Document 252772

GENERAL LEGEND
NOTES:
1.
2.
CONDUIT, CONCEALED IN FINISHED AREAS, EXPOSED
IN UNFINISHED AREAS.
1.
Work Included:
Construct complete, functional, electrical systems as shown on
these plans and described below. Coordinate all work with, owner,
engineer and other trades. Obtain and pay for any necessary
permits and fees for the electrical work.
2.
Existing site conditions:
Visit the site prior to bid and inform yourself as to all existing
conditions and limitations that may affect the work. No allowances
for extra expense will be made for neglecting to discover
conditions affecting this work.
CONDUIT BURIED OR EMBEDDED
4x4 FIR BLOCKING
CONDUIT BEND UP
CONDUIT BEND DOWN
1/4" Ø x 3"
LAG BOLT - TYP. OF 4,
SEE NOTE 1
CONDUIT STUBBED AND CAPPED
#
CONDUIT AND CONDUCTORS (OR CABLE WHERE
ALLOWED), SLASHES INDICATE NUMBER OF CONDUCTORS.
LONG SLASH IS NEUTRAL. # IS SIZE OF CONDUCTOR
(#12 IF NO NUMBER IS SHOWN) UNMARKED RUNS INDICATE
2#12. INCLUDE ADDITIONAL EQUIPMENT GROUND AS
INDICATED IN GENERAL NOTES ON THIS SHEET
SIZE CONDUIT PER N.E.C.
WALL STUDS
SIMPSON A34 FRAMING
ANGLE FILLED WITH (8)
8d x 1-1/2" NAILS - TYP.
AT EA. END OF 4x4 - SEE
NOTE 2.
6' - 0"
10
EXAMPLE - 4#10 CONDUCTORS IN 1/2"MIN. CONDUIT.
(1 OF THE 4 IS NEUTRAL) - IF REQUIRED BY
GENERAL NOTES INCLUDE ADDITIONAL #10 EQUIPMENT GND.
PANEL HOUSING
FEEDER # - SEE ONE LINE DIAGRAM FOR CONDUIT
AND CONDUCTOR SIZES.
FINISHED FLOOR
1
SCALE:
1/2"=1'-0
SURFACE PANEL MOUNTING
3.
ONE LINE LEGEND
CIRCUIT BREAKER
TRIP AMPS / # POLES SHOWN
30/3
100/3 90
FUSIBLE SWITCH - SWITCH AND
FUSE AMPS / # POLES SHOWN
2
MAGNETIC MOTOR STARTER WITH
O/L RELAY - NEMA SIZE SHOWN
JUNCTION BOX -- SIZE PER N.E.C.
4.
TRANSFORMER - RATINGS SHOWN
DELTA-WYE CONNECTION SHOWN
MECHANICAL EQUIP. DESIGNATION - UNIT
SUPPLIED UNDER MECH. SPEC.'S
POWER LEGEND
1/4" Ø x 1-1/2"
LAG BOLT - TYP. OF 4
SEE NOTE
FEEDER # - THIS # IS SHOWN
ON POWER PLANS TO IDENTIFY
THIS FEEDER
DUPLEX CONVENIENCE OUTLET MOUNTED +18" ABOVE
FINISH FLOOR TO BOX CENTER UNLESS NOTED OTHERWISE.
SUBSCRIPTS:
GFI - GROUND FAULT CIRCUIT INTERRUPTER
WP - WEATHERPROOF
IG - ISOLATED GROUND
CKT.#
WALL STUDS
x
PANEL HOUSING
FLOOR MOUNTED DUPLEX RECEPTACLE
SUBSCRIPTS: F = FLUSH
P = PEDESTAL
DOUBLE DUPLEX RECEPTACLE
CONNECTION POINT TO EQUIPMENT FURNISHED AND
INSTALLED UNDER THE MECHANICAL OR OTHER
SECTIONS OF THE SPECIFICATIONS.
