Automation and Drives
SIMATIC
Microbox PC 420
s imatic pc
Technical Information
SIMATIC Microbox PC 427B
Automation and Drives
SIMATIC Microbox PC 427B – Developed in
Accordance with Customer Requirements
SIMATIC
Microbox PC 427B
Requirements
Requirements
Basic customer requirements
Technical characteristics
High compactness
Dimensions/volume with functionality
High ruggedness
EMC
Technical Data
Temperature
Features
PC104
Shock/ vibration
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
EMC-tight full-metal enclosure
Isolated power supply
Large heat sink to the outside
directly on processor
Low-voltage CPU/chipset
CompactFlash card
Rugged enclosure
High system availability
24-h continuous operation / 365 days
Zero maintenance
Without fans
Without hard disks (option)
Without CMOS battery (option)
Ease of mounting
Standard mounting rail
Wall
Access protection
BIOS password
XPe configuration
Upgradeability
Profibus DP
3 x PCI-104
4 x USB 2.0
State-of-the-art technology
SIMATIC Microbox PC 427B – Technical Information
DDR2 RAM
Gbit-LAN (via PCI-Express)
DVI-I
32-bit buffered SRAM
A&D SE IPC, 01/2007 2
Automation and Drives
SIMATIC Microbox PC 427B
Technical Data
Subject to technical changes/improvements.
SIMATIC
Microbox PC 427B
Basic data
Requirements
Mounting /
installation position
Standard rail mounting
Wall mounting
Installation position: horizontal (preference) and vertikal
Processor
Intel Celeron M 900 MHz, 400 MHz FSB, SLC 0Kb, ULV
Intel Celeron M 1 GHz, 400 MHz FSB, SLC 512Kb, ULV 373
Intel Pentium M 1.4 GHz, 400 MHz FSB, SLC 2Mb, LV 738
Chipset
Intel Alviso 910GML
Main memory
Free extension slots
Up to 3 x PCI-104 (with extension frame)
3 W per slot
Graphics
Integrated Intel 2D/3D GMA900 graphics accelerator
8 to 128 MB shared graphics memory (dynamically
managed)
Resolution CRT: 640*480 pixels up to max. 1600*1200
pixels / true color / 60 to 120 Hz
Resolution DVI-D: 640*480 pixels up to max. 1600*1200
pixels / true color
Power supply
24 V DC; 20.4 ... 28.8 V DC
Isolated
Application conditions
Without fan
Technical Data
Technical
Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
SIMATIC Microbox PC 427B – Technical Information
256 MByte DDR2-SDRAM or
512 MByte DDR2-SDRAM or
1 GByte DDR2-SDRAM or
2 GByte DDR2-SDRAM
A&D SE IPC, 01/2007 3
Automation and Drives
SIMATIC Microbox PC 427B
Technical Data
SIMATIC
Microbox PC 427B
Subject to technical changes/improvements.
Drives
SIMATIC PC
CompactFlash
Replaceable (accessible):
256 Mbyte, 512 Mbyte, 1 Gbyte or 2 Gbyte optional
Internal (not accessible):
1 Gbyte or 2 Gbyte optional
High-performance, industrial-grade CompactFlash
PC104
Hard disk
≥ 60 Gbyte SATA optional
Zero Maintenance
Floppy /CD-ROM drive/
USB stick
Connectable via USB interface
Not included in scope of supply
Requirements
Technical Data
Technical
Data
Features
Windows® XPe
Other
Operating Systems
Interfaces
Serial
COM1 (RS232)
Data Back-Up
Graphical
DVI-I: DVI and VGA combined
BIOS
USB
4 x USB V 2.0 / high-speed (480 Mbit/sec)
Additional strain relief option included in accessories kit
Ethernet
PROFIBUS DP/MPI
12 Mbit/sec (isolated, CP 5611-compatible), optional
With exclusive, non-shared interrupt
Other field buses upon request
Keyboard, mouse
Connectable via USB interface
SIMATIC Microbox PC 427B – Technical Information
2 x 10/100/1000 Mbit/sec (RJ 45)
2 independent Intel controllers 82573L (via PCI-Express)
One controller with exclusive, non-shared interrupt
Both interfaces are teaming-capable
A&D SE IPC, 01/2007 4
Automation and Drives
SIMATIC Microbox PC 427B
Technical Data
Subject to technical changes/improvements.
