Page 01 - Adexbd

NIRAPOD 4
Low Voltage Air Circuit Breaker
800A-6300A,1000V
40kA-150kA
an innovative user friendly circuit breaker
with microprocessor control unit for protection
and measurements as standard
suitable for all applications in:
> Industry
> Infrastructures
> Constructions
> Utility
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
Presentation
NIRAPOD 4 air circuit breakers are designed and made
incorporating universal control unit NIRAPOD4.02M/H
having protection, control & measurement functions. They
may be installed in main LV switchboards as incoming units,
main and secondary outgoings. NIRAPOD 4 acb offers a
complete range with a large selection of performance level:
J ratings from 800 to 6300 A AC,
J breaking capacity from 40 to 100 kA rms;
J operational voltages 690V AC 1000V DC
NIRAPOD
4
circuit
breakers
are
equipped
with
microprocessor- based electronic control units. All the
protection functions are powered by the AC system and
no auxiliary power supply is required. The same is true
for most of the complementary functions.
NIRAPOD4.02M/H control units measure the true rms
value of the current Voltages cosϕ, Hz, kW, reading and
are therefore not affected by harmonics that may be
present on the system.
Operating safety
The insulating casing of NIRAPOD 4 circuit breakers
provides for:
NIRAPOD 4 circuit breakers comply with all
the major international standards:
J user safety:
j double insulation on the front face (class II)
J International standard IEC 947-2 They also comply with
j auxiliary circuits in a compartment insulated from the
the following national standards:
power circuits
J Germany VDE 0660
J switchboard safety when the circuit breaker is in the open
J United Kingdom BS 4752
position
J Italy CEI
j each pole is effectively isolated in its own housing
Adex circuit breakers comply with the specifications of the
j limitation of external disturbances
marine classification companies
Positive contact indication
The position indicator cannot indicate "open" unless the
poles are effectively separated by the required distance.
The circuit breakers automatically open during racking in
and out.
Tropicalisation
reliability
As standard, NIRAPOD 4 circuit breakers are designed
J NIRAPOD 4 circuit breakers comprise ten times fewer
for tropical conditions with 95% relative humidity at 45oC
parts than traditional devices. They are easier to produce
or 80% at 55oC, hot and humid climate conditions. They
and more reliable.
also comply with the following standards:
J the design of Adex circuit breakers is modular with delayed
I IEC 68-2-30 damp heat
differentiation (highest possible number of common parts on
I IEC 68-2-2 dry heat
all models). The result is shorter delivery times and
I IEC 68-2-11 salt spray
enhanced reliability.
I IEC 68-2-1 low temperatures during storage.
Corrosive atmospheres: Special grease or other surface
coatings available (please consult us).
AB-02
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
Standards
Ease of installation
NIRAPOD 4 is a complete and rationally designed range.
J 10 ratings;
J wide breaking-capacity levels;
J 1 control units covers all the protection & measurement
functions
J a complete range of auxiliaries and accessories;
J numerous versions (three and four-pole devices, fixed and
drawout versions, etc.).
NIRAPOD 4 circuit breakers are easy to incorporate in
switchboards
J a single frame size from 800 to 3200 A, thus making for
standardised columns;
J an upper safety clearance equal to zero due to the
arc-chute cover, on both the fixed and drawout versions;
J built-in measurement functions in the control units;
J auxiliaries are the same for the entire range and may be
easily implemented (only a screwdriver is required).
NIRAPOD 4 circuit breakers are easy to connect to the main
distribution system.
J all types of connections are available (horizontal and
vertical terminals, front and mixed connections);
J connections are possible with bars of any thickness
J connection to the input power source is possible on the
upper or lower terminals of the circuit breakers.
Due to their small size, NIRAPOD 4 circuit breakers can
replace most existing circuit breakers.
IEC 947-2
This standard provides the user with a better guarantee
concerning quality and performance.
Circuit breakers are subjected to tests that are more
representative of real operating conditions.
Definition of the terms breaking capacity:
IEC947-2 also clarifies the notion of breaking capacity.
