Microcare Pure Sine Wave Bi

MPPT Regulators, Pure Sine Wave Bi-Directional inverters, Grid Tied Inverters, and Grid Tied Limiters
are designed, developed, and manufactured by MICROCARE in Port Elizabeth, South Africa
Microcare Pure Sine Wave Bi-Directional Inverters
Microcare Inverters have been manufactured in Port Elizabeth, South Africa for more than 25 years.
During this period Microcare has manufactured and sold thousands of inverters locally and
internationally through our wide range of agents and distributors. Microcare has become synonomous
with quality and service delivery to a wide range of diverse markets and customers.
The technology has been upgraded and the current range of inverters use High Frequency Pulse
Width Modulation (PWM) to regulate the output of the inverter. The updated circuitary allows for
smaller units and more cost effective quality performance. The inverters are pure sine wave with very
low distortion and good regulation. The units incorporate battery low, overload, lightning protection,
load sensing and LCD display as standard.
Our inverters are short circuit proof, and our built in lightning protection offers safety not seen in a
pure sine wave inverter previously.
As we are a South African manufacturer, we are able to offer real time technical support to all our
customers, no matter where in the world they may be, and should there be a neccesity tocarry out
repairs, we can turn the repair around in a 24-72 hour time period.
Features:
•
•
•
•
•
•
•
•
•
•
•
•
•
•
st
Available for 12v/24v/36v/48v dc systems
Output power from 1Kw – 5Kw
LCD Display
Low idle current
High Surge capacity for motor start
Timed Overload capacity with Auto-Shutdown
3 Attempt Auto Restart
Protection against short circuits
Built in battery charger
Locally manufactured
Minimum Service Turnaround
Fan cooling for optimum performance
Audible Buzzer indicating faults and overload conditions
3 Year Warranty
1 Floor Neave Industrial Park, 7 Bennett Road, Korsten, Port Elizabeth – P O Box 7227, Newton Park, 6055 – Email: info@microcare.co.za
Tel: 041 453 5761 Fax: 041 453 5763 – VAT Registered: 4480110222 – www.microcare.co.za
12volt Inverters
Capacity
Input
Output
Charger
Watt
Nominal Voltage
Acceptable Voltage Range
Maxi Input Amps
Standby Power (manual mode)
Standby Power (search mode)
Voltage
Amps
Voltage Regulation
Frequency
Frequency Regulation
Power Factor
Wave Form
Efficiency
Overload Protection
Float Voltage
Boost Voltage
Boost Time
Maximum Current
Generation Mode
st
1kw 12volt
2kw 12volt
1000
12 Vdc
10-15 Vdc
100
15 watts
8 watts
220 Vac
5 amps
< 3 % RMS for entire battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
96%
Circuit Breaker
Programmable Overload Levels and Auto Retry
13.8
13.8…….15.5
Selectable 1, 2, 3 hours.
40 amps
Depending on the generator power available.
2000
12 Vdc
10-15 Vdc
200
24 watts
8 watts
220 Vac
10 amps
< 3 % RMS for entire battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
96%
Circuit Breaker
Programmable Overload Levels and Auto Retry
13.8
13.8…….15.5
Selectable 1, 2, 3 hours.
80 amps
Depending on the generator power available.
1 Floor Neave Industrial Park, 7 Bennett Road, Korsten, Port Elizabeth – P O Box 7227, Newton Park, 6055 – Email: info@microcare.co.za
Tel: 041 453 5761 Fax: 041 453 5763 – VAT Registered: 4480110222 – www.microcare.co.za
24volt Inverters
Capacity
Input
Watt
Nominal Voltage
Acceptable Voltage Range
Maxi Input Amps
Standby Power (manual mode)
Standby Power ( search mode)
Voltage
Amps
Voltage Regulation
Output
Frequency
Frequency Regulation
Power Factor
Wave Form
Efficiency
Overload Protection
Float Voltage
Boost Voltage
Boost Time
Charger
Maximum Current
Generation Mode
st
1kw 24volt
2kw 24volt
3kw 24volt
5kw 24volt
1000
24 Vdc
20-30 Vdc
55
20 watts
10 watts
220 Vac
5 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
> 90 %
Circuit Breaker
110 % ~ 150 % for 30
Sec, > 150 % for
200ms
27.6
28.6……….31
Selectable 1, 2, 3
hours
25 amps
Depending on the
generator power
available.
