Solution
Fire Suppression
System; Fire
Alarm and
Security System
Md. Salim Miah
+8801924100952
a4ssolution@gmail.com
53
Sothern Multi
Products Ltd.
Fire Alarm
System; Fire
Doors
Md. Mehedi
Hasan
+8801723888273
bde@smplbd.net
54
Aipro Engineering
and Consultancy
Services
Fire Suppression
System; Fire
Alarm and
Security System
Imran Udding
Ahmed
+8801988181920
imran@aiprobd.com
55
Kuulmerchant Ltd
Fire Alarm
System; Fire
Doors
Md. Salah Uddin
+8801611540455
kuulmerchant@gmail.com
The list will be updated frequently.
7|12
baffesco5@gmail.com
APPENDIX B
FIRE ALARM SYSTEM
Each submittal shall include two sets of complete plans on minimum A2 size paper with Factory
Stamp & Signature and product catalog. The following items are also required (2010 NFPA72
Section 10.18.1.2)
1. Factory Forwarding Letter with factory name, address and contacts.
2. The drawing’s cover page shall include Factory name, address, Accord ID.
3. The drawing shall include the site plan with all necessary information if applicable.
4. The drawing shall include detail on the system- Addressable or Conventional.
5. Fire Alarm Panel detail shall be included - How many loop or zone
6. If the system is addressable, drawing shall contain the device number with loop number (eg:
L1S1= Loop 1; Smoke 1); for conventional system clear indication on zones shall be outlined.
7. The Fire Alarm Design shall include a Schematic Diagram/line Diagram containing the loops
start to end and also devices shall include the device number and location. (if addressable)
8. The cable for Detectors shall be minimum 2-core- 1.5 mm2 Fire resistant/FP200 cable.
9. The cable for Bells and sounders shall be minimum 2-core- 2.5 mm2 Fire resistant/FP200
cable.
10. Floor Height, beam depth should be mentioned on the drawing. Architectural elevation is
required in case of shed building.
11. Please include a catalogue of the Fire Alarm System.
12. If the same floor is provided with sprinklers also, detectors can be eliminated.
13. Multi sensor detectors are recommended on the swing, cutting, iron & finishing and other
areas where there is a possibility of floating fabric dust, threads and cottons etc. to avoid false
alarm.
14. Beam detectors are recommended if the ceiling height is more than 6.00 meter from the
finished floor level.
15. If the factory wants to keep the fire door open “Door Hold Open device” to be used which
shall be interfaced with fire alarm system in such a way that in case of fire the door will be
closed automatically getting the signal from Fire Alarm Panel. It should be clearly shown on
the drawing.
Re-Submittals: Submittals requiring additional information will be placed “On Hold” until
required information has been submitted. Plan information revisions shall be submitted with
changes clouded. Changes in other documents shall be clearly identified.
FIRE FIGHTING SYSTEM
Each submittal shall include two sets of complete plans on minimum A2 size paper with Factory
Stamp & Signature. The following items are also required:
1. Factory Forwarding Letter with factory name address and contacts.
2. The drawing’s cover page shall include Factory name, address, Accord ID.
3. The drawing shall include the site plan with all necessary information.
4. The drawing shall be complete with legends, floor area and area title/name.
5. Complete data on sprinklers shall be provided like type of sprinkler, sprinkler K factor,
temperature rating and type of response.
6. Complete data on stand pipes shall be included in the drawing.
7. Complete data on Fire Brigade/Siamese Connection shall be included in the drawing.
8. Riser Diagram is mandatory.
9. The pipe network shall include riser location, zone control valve, pipe diameters and
dimensions.
10. The drawing shall include fire pump location and pump capacity
11. Hydraulic Calculation for the system shall be submitted for the system.
12. Top floor and Ground floor stairwells shall be covered by sprinkler.Sprinklers will not be
required in floors in between.
13. All the toilets and kitchen areas shall be covered by sprinkler.
14. Any room or open space in the working floor shall be covered by sprinklers if it is not
currently covered.
8|12
Re-Submittals: Submittals requiring additional information will be placed “On Hold” until
required information has been submitted. Plan information revisions shall be submitted with
changes clouded. Changes in other documents shall be clearly identified.
9|12
APPENDIX C
WHAT FIRE DOORS DO?
•
•
•
Fire doors save lives and property
Theyarepartofabuilding’spassivefireprotectionsystemandarefundamentaltomost
firestrategiesforbuildings
Theyprovidecriticalprotectionwithinabuildingsuchasescaperoutes(stairsand
corridors)andinprotectingfromfirehazardsinabuilding.
WHAT’S IMPORTANT ABOUT FIRE DOORS?
•
•
•
•
•
DoorsshallbecertifiedbyUL,FMorotherrecognizedthirdpartycertificationagency.
ThedoorsmustcomplywiththestandardsmentionedintheAccordstandard-NFPA
252;BS476part22,EN1634-1,GB12955-2008etc.Thespecificstandardshallbe
mentionedinthecertificateprovidedbythecertificationagencyandthedoorassembly
mustbemanufacturedinaccordancewiththecertificationagencyterms.
Thefiredoorsandframesshallhavepermanentlabelingwiththeinformationofthe
manufacturer,thecertificationagencyandthefirerating(seeexamplebelow).
Ifthedoorscontainglass,thethirdpartycertificationshallindicatetheacceptable
configuration.
Thedoorhardwarewillalsobelistedasfireratedorbetestedaspartoftheassembly.
All components such as the doorframe, hinges, closers, seals and glazing systems make
upthefiredoorassemblyandmustbecertified.
EXAMPLE OF FIRE DOOR RATING LABEL
DO’S & DON’TS  TO STAY SAFE
DO
•
•
•
10|12
•
Specifyandusethird-partycertifiedfiredoorsandcomponents
Makesureyouhavethecorrectcertificationforthedoor’sintendeduse
Make sure the test is carried out on a complete installed assembly – the door leaf, door
frame and essential hardware
Install the door and frame as per manufacturer’s instructions
DON’T
•
•
•
•
•
•
Fit a fire door like any other door – it’s not, it’s an engineered safety device
Cut vision panels and other holes on site
Patch up a fire door
Take risks by reducing the specification
Disconnect a fire door closer
Prop or wedge open a fire door
WHAT IS A THIRD PARTY CERTIFICATION?
•
•
It is the process of certifying that a manufacturer of a product has undergone an
appropriate independent appraisal to confirm their compliance with the performance
aspects of a specification for a particular product and its installation and maintenance.
To achieve third party certification, a manufacturer and their product will have to
undergo a rigorous audit and testing process, ensuring that they have in place
documented product specifications, installation instructions, and a factory production
control system, all of which integrate with an approved Quality Management Scheme.
REQUIRED FIRE PROTECTION RATING OF FIRE DOORS
•
•
•
•
•
11|12
Stairwells (if the building is 4 stories or greater): 1.5 hour
Stairwells (if the building is 3 stories or less): 1 hour
Generator Rooms: 1.5 hour
Transformer rooms: 1.5 hour
Warehouse and Storage rooms: 45 minutes
COLOPHON
Date: November 2014
Author: Accord Fire Safety Team
Graphic Design: JUSTAR.nl
Layout: Iwan Fokin
BANGLADESH ACCORD FOUNDATION
Level 13, AJ Heights
Cha 72/1/d, Pragati Sarani
North Badda, Dhaka - 1212
Bangladesh
Tel +88017666900
Keizersgracht 62-64
1015 CS Amsterdam
The Netherlands
Tel +31 (0) 20 520 7431
www.bangladeshaccord.org
contact@bangladeshaccord.com
12|12