J Icu: the ultimate breaking capacity, which must be greater
than or equal to the 3-phase short-circuit current at the
point of installation of the circuit breaker, a value unlikely
to be reached under real conditions;
J Ics: the service breaking capacity, generally expressed as
a percentage of the ultimate breaking capacity (25,50,75
or 100% of Icu). It corresponds to a short-circuit current
that is more likely to be reached under real conditions.
The circuit breaker must continue to operate normally after
having interrupted a current equal to Ics several times;
J Icw: short-time withstand current for circuit breakers
belonging to category B (category B refers to circuit
breakers with time discrimination and category A to those
without time discrimination).
Furthermore, IEC947-2
technological advances:
takes
into
account
recent
J suitability for isolation recognised for circuit breakers
having passed special electrical and mechanical test:
J industrial earth-fault circuit breakers covered by an
appendix;
maximum dependability
All NIRAPOD 4 circuit breakers are also disconnectors
(suitable for isolation) as specified by IEC 947-2. They bear
the corresponding symbol on the front cover:
J definition of tests designed to ensure coordination between
two circuit breakers.
This characteristic considerably increases the dependability
of the circuit breaker.
The conditions specified by IEC 947.2 for this function are:
J positive contact indication;
J impulse withstand; 8kV at sea level;
J very low leakage current, checked on new circuit breakers
and on circuit breakers subjected to tests representative of
the end of service life.
Moreover Adex circuit breakers have a double- insulation
front face (i.e.a class II device) allowing control from the
outside.
installation
NIRAPOD 4 circuit breakers may be installed on horizontal
metal surfaces or on rails. They are secured by four points
accessible at the bottom of the chassis (drawout versions) or
on either side of the circuit breaker (fixed versions.) A single
door cut-out is required for the entire range and provides
access to NIRAPOD 4 controls.
AB-03
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
Model
NIRAPOD 4
control unit
NIRAPOD 4.02M/H
basic protection
long time protection LT
adjustable current setting (Ir) in 2% steps
J
Ir = In x ...
0.4 to 1
tripping range
between 1.05 and 1.20 x Ir
time delay (tr)
adjustable
accuracy :+0 -20%
tr at 1.5 Ir (s)
15
30
60
120
240 480
tr at 6 Ir (s)
0.94
1.88
3.75
7.50
15
30
tr at 7.2 Ir (s)
0.65
1.30
2..60
5.20
10
21
adjustable pick-up (Im) in 4% steps
Im = Ir x ...
0.4 to 15 W 10%
time delay (tr)
tm setting with I2t OFF
0.09
0.18
0.27
0.36
tm setting with I2t ON
0.09
0.18
0.27
0.36
max. overcurrent time before tripping (ms)
60.9
140.9 230.9
350.9
max. break time (ms)
140.9 230.9 350.9
500.9
short time protection ST
J
Instantaneous protection I
J
fixed pick-up I (kA)
see technical data page
pick-up (I) adjustable in 8% steps
from In to fixed pick-up (mini at 1.6 kA)
accuracy
W 15%
OFF switch on front face
on types N1 and H1
basic functions
fault indication
J
for tripping on a fault
button on front face
fault trip alarm contact
J
for Ir setting overrun
LED on front face
J
self powered
J
indication of fault type
LEDs on front face
J
and value of interrupted current
self-monitoring
display on ammeter
J
internal overheating and microprocessor errors
J
self-powered
J
integrated test
J
The electrical operating mechanism includes:
Electrical operating mechanism
J the gear motor
J a closing release
J a shunt release or an undervoltage release for opening;
J "springs charged" limit switch changeover contact
The addition of the electrical operating mechanism does
not alter circuit breaker dimensions.
Added to the manual charging mechanism, a motor charges
and automatically recharges the stored-energy spring upon
breaker closing making possible fast O-C-O cycles
Opening and closing operations are instantaneous.