FIN. FLOOR
SCALE:
1/2"=1'-0
EQ
2
RECESSED PANEL MOUNTING
60/2
F
NOTE :
60/40/2
1. MAINTAIN 12" HORIZ & VERTICAL CLEARANCE TO GAS PIPE(S)
2. MAINTAIN 36" HORIZ & 12" VERTICAL CLEARANCE TO WATER OR
SEWER
3. INSTALL ELECTRICAL SERVICE TRENCHES & JOINT SERVICE
TRENCHES IN ACCORDANCE WITH ALL UTILITY CO. STD'S.
INCLUDING MIN. DEPTHS, CLEARANCES, BACKFILL, GROUNDING,
AND PULL CORDS OR WIRES.
SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION
CODE SHOWN. "EQ" MEANS DETERMINE TERMINATION
FROM EQUIPMENT SUPPLIER.
FACP
FLEX ,FMC
FIRE ALARM CONTROL PANEL
FLEXIBLE METALLIC CONDUIT
#
SHADING THROUGH FIXTURE INDICATES BATTERY
FOR EMERGENCY LIGHTING
G, GND
GFI
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
#
SLASH MARK THROUGH FIXTURE INDICATES
RECESSED FIXTURE
IMC
INTERMEDIATE METALLIC CONDUIT
MIN.
MSB
MINIMUM
MAIN SWITCHBOARD
(N)
N, NEUT.
NC
NO
NIC
NM
NMT
NEW
NEUTRAL
NORMALLY CLOSED
NORMALLY OPEN
NOT IN CONTRACT
NON-METALLIC SHEATHED CABLE (ROMEX)
NON-METALLIC TUBING
WALL SWITCH -- MOUNT +48" AFF TO BOX CENTER
SUBSCRIPTS:
M = MOMENTARY CONTACT MD= MOTION DETECTOR
2 = DOUBLE POLE
D = DIMMER
3 = THREE WAY
K = KEY OPERATED
4 = FOUR WAY
T = TIME SWITCH
WP = WEATHERPROOF
a, b, ETC. = SWITCH OPERATES ALL FIXTURES
WITH SAME SUBSCRIPT
OL
OVERLOAD RELAY
PNL
PANEL
UNO
UNLESS NOTED OTHERWISE
DUAL HEAD EMERGENCY LIGHT - SEE LFS
WP
WEATHER PROOF
#
OPEN STRIP FLUORESCENT - SEE SCHEDULE
ILLUMINATED EXIT SIGN, QUADRANT(S) FILLED
INDICATE DIRECTIONS OF FACE(S). ARROW
INDICATES DIRECTIONAL ARROW ON SIGN. SEE
LIGHTING FIXTURE SCHEDULE TYPE "EXIT"
PRE-CAST CONCRETE
VALVE BOX
LL
Sx
FINISH GRADE
5/8" Ø x 10'-0"
COPPER CLAD
GROUND ROD
BURNDY TYPE "GAR"
GROUND CLAMP OR EQUAL
(ONE PIECE WITH SINGLE BOLT
UL LISTED FOR DIRECT BURIAL)
GROUND ELECTRODE CONDUCTOR
SEE 1-LINE
SCALE:
NONE
4
GROUND ROD INSTALLATION
ABBREVIATIONS
FIXTURE INTER TIE FOR MASTER/SLAVE WIRING OF
3-LAMP FIXTURES
#
CONDUIT(S)
SCHD 40 PVC
#
LOW LEVEL EXIT SIGN - SEE TYPE 'EXIT-LL"
Service continuity:
Maintain continuity of all electrical systems to all functioning areas
and processes in buildings being remodeled. Coordinate all
unavoidable outages with the owner. Keep such outages to a
minimum. Supply any necessary temporary wiring. Include any
cost for overtime work in your bid.
(R)
RA
RMC
REMOVE
RETURN AIR (HVAC EQUIP.)
RIGID METALLIC CONDUIT
SA
SWBD
SUPPLY AIR (HVAC EQUIP.)