SIMATIC
Microbox PC 427B
Requirements
Safety functions
Technical Data
Technical
Data
Watchdog
Temperature monitoring
Processor and basic board (via SIMATIC PC DiagMonitor)
Hour meter
Via SIMATIC PC DiagMonitor
LED display
4 LEDs for system state display
2 of which are freely programmable by the user
(each two-colored: yellow/green and yellow/red)
Short-time
voltage interruption
Up to 5 msec
Then buffering for at least another 10 msec
Network failure signaling through power fail signal
Buffer memory
2 Mbyte battery-buffered SRAM
128 kbyte of which are writable within the buffer time
Features
PC104
Zero Maintenance
Program sequence monitoring
Monitoring time parameterizable via software
Restart parameterizable for fault cases
Evaluation of the application program‘s fault states
(locally, via LAN)
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 5
Automation and Drives
SIMATIC Microbox PC 427B
Technical Data
Subject to technical changes/improvements.
SIMATIC
Microbox PC 427B
Requirements
Operating systems
Technical Data
Technical
Data
Orderable
Without
Windows® XP embedded® pre-installed,
no activation required
in connection with
SIMATIC PC CompactFlash ≥ 512 Mbyte or hard disk
Windows® XP Professional®,
no activation required
in connection with hard disk
RMOS3 as independent product
Project-specific
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
SIMATIC Microbox PC 427B – Technical Information
Linux
QNX®
VxWorks®
Others
A&D SE IPC, 01/2007 6
Automation and Drives
SIMATIC Microbox PC 427B
Technical Data
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Technical
Data
Subject to technical changes/improvements.
Ambient conditions
General
In accordance with SIMATIC SPH environment
Degree of protection
IP 20 in accordance with EN 60529
Vibration
Device without hard disk:
Requirements in accordance with: IEC 61131-2
Testing in accordance with: IEC 60068-2-6, test Fc
5-9 Hz, 3.5 mm deflection, 10x /axis, 1 octave/min
9-150 Hz, 9.8 m/s2, 10x /axis, 1 octave/min
Features
PC104
Zero Maintenance
Device with hard disk: wall mounting
Requirements in accordance with: IEC 61131-2
Testing in accordance with: IEC 60068-2-6, test Fc
10-58 Hz, 0.0375 mm deflection, 10x /axis, 1 octave/min
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
58-200 Hz, 4.9 m/s2, 10x /axis, 1 octave/min
Shock
SIMATIC Microbox PC 427B – Technical Information
Device without hard disk:
Requirements in accordance with: IEC 61131-2
Testing in accordance with: IEC 60068-2-27, test Ea
Module/rack: 150 m/s2, acceleration,
11 msec shock duration
Device with hard disk: wall mounting
Requirements in accordance with: IEC 61131-2
Testing in accordance with: IEC 60068-2-27, test Ea
Devices with drives: 50 m/s2, acceleration,
30 msec shock duration
A&D SE IPC, 01/2007 7
Automation and Drives
SIMATIC Microbox PC 427B
Technical Data
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Technical
Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
Subject to technical changes/improvements.
Ambient conditions
Electromagnetic compatibility (EMC):
Interference emission
Interference resistance to transient disturbance
variables
Interference resistance to
surge voltages
Interference resistance to electrostatic discharge
Interference resistance to
high-frequency irradiation
Interference resistance to
high-frequency power supply
on lines
Interference resistance to
magnetic fields
EN 55022 class B
± 2 kV (IEC 61000-4-4, burst)
± 1 kV (IEC 61000-4-5, surge symmetrical)
± 2 kV (IEC 61000-4-5, surge asymmetrical)
± 6 kV, contact discharge (IEC 61000-4-2)
± 8 kV, air discharge (IEC 61000-4-2)
10 V/m, 80% AM (1 kHz), 80 MHz to 1 GHz (IEC 61000-4-3)
10 V/m, 50% PM, 1.4 GHz to 2 GHz (IEC 61000-4-3)
10 V, 80% AM (1kHz), 10 kHz to 80 MHz (IEC 61000-4-6)
100 A/m effective value, 50/60 Hz (IEC 61000-4-8)
Ambient temperature
during operation
(depending on installation position)
0 to 55 ºC with CompactFlash card
(horizontal, with derating)
0 to 50 ºC with CompactFlash card (horizontal)
0 to 45 ºC with CompactFlash card (vertical)
5 to 40 ºC with hard disk (horizontal and vertical)
Humid heat
With CompactFlash card: 95%
With hard disk: 80%
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 8
Automation and Drives
SIMATIC Microbox PC 427B
Technical Data
SIMATIC
Microbox PC 427B
Requirements
Subject to technical changes/improvements.