The manual mechanism remains available for emergency use.
characteristics
power supply
50/60 Hz (V)
consumption (VA)
DC (V)
consumption (W)
motor start-up surge
charging time
geared motor
100/127 - 200/240 - 250/277 - 380 - 415 - 440 - 480
180
24/30 - 48/60 - 100/125 - 200/250
180
2 to 3 In for 0.1 s
3 to 4 s
AB-04
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
NIRAPOD 4
In =
NIRAPOD 4.02H Controller
Protection & measurement
N
The NIRAPOD4.02M/H control unit is used as standard for
protection, measurement and supervision functions. The liquid
crystal display and function keys ensure high accuracy and easy
adjustment. The standard NIRAPOD4.02M/H control unit provides
the following:
1
V
2
3
Hz
COS
kW
V
I
L2
L1
J universal protection for overcurrent, short circuit & earth
faults with different level & adjustable characteristics
L3
X10
%
J measurement with digital display I, V, kW, cosϕ, Hz, kA, t
A/kA
J setting & measurement with digital display I, kA, t
S
J indication of fault type
Ic1
J values of interrupted currents
Ic2
N
δ
If
S
L
s
J integrated on-load test, trip/no trip conditions.
I2t ON
tr
LT time delay (tr)
I2t OFF
ST pick-up (Im)
ST time delay (tm)
tm
Instantaneous
pick-up (I)
th
0
Ir
Im
I
A
overcurrent settings
1 : LT setting Ir (long time)
2 : LT time delay tr (long time)
3 : ST pick-up Im (short time)
4 : ST time delay tm (short time)
5 : INST pick-up I (instantaneous)
Earth fault protection (option T)
I2t ON
t
I2t OFF
T1
T2
0
earth fault protection settings
T1 : earth fault pick-up Ih
T2 : earth fault time delay th
I
Instantaneous
pick-up (I)
th
Ih
Ir
Im
I
A
STATE
SET
SELECT
TEST
FAULT
FUNCTION
ALARM
ENTER
MEMORY
RESET
Tx
J "earth" protection with time discrimination or zone selective
interlocking. The protection is of the residual current type (or
source ground return type on request).
LT setting (Ir)
ST time delay (tm)
earth 2fault time delay (th)
I t OFF
0
I2t OFF
ST pick-up (Im)
I2t ON
tm
J short-circuit protection:
j delayed, with short time function ST, for which the I2t
curve can be disabled by the user,
j instantaneous, with the INST function that can be disabled by
the user
s
I2t ON
LT time delay (tr)
earth fault
pick-up (Ih)
Basic functions: long time LT,
short time ST, instantaneous INST
T
LT setting (Ir)
tr
The NIRAPOD4.02M/H control unit provides:
J overload protection, with long time Protection LT including:
j adjustable time delay and thermal memory possibility
I
Controller Setting
Programing
interface
Rx
indication and measurement
a digital display continuously indicates the current of the phase
with the greatest load (lmax), Voltages, cosϕ, Hz, kW, reading. By
pressing a scroll button, it is also possible to display successively
the readings of I1, I2, I3 & voltage in phases. The display unit also
helps setting parameters related to protections & measurement of
the programmable control unit.
Factory adjustments
The NIRAPOD4.02M/H control unit is factory adjusted as follows:
LT
setting Ir
In
time delay tr
480 s
ST
pick-up Im
4 In
time delay tm
0,2 s
INST
pick-up I
maxi
T
earth fault pick-up Ih
0.2 In
time delay th
0,1 s
load monitor
Ic1
In
Ic2
In
earth fault protection
This earth fault protection is designed to protect the installation
against the risks of fire due to high earth faults (not to be confused
with schemes designed for the protection of persons against
electrical shock).
Two types of earth protection are available:
J residual current type (T): the control unit calculates the vector
sum of the phase and neutral (if distributed) currents
J source ground return type (W): the control unit acts directly on the
signal received from an external current transformer installed on
the source earthing circuit.