SWITCHBOARD
XFMR
TRANSFORMER
+##
HEIGHT IN INCHES ABOVE FIN. FLOOR, INDOOR
HEIGHT IN INCHES ABOVE FIN. GRADE, OUTDOOR
ALL HEIGHTS ARE TO BOX CENTER
CHECK ALL SYMBOLS TO MAKE SURE YOU UNDERSTAND WHAT THEY
INDICATE ON THESE PLANS. SHEET E-1 IS A STANDARD SHEET
AND MAY INCLUDE SYMBOLS AND DETAILS NOT INCLUDED IN THIS
PROJECT.
1.
ALL CONDUCTORS SHALL BE COPPER WITH THWN/THHN
INSULATION UNLESS NOTED OTHERWISE
2.
PANEL AND EQUIPMENT FEEDERS: INDIVIDUAL
CONDUCTORS IN CONDUIT UNLESS NOTED OTHERWISE.
3.
BRANCH CIRCUIT WIRING: INDIVIDUAL CONDUCTORS IN
CONDUIT UNLESS NOTED OTHERWISE.
4.
USE THESE CONDUIT TYPES:
EXTERIOR OR INTERIOR WET LOCATIONS: EMT WITH
WATERTIGHT COMPRESSION CONNECTORS OR SCHEDULE 80 PVC
UNDERGROUND: SCHEDULE 40 PVC
LICENSE STAMPS
EQUIPMENT CONNECTIONS AND FIXTURE WHIPS - INTERIOR
DRY LOCATIONS: FLEX OR TYPE MC CABLE
Wiring methods:
See General Notes on this page.
CABINETS AND BUILT-IN FURNITURE: TYPE MC (METAL
CLAD) CABLE
11.
Conduit:
Interior: EMT
Exterior: RMC or Schedule 80 PVC.
Underground or embedded: Sched. 40 PVC with 4" sand bedding
and rock free backfill . Minimum burial depth per NEC /CEC
Table 300-5
Wiring devices: Furnish general duty commercial grade switches
and receptacles as manufactured by Hubbell , Eagle, Pass and
Seymour or Bryant. Furnish plates of high impact thermoplastic or
nylon. Supply gasketed weatherproof plates outdoors with vertical
cover mounted with hinge up. At interior unfinished areas furnish
cast metal plates that do not extend past edges of a surface
mounted box.
14.
Lighting fixtures: supply lighting fixtures as shown on the lighting
fixture schedule.
15.
Grounding:
Provide green insulated grounding conductors on all receptacle
branch circuits and panel feeder circuits. Ground all exposed
non-current carrying metallic parts of electrical equipment and
raceway systems. Ground metal sheathing and any exposed metal
vertical structural elements of buildings. Bond all metallic piping
systems to ground.
16.
HAZARDOUS AREAS: RMC
E.
WIRING METHODS FOR LOW VOLTAGE, CLASS 2 POWER LIMITED
CONTROL:
USE SAME METHODS AS SHOWN FOR NON-POWER LIMITED SHOWN
ABOVE EXCEPT LISTED CABLES TYPE CL2P MAY BE SUBSTITUTED
IN CONCEALED, INTERIOR, DRY LOCATIONS NOT SUBJECT TO
PHYSICAL DAMAGE.
PROJECT NAME
YIHA
STORAGE
GARAGE
KLAMATH, CA
95548
SHEET TITLE
ELECTRICAL
LEGENDS, DETAILS
Ground rods:
Provide copper clad steel ground rods not less than 3/4 inch
diameter, 10 feet long driven full length into the earth. Provide
exothermic welded connection or ground clamps UL listed for
direct burial.
17.
Notching: don't notch any building structural member without the
permission of the engineer or architect.
18.
Support:
Support lighting fixtures securely from building structure. Support
fixtures independently of the suspended ceiling. Secure all
electrical equipment including conduits and boxes securely from
building structure or floor slab. Meet all seismic support and
bracing requirements for CBC seismic zone 4.
19.
CONSULTANTS
INTERIOR OR EXTERIOR EXPOSED TO VEHICULAR TRAFFIC:
RMC
19.