2000
24 Vdc
20-30 Vdc
75
48 watts
15 watts
220 Vac
10 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
96%
Circuit Breaker
Programmable
Overload levels and
Auto Retry
27.6
27.6…….31
Selectable 1, 2, 3
hours.
40 amps
Depending on the
generator power
available
3000
24 Vdc
20-30 Vdc
150
48 watts
15 watts
220 Vac
14 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
96%
Circuit Breaker
Programmable
Overload levels and
Auto Retry
27.6
28.6…….31.0
Selectable 1, 2, 3
hours.
60 amps
Depending on the
generator power
available.
5000
24 Vdc
20-30 Vdc
250
60 watt
20 watt
220 Vac
22 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
> 90 %
Circuit Breaker
110 % ~ 150 % for 30
Sec, > 150 % for
200ms
27.6
28.6…….31.0
Selectable 1, 2, 3
hours.
100 amps
Depending on the
generator power
available.
1 Floor Neave Industrial Park, 7 Bennett Road, Korsten, Port Elizabeth – P O Box 7227, Newton Park, 6055 – Email: info@microcare.co.za
Tel: 041 453 5761 Fax: 041 453 5763 – VAT Registered: 4480110222 – www.microcare.co.za
36volt Inverters
5kw 36volt
Capacity
Input
Output
Charger
st
Watt
Nominal Voltage
Acceptable Voltage Range
Maxi Input Amps
Standby Power (manual mode)
Standby Power ( search mode)
Voltage
Amps
Voltage Regulation
Frequency
Frequency Regulation
Power Factor
Wave Form
Efficiency
Overload Protection
Float Voltage
Boost Voltage
Boost Time
Maximum Current
Generation Mode
5000
36 Vdc
30-45 Vdc
150
60 watts
20 watts
220 Vac
22 amps
< 3 % RMS for entire battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
90%
Circuit Breaker
Programmable Overload Levels and Auto Retry
41.4
42.9…….46.5
Selectable 1, 2, 3 hours.
75 amps
Depending on the generator power available.
1 Floor Neave Industrial Park, 7 Bennett Road, Korsten, Port Elizabeth – P O Box 7227, Newton Park, 6055 – Email: info@microcare.co.za
Tel: 041 453 5761 Fax: 041 453 5763 – VAT Registered: 4480110222 – www.microcare.co.za
48 Volt Inverters
Capacity
Input
Watt
Nominal Voltage
Acceptable Voltage
Range
Maxi Input Amps
Standby Power
(manual mode)
Standby Power
(search mode)
Voltage
Amps
Voltage Regulation
Output
Frequency
Frequency Regulation
Power Factor
Wave Form
Efficiency
Overload Protection
Charger
Float Voltage
Boost Voltage
Boost Time
Maximum Current
Generation Mode
st
1kw 48volt
2kw 48volt
3kw 48volt
5kw 48volt
1000
48 Vdc
2000
48 Vdc
3000
48 Vdc
5000
48 Vdc
40-60 Vdc
40-60 Vdc
40-60 Vdc
40-60 Vdc
25
75
125
75
30 watts
30 watts
48 watts
60 watts
10 watts
10 watts
15 watts
20 watts
220 Vac
5 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
96%
Circuit Breaker
Programmable Overload
levels and Auto Retry
55.2
57.2V-62.0V
Selectable 1, 2, 3 hours.
10 amps
Depending on the
generator power available.
220 Vac
10 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
96%
Circuit Breaker
Programmable Overload
levels and Auto Retry
55.2
57.2V-62.0V
Selectable 1, 2, 3 hours.
20 amps
Depending on the
generator power available.
220 Vac
14 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
90 % @ 90% Load
Circuit Breaker
Programmable Overload
levels and Auto Retry
55.2
57.2V-62.0V
Selectable 1, 2, 3 hours.
30 amps
Depending on the
generator power available.
220 Vac
22 amps
< 3 % RMS for entire
battery voltage range
50Hz
± 0.1Hz
1
Pure Sine Wave
96%
Circuit Breaker
Programmable Overload
levels and Auto Retry
55.2
57.2V-62.0V
Selectable 1, 2, 3 hours.
50 amps
Depending on the
generator power available.
1 Floor Neave Industrial Park, 7 Bennett Road, Korsten, Port Elizabeth – P O Box 7227, Newton Park, 6055 – Email: info@microcare.co.za
Tel: 041 453 5761 Fax: 041 453 5763 – VAT Registered: 4480110222 – www.microcare.co.za