AB-05
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
circuit breakers model
number of poles
AB08
AB10
3-4
3-4
800
1000
800
1000
1000
1000
8000
8000
690
690
electrical characteristics as per IEC 947-2 and EN 60947-2
rated current (A)
In
40oC
rating of 4th pole (A)
rated insulation voltage (V)
Ui
rated impulse withstand voltage (V)
Uimp
rated operational voltage (V)
Ue
AC 50/60 Hz
Icu
AC 50/60 Hz
type of circuit breaker
ultimate breaking capacity (1)
(kA rms)
service breaking capacity
Ics
(% Icu)
short - time withstand current
Icw
AC 50/60 Hz
(kA rms)
making capacity (kA peak)
Icm
AC 50/60 Hz
N1
H1
H2
N1
H1
H2
220/415 V
40
65
100
40
65
100
500/690 V
40
65
85
40
65
85
100%
100%
100%
100%
100%
100%
0.5 s
40
65
65
40
65
65
1s
30
50
50
30
50
50
3s
22
32
32
22
32
32
220/415 V
84
143
220
84
143
220
440 V
84
143
220
84
143
220
500/690 V
84
143
187
84
143
187
84
143
143
84
143
143
electrodynamic withstand (kA peak)
utilization category
B
B
suitability for isolation
J
J
break time
25 to 35 ms
closing time
endurance (C-O cycles) x 1000
70 ms
mechanical
with maintenance
20
no maintenance
electrical
no maintenance
motor control (AC3-947-4) (2)
20
20
20
20
10
10
10
10
10
10
440 V - In
10
10
10
10
10
10
690 V - In
10
10
10
10
10
10
690 V
10
10
10
10
10
10
installation and connections
connection
front and rear connections
drawout
J
J
fixed
J
J
auxiliary switches
J
J
electronic trip unit related functions
J
J
auxiliary releases
J
J
motor mechanism
J
J
operation counter
J
J
interphase barriers
J
J
terminal - block cover
J
J
door frame
J
J
3P
290x400x312
290x400x312
4P
550x439x367
550x439x367
3P
290x400x312
290x400x312
4P
537x356x290
537x356x290
version
indication and measurement auxiliaries
control auxiliaries
installation and connection accessories
dimensions and weights
dimensions W x H x D (mm)
drawout
fixed
20
AB-06
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
AB12
AB16
AB20
AB25
3-4
3-4
3-4
3-4
1250
1600
2000
2500
1250
1600
2000
2500
1000
1000
1000
1000
8000
8000
8000
8000
690
690
690
690
N1
H1
H2
N1
H1
H2
N1
H1
H2
N1
H1
H2
40
65
100
40
65
100
55
75
100
55
75
75
40
65
85
40
65
85
55
75
85
75
75
85
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
100%
40
65
65
40
65
65
55
75
75
55
75
75
30
50
50
40
50
50
55
75
75
55
75
75
22
32
32
22
32
32
50
57
57
50
75
75
84
143
220
84
143
220
121
165
220
121
165
220
84
143
220
84
143
220
121
165
220
121
165
220
84
143
187
84
143
187
121
165
187
121
165
187
84
143
143
84
143
143
121
165
165
121
165
165
B
B
B
J
J
J
B
25 to 35 ms
70 ms
20
20
20
10
10
10
10
10
10
10
10
10
10
10
10
20
20
20
15
15
15
15
15
15
10
10
10
10
10
10
10
10
10
10
10
10
9
9
9
8
8
8
10
10
10
7
7
7
6
6
6
10
10
10
7
7
7
6
6
6
front and rear connections
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
290x400x312
290x400x312
290x400x312
290x400x356
550x439x367
550x439x367
550x439x367
550x439x367
290x400x312
290x400x312
290x400x312
290x400x356
550x439x367
550x439x367
550x439x367
537x356x290
AB-07
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
AB32
AB40
AB50
AB63
3-4
3-4
3-4
3-4
3200
4000
5000
6300
3200
4000
5000
6300
1000
1000
1000
1000
8000
8000
8000
8000
690
690
690
690
H1
H2
H1
H2
H1
H2
H1
H2
75
100
75
100
100
150
100
150
75
85
75
85
85
85
85
85
100%
100%
100%
100%
100%
100%
100%
100%
75
75
75
75
100
100
100
100
75
75
75
75
100
100
100
100
75
75
75
75
100
100
100
100
165
220
165
220
220
330
220
330
165
220
165
220
220
330
220
330
165
187
165
187
187
187
187
187
165
165
165
165
220
220
220
220
B
B
B
J
J
J
J
25 to 35 ms
70 ms
15
15
10
10
10
10
5
5
4
4
3
3
2.6
2.6
2.5
2.5
2.6
2.6
2.5
2.5
front and rear connections
10
10
10
10
5
5
5
5
3
3
2
2
2.5
2.5
1.5
1.5
2.5
2.5
1.5
1.5
rear connections
J
J
J (3P only)
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
290x400x370
290x400x370
290x400x370
290x400x370
550x439x367
550x439x367
550x439x367
550x439x367
290x400x370
290x400x370
290x400x370
290x400x370
537x356x290
537x356x290
537x356x290
537x356x290
AB-08
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
Communication Network: Nirapod4.02H Controller
Through Modbus-Rtu, Profibus-DP or Device-Net.