13.
All ideas, designs, arrangements and plans indicated or represented by
this drawing are owned by, and the property of David PierceArchitect
and were created, evolved and developed for use on, and in conjunction
with, the specified project. None of such ideas, designs, arrangements or
plans shall be used by, or disclosed to any peson, firm or corporation for
any purpose whatsoever without the written permission of David Pierce
Architect.
INTERIOR CONCEALED AND EXPOSED: EMT
EQUIPMENT CONNECTIONS AND FIXTURE WHIPS - EXTERIOR
OR INTERIOR WET LOCATIONS: LIQUID TIGHT FLEX OR PVC
JACKETED TYPE MC CABLE
Circuit breaker panelboards:
Supply panelboards with bolt on breakers. Use only full, 1" frame
breakers. Tandem or double breakers are not acceptable. Panels
and breakers shall be rated to interrupt the maximum fault current
available at the panel location.
For every house is builded by some man; but
he that built all things is God. Hebrews 3:4
WIRING METHODS FOR POWER, LIGHTING AND NON-POWER
LIMITED CONTROL WIRING--USE THE FOLLOWING:
Conductors: Unless noted otherwise, supply copper conductors
with THWN / THHN insulation.
12.
95536
(707) 786-4266
FAX (707) 786-4966
9.
CONC. PULL BOX 24"x36"x30" DEEP (MIN.)
EXISTING
ELECTRICAL METALLIC TUBING
ELECTRICAL NONMETALLIC TUBING
#
8.
CONC. PULL BOX 17"x30"x12" DEEP (MIN.)
(E)
EMT
ENT
DIRECTIONAL FIXTURE, AIMING
DIRECTION SHOWN
#
Substitutions and Submittals :
Follow procedures described in the General Conditions.
CONC. OR FIBERGLASS PULL BOX 10"x17"x12" DEEP (MIN.)
LUMINAIRE, SEE LIGHTING FIXTURE SCHEDULE
POLE MOUNTED FIXTURE
24" MIN.
18" MIN.
7.
CONC. OR FIBERGLASS PULL BOX 13"x24"x12" DEEP (MIN.)
CONDUIT
CIRCUIT BREAKER
CURRENT LIMITING FUSE
CONDUIT ONLY, (WITH PULL ROPE)
COPPER
CEILING MOUNTED FIXTURE
(600V AND LOWER)
CABLE TV SERVICE CONDUIT
C
CB, BKR
CLF
CO
CU, Cu
LIGHTING LEGEND
WALL MOUNTED FIXTURE
TYPICAL CONDUIT TRENCH
TELEPHONE SERVICE CONDUIT(S)
TV
AMPERE
C.B. FRAME AMPERE RATING
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
AMPS INTERRUPTING CAPACITY
ALUMINUM
C.B. TRIP AMPERE RATING
ARMORED CABLE (BX)
CROSSING PIPE
3
SECONDARY ELECT. SERVICE CONDUIT(S)
T
A, AMP.
AF
AFF
AFG
AIC
Al
AT
AC
DUAL CHANNEL SURFACE RACEWAY OUTLETS WHERE
SHOWN
PLASTIC
WARNING TAPE
SCALE:
NONE
S
12" MULTI-OUTLET STRIP, LENGTH DRAWN TO SCALE,
RECEPTACLE SPACING IN INCHES SHOWN
WIDTH AS REQ'D
12" MIN.
PRIMARY (HIGH VOLTAGE) ELECT. SERVICE CONDUIT(S)
DISCONNECT SWITCH, NON-FUSED,
AMP RATING/NUMBER OF POLES INDICATED
FUSIBLE DISCONNECT SWITCH
SWITCH AMPS/FUSE AMPS/NUMBER OF POLES
INDICATED
FINISH GRADE
4" SAND
BEDDING
AND COVER
P
D.
Intent of drawings:
Drawings show approximate locations only. Contractor is
responsible for correct positioning of equipment, adequate
clearances and routing of conduits. Report any conflicting
conditions to the architect or engineer prior to proceeding with the
work.