Approvals
Safety standards
IEC 61131-2
IEC 61010-1
EN 60950-1
Approvals
cULus approval in accordance with UL 60950 and UL 508
CE-conformity
EC directive 89/336/EEC (EMC directive)
Application in industrial environments:
Interference emission: EN 61000-6-4
Interference resistance: EN 61000-6-2
Application in residential, business and
commercial environments as well as small companies:
Interference emission: EN 61000-6-3
Interference resistance: EN 61000-6-1
Technical Data
Technical
Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
Dimensions and weights
Installation dimensions
Width x height:
Depth basic device:
Depth basic device from
standard mounting rail:
Additional depth per extension (1-3):
Weight
Approx. 2 kg
MLFB body
6ES7647-7A
SIMATIC Microbox PC 427B – Technical Information
262 x 134 mm
47 mm
50 mm
+17 mm each
A&D SE IPC, 01/2007 9
Automation and Drives
Further Features
SIMATIC
Microbox PC 427B
Microbox offers:
Benefits:
Reset button
Device reset during commissioning without disconnection
of the supply voltage
Little influence on the overall process
No noise development
Thanks to the abolishment of fans and hard disk, application also possible in acoustically
sensitive areas
Status LEDs
Serve visual support during:
commissioning / operation / servicing
Easy and fast diagnostics without auxiliary tools
Lower power consumption (approx. ≥
15 W)
than standard PCs
Smaller dimensioning of the upstream 24 V power supply possible
Compact design thanks to reduced heat development
Cable clamp for USB plug
Compliance with vibration/shock values also without cable clamp
Further improved mechanical design thanks to the cable clamp included in the scope of
supply
Isolated power supply
Power monitoring
Query of the battery status for increased system availability
Two-level execution of the monitoring function
Headless operation
Support of system configurations without monitor
Start-up possible without monitor and keyboard
Monitor can be subsequently connected for diagnostic purposes
Requirements
Technical Data
Features
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
SIMATIC Microbox PC 427B – Technical Information
Prevention of potential transfers
Improved system reliability
Support of eased potential/grounding concepts
Application without additional measures
A&D SE IPC, 01/2007 10
Automation and Drives
PCI-104
General Information
SIMATIC
Microbox PC 427B
Requirements
(also see: http://www.pc104.org/)
Technical Data
Features
PC104
Windows® XPe
=
=
=
ISA bus (8 or 16 Bit)
ISA bus + PCI-Bus
PCI bus (without PC/104)
PCI104 and PC/104-Plus cards are consistently usable (use of PCI signals)
Old PC104 cards (only ISA bus) are not usable
Up to three PC/104 modules can be integrated
Data Back-Up
BIOS
PC/104
PC/104-Plus
PCI104
Microbox PC 427B is equipped with a PCI104 interface
Zero Maintenance
Other
Operating Systems
Specifications in accordance with the PC/104 committee
With extension frame
Numerous suppliers of basic and special functions
No manufacturer offers a full-range portfolio
The long-term availability of PC104 modules from
the embedded market bears considerable customer benefits
Typical 3 W power consumption per slot possible
Two "non-shared interrupts" available for high-performance extensions
Optimum EMC connection of interfaces through slot plates on the extension frames
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 11
Automation and Drives
Extension Frame
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
Extension frame
Required for the integration of PC104 modules
Extend the enclosure towards the front and create space for modules
Can be modularly stacked
Can be ordered separately as extension kit
Extension kit PC/104
6AG4070-0BA00-0XA0
6 extension frames, including mounting material and slot plates
1 extension frame (17 mm) required per PC104 module
The basic device's front cover also serves as front-side cover
when using the extension frame.
Any interfaces of the PC104 modules are routed to the
extension frame‘s slot plates via short cables.
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 12
Automation and Drives
I/O Cards
Selection and Integration
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
A&D SE IPC provides support in the form of pre-sales services regarding the selection and
integration of PC104 extension modules.
Integration
by customers or
by the IPC Customization Center
The following steps must be performed by customers:
Routing the connection cable between the PC104 module
and the slot plate
these are partially included in the modules‘ scope of supply
Placing cutouts in the slot plates for the interface plugs
PC104 modules can be integrated in the Microbox PC by means
of customizing, for which the above-mentioned steps have to be performed.