The RS485 connection, address and baud rate can be set
through the programmer.
The “four remote” function, remote measuring, remote
communication, remote control, and remote modifying can be
realized through the communication interface.
ST-DP is the communication module. The master station card
is SIEMENS’s CP5X11,RTis the resistance of the network
terminal,usually 150 ohm.
Rt
RS232
RS485
Converter
Monitoring PC
NIRAPOD 4.02H
Modbus
Communication Module
To be used with the H type controller for converting from
Modbus-Rtu to Profibus -DP. Auxiliary power is AC/DC 220V
Dimension diagram:
Communication Interface T04
To be used in switchboard for communication connection with
the breaker.
(Encoded as 2 in the Switchboard diagram)
Communication Line
For the connection with various communication terminals, A
shielding twisted-pair is OK for this purpose. When ST-DP is
used, T215-01 is needed;when ST-DN is used, T415-01 is
used.
AB-09
NIRAPOD 4.02H
NIRAPOD 4.02H
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
drawout wiring diagrams
CHASSIS AUXILIARIES
CONTROL UNIT
- CN +
CN 1
BREAKER AUXILIARIES
Fu
N
P1
S1
P2
S2
AT
(4)
(2)
(4)
LR
alarm
fault
closed
BPF
open
springs
charged
Ic1 Ic2
(5)
372
374
352
354
362
364
disconnected
334
332
344
342
324
322
314
312
connected
ready
to
close
BPO
Z11 Z12
LR2
T2
T1
V2
R1
R2
e+
e-
82
84
212 222
234 244
12
14
22
24
32
34
42
44
D4
C12
C2
A4
252
254 262
B4
CE
or
T
F
V
F
XF
SR
OF
F
M
URV
SR
or
UVR-T
O O
CH
SDE
ammeter
processing
unit
CD
311
321
331
341
351
361
AT
BPO
BPF
LR
CR
T
CE
:
:
:
:
:
:
:
M
:
R
XF
T
:
:
:
SR :
UVR :
UVR-T:
OF
:
O
:
F
:
FTIC :
CMS :
F
:
FV :
PF
:
PF
C
R
CT
371
Z21
Z22 LR1
(3)
CN 1
ALR
F21 F1
V1
C
81 211 221
11
21
31
41
D1
C11 C1 A1
251
B1
power supply
(1)
Fu
- CN -
emergency off
"open" push button
"close" push button
long time trip (LT) indicating lamp
short time trip (ST) indicating lamp
earth fault trip indicating lamp
"connected" position contact
(10A/240V AC)
spring charging motor
(180V A/240V AC)
load monitoring and control
closing release (20V A/240V AC)
earth fault protection (EZ and SZ:
input and output for zone selective
interlocking)
shunt release (20V A/ 240V AC)
undervoltage release
(20V A/240V AC)
time delayed undervoltage release
(20V A/240V AC)
auxiliary changeover contacts
(10A/240V AC)
2 auxiliary NC contacts
(10A/ 240V AC)
2 auxiliary NC contacts
10A/ 240V AC)
fault trip indication contact
(10A/ 240V AC)
charging motor limit switch contact
fault trip local indicator
segregated fault trip indication contact
(5A/ 240V AC)
"ready to close" contact
(10A/ 240V AC) (closing possible if
breaker is open, not locked and
operating mechanism charged)
231 241
CD : "disconnected" position contact
(10A/ 240V AC)
CT : test position contact (10A/ 240V AC)
C : communication.