SITE PLAN LEGEND
WIRE RECEPT. TO CKT # SHOWN USING #12 CONDUCTORS.
6' - 0"
CLOSE COORDINATION BETWEEN THE ELECTRICAL AND MECHANICAL
TRADES IS A PART OF THE WORK THAT IS REQUIRED BY THIS
CONTRACT. NO ALLOWANCE WILL BE MADE FOR OMISSIONS BASED
ON INCORRECTLY ASSUMING ANOTHER TRADE WILL BE PERFORMING
YOUR WORK. REFER TO THE SPECIFICATIONS AND CONFIRM YOUR
SCOPE OF WORK WITH THE GENERAL CONTRACTOR.
Comply with the National Electrical Installation Standards
published by the National Electrical Contractors Association.
(NECA) including the following:
NECA 1, Standard Practice of Good Workmanship in
Electrical Contracting
6.
CURRENT TRANSFORMER
B. THE MECHANICAL / ELECTRICAL INTERFACE:
C. STANDARD LEGENDS AND DETAILS:
Products:
Supply all new equipment. Only supply equipment listed by UL or
other nationally recognized testing laboratory. Like items of
equipment shall be the products of a single manufacturer.
GROUND
FOR METAL STUDS USE #12 SELF TAPPING
SHEET METAL SCREWS, SIX SCREWS ON
EACH SIDE.
A. ANY DEVIATION FROM THE APPROVED ELECTRICAL PLANS WILL
REQUIRE APPROVAL FROM THE ELECTRICAL DESIGNER OF RECORD,
PER CALIFORNIA BUSINESS & PROFESSIONS CODE.
Comply with applicable codes and standards including the
following:
The currently applicable California Electrical Code.
The currently applicable California Building Code
Requirements of state and local fire marshals.
Americans with Disabilities Act
5.
KEYNOTE
NOTE:
GENERAL NOTES
ELECTRICAL SPECIFICATIONS
HOME RUN, DESTINATION SHOWN
ON C.M.U. WALLS USE (4) 3/8"x 3-1/2"
EMBED HILTI HIT ANCHORS.
ON METAL STUD WALLS USE #12 SHEET METAL SCREWS.
DRAWING STATUS
PLAN
CHECK
REVISIONS
Sym. Description
Date
1
2
3
4
Penetrations:
Flash, counterflash, seal and make watertight any roof
penetrations. Grout and seal penetrations through floor slabs and
CMU walls. Provide paintable metal escutcheons in finished areas.
Install UL listed fire sealant at conduit penetrations through fire
rated partitions in accordance with an approved UL System.
5
6
7
8
20.
Construction observation:
Work is subject to observation by the engineer. Correct work to
comply with the plans and these specifications to satisfaction of the
engineer.
21.
Warranty:
As a minimum, guarantee all work for one full year from the date
of the owner's first beneficial use.
Checked By
22.
Final test:
Upon completion, perform a complete test and demonstration of
all systems in the presence of the engineer and owner. Remove
panel covers as requested by the engineer. Check for proper motor
rotation and panelboard load balance.
Job No.
H.MAURO
Drawn By
Scale
PRELIMINARY
NOT FOR
CONSTRUCTION
ELECTRICAL ENGINEER
317 Third Street, Suite 11
Eureka, CA 95501
(707)445-2163 tel
(707)445-2426 fax
AS NOTED
DPA11YIHA1
SHEET No.
E-1
NOTE:
INFORMATION PERTAINING TO EXISTING UNDERGROUND
FACILITIES AS SHOWN HEREIN IS FOR INFORMATION
PURPOSES ONLY. CONTRACTOR SHALL BE RESPONSIBLE FOR
CONTACTING ALL AGENCIES INVOLVED AND SHALL LOCATE
ALL FACILITIES PRIOR TO EXCAVATION IN ANY AREA.