The delivery conditions of the manufacturers apply
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 13
Automation and Drives
Zero Maintenance
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
The zero maintenance of the Microbox PC results from the complete abolishment of rotating
parts, i.e.:
PC104
Zero Maintenance
Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
Abolishment of fans
and abolishment of a hard disk by focusing on CompactFlash operation – as far as permitted by the
application.
Moreover, a battery is not necessarily required, only if
remanent data are to be stored in the SRAM due to:
Remanent storage of setup data (settable in BIOS)
Time synchronization possible via LAN (via DiagMonitor)
BIOS
The Microbox PC offers zero maintenance if the hard disk and battery can be done
away with!
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 14
Automation and Drives
Operating Systems
Windows® XP embedded
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Why Windows XP embedded?
The bulk memory requirement of Windows XP Professional
is too large for a CompactFlash-based system
The license costs of Windows XP embedded are considerably lower than those of Windows XP
Windows® XPe
Windows®
XPe
Other
Operating Systems
Data Back-Up
BIOS
Windows XP embedded contains additional features for embedded applications, e.g.:
Enhanced write filter:
Activatable write protection for partitions to increase system stability
Message box interception:
Configurable output suppression of system and fault messages for unattended systems
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 15
Automation and Drives
Operating Systems
Windows® XP embedded
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Windows®
XPe
Other
Operating Systems
Windows XP embedded is pre-installed on the Microbox PC to allow for manifold applications
Can the customer subsequently install, e.g., Microsoft Word?
Data Back-Up
BIOS
Small size facilitates application on CF card 512 Mbyte or larger
Standard drivers/functions included, e.g. CD-ROM, memory stick, print service, UPS support, etc.
If required, drivers can be subsequently installed
The pre-installed Windows XP embedded is system-tested
Turn-key system
Cost reductions in terms of system generation, tests and commissioning
Yes. For license reasons, the Microsoft Office packages must only be used application-specifically; no general use
(e.g. letter preparation) permissible.
Incl. Service Pack 2 Feature Pack 2007
Latest hot fixes and security patches for increased system reliability
Booting of USB bulk memories, e.g. to boot USB flash drives in service cases
Improved Enhanced Write Filter (EWF) allows, e.g., for the write protection
for individual files instead of partitions only
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 16
Automation and Drives
Windows® XP embedded
Optimization
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Windows®
XPe
Other
Operating Systems
Data Back-Up
If required, XPe can be further optimized for special applications
Adding of components not contained in the standard image
Reduced demand for CF cards thanks to abolishment of unnecessary components
A special tool chain (Target Designer) and respective
know-how are required for these adjustments
A&D SE IPC CC offers a project-specific generation of
XP embedded
BIOS
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 17
Automation and Drives
Windows® XP embedded
Basic Images
SIMATIC
Microbox PC 427B
Requirements
Two basic versions cover the basic requirements.
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Windows®
XPe
Other
Operating Systems
Data Back-Up
1. Basic image for applications in rough environments
Application on Microbox with CF card (
Restricted Windows functional scope
Full interface support
Enhanced Write Filter enabled
Support of Win AC Basis
512 Mbyte)
BIOS
2. Basic image for universal applications
Application on Microbox with hard disk
Full functional scope of XP Professional
Subsequent installation of any customer software
Enhanced Write Filter possible but not enabled
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 18
Automation and Drives
Windows® XP embedded
Updates / Virus Scan / Firewall
SIMATIC
Microbox PC 427B
Requirements
Updates
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Windows®
XPe
Other
Operating Systems
Virus scanner
Data Back-Up
BIOS
XPe fillings contain a “Desktop Update” component
for the subsequent installation of XP Professional hot fixes
via USB devices (CD-ROM, USB stick ..) or via LAN
Subsequent installation of complete service packages not possible
Microsoft offers correspondingly updated components for XPe time-delayed
to the respective service packs .
These components are integrated in the XPe fillings as required.
With its configurable Enhanced Write Filter (EWF), XPe offers a better protection against viruses than Windows XP
Professional
A virus scan can be installed, updates are carried out with the conventional mechanisms
as with XP-Professional in consideration of the EWF
(disabling with installations)
via USB devices (CD-ROM, USB stick ..) or via LAN
Firewall
The XPe fillings of the Microbox contain the “Internet Connection Firewall”
It has to be configured by the end user
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 19
Automation and Drives
Operating Systems
Others
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
Thanks to the standard architecture, also other operating
systems can be employed.