J Ic1: load shedding command according to
Ic1 setting
Ic2: load shedding command according to
Ic2 setting
J diagram shown with circuits deenergised,
breaker open and in "connected" position,
springs charged and relays in released
position
J accessories such as pushbuttons, lamps
and fuses are not supplied with the circuit
breaker.
Wiring of the UVR-T (modified diagram).
Instantaneous tripping with UVR-T when
contact 254-262 opens.
D4
254
262
UVR-T
D1
Note: the wiring of the external contact
replaces the spring charged indication
and the contact PF.
V contact wiring:
for breaker locking, depending on the
selected fault.
(1) Power supply terminals for I or T or F
options (AD module with BAT battery module
for backup power).
(2) Zone selective interlocking with line side
breaker.
(3) Zone selective interlocking with load side
breaker (remove jumper)
(4) DC power supply R contacts reset request
wiring of an external contact
(5) With Z and/ or C options, terminal 84 is
not available.
AB-10
CN1/CN +
BPO
V
C2
V
CN2/CN-
V
SR
C1
Selective locking needs:
* external power supply (F1, F2)
* an additional terminal (BS)
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
Wiring: NIRAPOD 4.02M
L1 1
N
PE
2
Breaker line side
UN U1 U2 U3
SB3 SB2 SB1
external mutual
inductor
2
4
6
8
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
QT SHT CC
7
9
13
15
17
19
21
23
25
27
29
31
33
Closed
wire
35
37
39
41
43
45
Under
voltage release
Intelligent controller
Energy
Main
power
47
Auxiliary switch
Energy
External terminals of
NIRAPOD 4.02M
Breaker line side
External
power supply
UN U1 U2 U3 External
mutual
inductor
1
2
4
6
8
10
12
14
16
18
20
22
24
3
5
7
9
11
13
15
17
19
21
23
25
AB-11
26
Together/close
5
Separate
3
Energy
Storage
1
Shunt off
and control
M
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
Wiring: NIRAPOD 4.02H
L1 1
N
PE
2
hub
T03
1
Profibus-DP
+
Connecting
wire
1
4
Red
Green
8
10 12 14
6
4
N
16
18
20
22
24
5
-
PE
ST Model IV
+
-
14 15
-
+
-
2
3
4
5
+
-
16 17
6
7
8
26
28
30
D01
12 13
D02
14 15
34
36
32
D03
16 17
+
18 19
9
DI1 DI2 DI3
D024V DC24V COM
Breaker line side
UN U1 U2 U3
2
3
L
-
12 13
ST-DP
Device
2
L N
+
10 11
ST201
18 19
38
40
42
44
46
QT SHT CC
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
39
41
43
45
Separate
3
Under
voltage release
Intelligent controller
Closed
wire
Energy
Main
power
Shunt off
and control
Energy
Storage
1
Auxiliary switch
Energy
External terminals of
NIRAPOD 4.02H
External
power supply
Breaker line side
UN U1 U2 U3 External
mutual
inductor
1
2
4
6
8
10
12
14
16
18
20
22
24
3
5
7
9
11
13
15
17
19
21
23
25
AB-12
26
47
Together/close
M
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
Installation: Fixed circuit breakers AB08 to AB32
dimensions
553
necessary space for removing
the arc chutes
(with or without arc chute cover
3 or 4 poles
438
493
378
90 130
45
311
(*)
(*)
30 mini
60 maxi
400
11
68
150
11
422 (3p)
290
515
11
11
537 (4p)
mounting
on a base plate
Panel cut-outs
mounting detail
holes for escutcheon
X14
155
B
268
A
X11
150
3 poles
150
400
A
B
30 mini
60 maxi
155
(*)
2 X11 x 6
4 poles
150
515
80 mini
27
37.5
80
mini
302
(*)
11 X5
172.5
172.5
22
Drawout circuit breakers AB08 to AB32