KEY NOTES
NEW STORAGE GARAGE
SUPPLY GFCI TYPE CIRCUIT BREAKERS
(E) ADMIN. OFFICE
95536
(707) 786-4266
FAX (707) 786-4966
NEW PANEL B
For every house is builded by some man; but
he that built all things is God. Hebrews 3:4
RUN A SPARE 1-1/4"
EMPTY CONDUIT IN
TRENCH WITH PANEL B
FEEDER P2
Copyright
C
2011
All ideas, designs, arrangements and plans indicated or represented by
this drawing are owned by, and the property of David PierceArchitect
and were created, evolved and developed for use on, and in conjunction
with, the specified project. None of such ideas, designs, arrangements or
plans shall be used by, or disclosed to any peson, firm or corporation for
any purpose whatsoever without the written permission of David Pierce
Architect.
CONSULTANTS
(E) SHOP
LICENSE STAMPS
(E) SHOP PANEL
(E) METER / MAIN BKR
SERVICE PANEL
PROJECT NAME
SCALE:
1"=20'
1
ELECTRICAL POWER PLAN
YIHA
STORAGE
GARAGE
KLAMATH, CA
95548
(E) PG&E SERVICE DROP
120/240V, 1 PH, 3W
SHEET TITLE
ELECTRICAL
SITE PLAN
KWH
(E) COMBINATION METER/
MAIN BKR SERVICE PANEL
DRAWING STATUS
200A/2P MAIN BKR
PLAN
CHECK
NEW PANEL
(E) SHOP
PANEL
NEW 70/2 BKR
REPLACES (2)SPARE
20/1 BKRS
B
DO NOT BOND FEEDER
NEUTRAL TO GROUND
REVISIONS
GND
Sym. Description
Date
1
2
3
#8 Cu - IN CONDUIT
WHERE EXPOSED
4
5
6
(E) FEEDER - NO CHANGE
7
1-1/4"C - 3#4, 1#8G
BUILDING STEEL FRAME
(N) GND ROD
8
H.MAURO
Drawn By
Checked By
SCALE:
NONE
2
SINGLE LINE DIAGRAM
Scale
AS NOTED
DPA11YIHA1
Job No.
SHEET No.
E-2
LIGHTING FIXTURE SCHEDULE
TYPE NO:
DESCRIPTION:
A
96" INDUSTRIAL FLUORESCENT WITH WHITE
POWDER COAT REFLECTORS, AND WIRE GUARD
MOUNTING:
24" CHAIN SUSPENDED
(#LAMPS)TYPE: (2) FO32/750/ECO
BALLAST/VOLTS: ELECTRONIC LOW TEMP. START / 120
INPUT WATTS:
60
MFR CAT.#:
WILLIAMS 80-8-232-VBY-2-WG-8014-EBLO-120
KEY NOTES
BOND ALSO TO BUILDING STEEL FRAME - SEE 1-LINE DIAGRAM
TYPE NO:
DESCRIPTION:
B
48" GASKETED INDUSTRIAL FLUORESCENT - UL
LISTED FOR WET LOCATIONS - FIBERGLASS
HOUSING AND HIGH IMPACT ACRYLIC DIFFUSER
MOUNTING:
12" CHAIN OR CABLE SUSPENDED
(#LAMPS)TYPE: (1) FO32/750/ECO
BALLAST/VOLTS: ELECTRONIC LOW TEMP. START / 120
INPUT WATTS:
30
MFR CAT.#:
WILLIAMS 96-4-132-PC-WET/1-EBLO2-120
BRING BOTH EVENING USE AND SECURITY CIRCUITS TO ALL
FIXTURES SO THEY CAN BE EASITLY CHANGED IN FUTURE IF
DESIRED.
10
10
CONNECT EXIT SIGNS TO THE UNSWITCHED LEG OF LIGHTING
CIRCUIT B2
B3
B5
MOUNT THESE SWITCHES NEXT TO DOOR. LABEL THE ON POSITION
OF THE SWITCHES AS "AUTO" AND THE OFF POSITION AS "OFF".