Installation and switch-on test with Suse Linux
Further operating systems (QNX, VxWorks ...) upon request
PC104
Zero Maintenance
Windows® XPe
Other
Other
Operating Systems
Operating
Systems
Data Back-Up
BIOS
Project-specific solutions are realized by the SIMATIC PC Customization Center.
If required, a customer-provided software image can be
pre-installed ex works.
Realtime operating system SICOMP RMOS3
system-tested on Microbox PC 427B
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 20
Automation and Drives
Back-Up and Restoration
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
Data
Back-Up
BIOS
A restore DVD is included in the standard scope of supply.
For data back-up and restoration, the standard IPC tools
("SIMATIC PC/PG Image & Partition Creator“) or comparable products can be used.
With the CompactFlash version, the application of a PCMCIA adapter in the programming
device is recommendable.
For monitoring the Microbox PC, the "SIMATIC PC DiagMonitor" monitoring and remote
signaling software can be employed.
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 21
Automation and Drives
Restore DVD
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
The restore DVD contains the as-delivered XPe image of the SIMATIC Microbox PC 427B for
the respective filling
Transfer of the image to the hard disk / CF card via Ghost (component DVD)
Delivery of SIMATIC Microbox PC without restore DVD
Customers can order the restore DVD from the Customer Support
Zero Maintenance
Windows® XPe
Other
Operating Systems
SIMATIC Microbox
PC
Data Back-Up
Data
Back-Up
BIOS
Siemens
CS Fuerth
+ Customer application
Customer
Restore
DVD
SIMATIC Microbox
PC
+ Customer
application
SIMATIC Microbox
PC
+ Customer
application
SIMATIC Microbox
PC
+ Customer
application
Machine
image
+ Customer
application
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 22
Automation and Drives
Data Back-Up via Buffered SRAM
SIMATIC
Microbox PC 427B
2 Mbyte SRAM for data back-up in case of network failures
Requirements
Data storage via integrated battery
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
Data
Back-Up
High-performance bus interface (32-bit PCI, memory-mapped)
High-capacity battery (> 5-year service life)
Remanence strategies
Cyclic storage of important data
Storage of all required data in case of network failure
Initialization of data recovery via Powerfail and NMI
Storage time after interrupt at least 10 msec, depending on HW configuration
Currently application-specific implementation of data back-up
Network failure
BIOS
NMI, initialization of the interrupt service
routine
1-3msec
frequent
normal
voltage
interruptions
Computer
power OFF
Storage time in full configuration
10 msec (with max. power demand)
5msec
SIMATIC Microbox PC 427B – Technical Information
min. 10 msec
A&D SE IPC, 01/2007 23
Automation and Drives
Microbox PC Data Back-Up
Customer Benefits
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Important data can be rapidly stored in the battery-buffered SRAM even after switch-off
Faster writing of small data volumes on SRAM than on CompactFlash or hard disk
WinAC can store data blocks and continue operation with the saved data upon the next start-
up
Windows® XPe
Other
Operating Systems
SRAM on-board, i.e. no additional HW (memory board) required
Data Back-Up
Data
Back-Up
BIOS
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 24
Automation and Drives
Microbox PC Data Back-Up
Status Win XPe
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
Data
Back-Up
Windows XPe works with the same mechanisms as
Windows XP Professional
Storage of remanent data in the SRAM
via access to memory in the SRAM by employing an I/O driver
(e.g. IMCEA driver)
via WinAC and use of suitable remanence library
Data back-up is carried out application-specifically by means
of suitable cyclic storage measures
BIOS
Safe shutdown in case of voltage failures (incl. prior storage
of open files) via UPS
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 25
Automation and Drives
BIOS
SIMATIC
Microbox PC 427B
Requirements
Technical Data
Features
PC104
Zero Maintenance
Windows® XPe
Other
Operating Systems
Data Back-Up
BIOS
Boot devices
CompactFlash disk
Hard disk
USB floppy disk
USB optical disk (CD, DVD)
USB memory stick
LAN via PXE (preboot execution environment)
Adjustment of Microbox PC-specific functions
Watchdog
Field bus interface
IDE operating mode enhanced / legacy
Setup values can be stored in EPROM.
Legacy support for keyboard, mouse and drives
USB2.0 legacy support
USB drivers have to be available for realtime applications
Unique number (stored via DMI)
SIMATIC Microbox PC 427B – Technical Information
A&D SE IPC, 01/2007 26
© Copyright 2025