dimensions
"disconnected" position
3 or 4 poles
45
311
800
mini
128
60
(*)
55
101
175
325
55
435 (3p)
85
425
70
367
55
550 (4p)
(*)
mounting
Panel cut-outs
on a base plate
mounting detail
holes for escutcheon
ACB's side
X14
B
155
270
X11
101
175
A
B
A
3 poles
175
325
2 X11 x 6
155
75
4 poles
175
425
100
mini
ACB's basis
AB-13
268
55
302
65
100
mini
19
75
20
7 X3
172.5
172.5
17.5
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
installation: Fixed circuit breaker AB40
dimensions
819
necessary space for removing
the arc chutes
(with or without arc chute cover)
3 or 4 poles
90
45
553
759
493
130
311
(*)
(*)
30 mini
60 maxi
150
290
11
515
11
68
537 (3p)
11
780
11
802 (4p)
mounting
Panel cut-outs
on a base plate
mounting detail
holes for escutcheon
X14
B
155
268
A
X11
150
30 mini
60 maxi
50 maxi
3 poles
150
515
A
B
Drawout circuit breaker AB40
dimensions
3 or 4 poles
(*)
2 X11 x 6
4 poles
150
780
27
37.5
80 mini
155
80
mini
361
(*)
11 X5
202
22
202
"disconnected" position
45
439
484
(*)
800
mini
128
60
70
(1)
101
175
425
55
550 (3p)
85
60
367
350
350
55
815 (4p)
(*)
mounting
on a base plate
panel cut-outs
mounting detail
40
holes for escutcheon
40
ACB's side
30
155
350
270
150
(1)
101
175
175
155
75
350
2 X11 x 6 (3p)
6 X11 x 22 (4p)
100
mini
ACB's basis
AB-14
268
55
302
65
100
mini
75
19
20
7 X3
172.5
172.5
17.5
ISO 9001 : 2008 Certified
NIRAPOD 4
Air Circuit Breaker
installation
Fixed circuit breaker AB50-63
Dimension
necessary space for removing
the arc chutes
(with or without arc chute cover)
3 poles
90
45
819
759
130
311
(*)
(*)
30 mini
60 maxi
mounting
on a base plate
150
11
780
11
68
802
290
mounting detail
panel cut-outs
holes for escutcheon
X14
155
B
A
X11
150
30 mini
60 maxi
50 maxi
268
155
2 X11 x 6
3 poles
150
780
A
B
27
37.5
80 mini
11 X5
80
mini
361
202
202
22
Drawout circuit breaker AB50-63
dimensions
"disconnected" position
3 or 4 poles
70
45
484
(*)
800
mini
128
60
60
350
350
101
175
40
85
475
475
1045 (4p)
367
mounting
55
(*)
panel cut-outs
on a base plate
mounting detail
40
40
panel cut-outs
30
holes for escutcheon
ACB's side
350
152.5
150
350
(1)
101
55
815 (3p)
175
47
6 X11 x 22 (3p)
6 X11 x 33 (4p)
270
148.5
71.5
19
55
175
325
ACB's basis
AB-15
69
45 (1)
100
mini
18.5
11 X5
180
180
17.5
ISO 9001 : 2008 Certified
Bitoron-600
Compartmented LV Switchgear
incorporating NIRAPOD 4 circuit breakers
made in conformity to IEC60439.1
a complete low voltage
fully Type Tested Assemblies (TTA) for
- industry
- infrastructures
- construction
- utilities
Corporate Office : Baitul Abed
53 Purana Paltan (3rd Floor)
Dhaka-1000, Bangladesh.
Phones : 02-9559868, 9559826
Fax
: 02-956 2705
e-mail : info@adexbd.com
Web
: www.adexbd.com
Sales Office : Shakh Centre
56 Purana Paltan (3rd Floor)
Dhaka-1000, Bangladesh.
Phone : 02- 956 0626
Fax : 02- 956 2705
e-mail : sales@adexbd.com,
web : www.adexbd.com
Chittagong Office :
Bank Asia Bhaban (4th Floor)
69 Agrabad Commercial Area
Chittagong, Bangladesh.
Phone : 031-2523993
e-mail : adex_ctg@adexbd.com
web : www.adexbd.com
Factory :
West Dogri, Bhawal Mirzapur
Gazipur, Bangladesh.
e-mail : ael_works@adexbd.com
web : www.adexbd.com
Q3000-January’14-gd:pulin
ADEX ENGINEERING LIMITED.