TYPE NO:
DESCRIPTION:
C
WALL LIGHT - 13"W x 12"H - DIE CAST ALUMINUM
HOUSING - DARK BRONZE FINISH POLYCARBONATE LENS
MOUNTING:
WALL CENTERED ABOVE GARAGE DOORS
(#LAMPS)TYPE: (1) 70W METAL HALIDE
BALLAST/VOLTS: HPF / 120
INPUT WATTS:
95
MFR CAT.#:
DAYBRITE WLI070MDT
10
SHEET LEGEND
SEE ALSO SHEET E-1
CEILING MOUNTED, LOW VOLTAGE OCCUPANCY SENSOR - EXTENDED
RANGE, PASSIVE DUAL TECH. - SENSOR SWITCH CM-PDT-10
CLASS II LOW VOLTAGE WIRING TO MOTION SENSORS
INSTALL IN CONDUIT
GROUND ROD
WP
WP
PANEL"B"
+48
+48
+48
For every house is builded by some man; but
he that built all things is God. Hebrews 3:4
Copyright
C
2011
All ideas, designs, arrangements and plans indicated or represented by
this drawing are owned by, and the property of David PierceArchitect
and were created, evolved and developed for use on, and in conjunction
with, the specified project. None of such ideas, designs, arrangements or
plans shall be used by, or disclosed to any peson, firm or corporation for
any purpose whatsoever without the written permission of David Pierce
Architect.
CONSULTANTS
D
FLOOD LIGHT APPROX. 10" SQ x 7"D- DARK BRONZE
FINISH- DIE CAST ALUMINUM HOUSING
MOUNTING:
WALL MOUNT - ADJUSTABLE
(#LAMPS)TYPE: (1) 70W METAL HALIDE
BALLAST/VOLTS: HPF / 120
INPUT WATTS:
95
MFR CAT.#:
WILLIAMS FL2-PSMH-70-120
RELAY - POWER PACK
B1
FAX (707) 786-4966
TYPE NO:
DESCRIPTION:
10
PP
95536
(707) 786-4266
TYPE NO:
DESCRIPTION:
E
SMALL WALL LIGHT - POLYCARBONATE HOUSING
AND LENS - DARK BRONZE FINISH
MOUNTING:
WALL MOUNT AT HEIGHT SHOWN
(#LAMPS)TYPE: (1) 26W COMPACT FLUORESCENT
BALLAST/VOLTS: LO TEMP START / 120
INPUT WATTS:
26
MFR CAT.#:
DAYBRITE WL26CFU
B7
SEE SITE PLAN
]TYPE NO:
DESCRIPTION:
SCALE:
1
1/8"=1'-0
XE
COMBINATION ILLUMINATED EXIT SIGN /
EMERGENCY LIGHTING WITH 90 MINUTE BATTERY
BACK-UP. WHITE HOUSING, 6" RED LETTERS.
SINGLE OR DOUBLE FACED AS SHOWN, WITH
ARROWS AS SHOWN. LED ILLUMINATION WITH (2)
5.4 WATT HALOGEN LAMPS
MOUNTING:
WALL OR CEILING SURFACE AS SHOWN (CENTER
ABOVE DOORS)
(# LAMPS)TYPE: LED
BALLAST/VOLTS: /120
INPUT WATTS:
LESS THAN 5
MFR CAT.#:
WILLIAMS EXIT/EM-SF-R-WHT
WEIGHT:
LESS THAN 20 LBS
LICENSE STAMPS
ELECTRICAL POWER PLAN
NOTES:
1.
VERIFY ALL CATALOG NUMBERS. SUPPLY ALL MOUNTING
HARDWARE AND ACCESSORY ITEMS REQUIRED FOR A COMPLETE,
FUNCTIONAL INSTALLATION MEETING ALL REQUIREMENTS OF
THE DESCRIPTION AND THE SPECIFICATIONS.
2.
BALLASTS -- GENERAL:
SUPPLY U.L. LISTED BALLASTS COMPATIBLE WITH LAMPS SHOWN
ON FIXTURE SCHEDULE. ALL BALLASTS INSTALLED INDOORS
SHALL HAVE A CLASS A SOUND RATING UNLESS NOTED
OTHERWISE. ALL H.I.D. AND COMPACT FLUORESCENT BALLASTS
SHALL BE HIGH POWER FACTOR TYPE UNLESS NOTED OTHERWISE.
FLUORESCENT BALLASTS SHALL HAVE A CLASS P THERMAL
RATING.
EXTERIOR LIGHTING CONTROLLER
INTERMATIC ET8215C
s
E +84
+84
e E
+84 E
7-DAY, 2-CIRCUIT ASTRONOMIC
ELECTRONIC TIME SWITCH NEMA 1 ENCLOSURE
e
CKT #1:
B
A
e
A
A
A
e
B
CKT #2:
14
A
DUSK ON /
TIME OFF /
TIME ON /
DAWN OFF /
(EVERY DAY)
LCD DISPLAY
KEY PAD
3.
CKT 1
L
A
A
A
e
B
C NO NC
120V CKT B4
e
YIHA
STORAGE
GARAGE
KLAMATH, CA
95548
SHEET TITLE
ELECTRICAL
PLAN
BALLASTS -- ELECTRONIC: SUPPLY BALLASTS MEETING THE
FOLLOWING REQUIREMENTS:
BALLAST FACTOR EQUAL OR GREATER THAN 0.88
BALLAST CREST FACTOR LESS THAN 1.5.
TOTAL HARMONIC CURRENT DISTORTION LESS THAN 20%.
POWER FACTOR GREATER THAN 90%.
5 YEAR MINIMUM WARRANTY
CERTIFIED AS COMPLYING WITH THE CALIFORNIA ENERGY
COMMISSION STANDARDS
CKT 2
14
14
B
DUSK ON /
TIME OFF /
TIME ON /
DAWN OFF /
(SELECTED DAYS)
PROJECT NAME
C NO NC
N
DRAWING STATUS
PLAN
CHECK
B2
4.
14
A
A
A
e
XE
E
+84
e
D
EXTERIOR LIGHTING
CONTROLLER (ELR)
a b c d
A
B
PP
e
PANEL"B"
XE
B4 VIA ELR
eC
C s
C
e
C
e
s
s
s
e
e
e
FIXTURE PERFORMANCE
APPEARANCE
CONSTRUCTION MATERIALS
HOUSING DIMENSIONS INCLUDING DEPTH
FINISH
CORROSION AND VANDAL RESISTANCE WHERE APPLICABLE
E
s
s
B
ANY SUBSTITUTIONS FOR THE FIXTURES SPECIFIED WILL BE
CHECKED FOR EQUIVALENCE BASED ON THE FOLLOWING
CRITERIA AS A MINIMUM:
REVISIONS
Sym. Description
Date
1
2
3
4
+84
D
SCALE:
NONE
3
SUBMIT DETAILED INFORMATION REGARDING ANY PROPOSED
SUBSTITUTION INCLUDING PHOTOMETRIC DATA AND SHOP
DRAWINGS. THE ENGINEER RESERVES THE RIGHT TO REQUIRE THE
SUBMISSION OF FIXTURE SAMPLES WHERE APPEARANCE,
QUALITY, OR PERFORMANCE IS CRITICAL.
EXTER. LIGHTING CONTROL
(ELC) WIRING DIAGRAM
5
6
7
8
6.
LAMP MODEL NOS SHOWN ARE FOR SYLVANIA. ACCEPTABLE
ALTERNATE MANUFACTURERS ARE G.E. AND PHILLIPS.
H.MAURO
Drawn By
SCALE:
1/8"=1'-0
2
ELECTRICAL LIGHTING PLAN
Checked By
Scale
PRELIMINARY
NOT FOR
CONSTRUCTION
ELECTRICAL ENGINEER
317 Third Street, Suite 11
Eureka, CA 95501
(707)445-2163 tel
(707)445-2426 fax
AS NOTED
DPA11YIHA1
Job No.
SHEET No.
E-3